Section 3: Programming the 7845i-GSM
3-13
•
(V–), where a ground trigger causes an alarm for normally high connections
•
(EOLR) End of Line Resistor, where the input is supervised by an appropriate EOL resistor. The zone can be
triggered by NO or NC contacts, or open collector ground, or voltage trigger outputs
Inverted Trigger:
Zones can be programmed for inverted trigger, where the alarm and normal states of the zones are
inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports:
Zone inputs can be programmed for restore reporting, and for delayed reporting
(allowing time for the user to abort false alarms).
UL NOTE:
Zone restoral must be enabled.
Report Only if Armed option:
To help eliminate redundant reports, zone alarms can be restricted to report only if a
conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the
“arming” zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be
programmed as necessary in the control panel.
The conditional (arming) zone on the module is a different dedicated zone for each programming mode, as follows:
Mode
Conditional (Arming) Zone
Zone Trigger
7
4204 4
2-4204 8
IMPORTANT:
If any zone (zones 1-6 in zone trigger mode, zones 1-3 in 4204 mode, zones 1-7 in 2-4204 mode) is set for
Report Only if Armed, the conditional (arming) zone becomes unavailable for reporting (as it is reserved for the
“arming” trigger connection).
PROMPTS
ZONE
TRIG.
4204/
2-4204
ENTRY
OPTIONS
DESCRIPTION
28
Trip Inputs 1or2
w/Bell Out (N)_
✔
[Y], [N]
Use if the zone 1 connection to the control's bell
output causes a bell fault on the control panel.
NOTES:
1. If used, EOLR trigger type is not available
for zones 1 and 3.
2. Do not use with Lynx controls.
29
Telco Zone
(0)_
✔
✔
Zone Trig: [3-7]
4204: [1-4]
2-4204: [1-8]
[0] = not used
See Important Information Regarding Zone
Input Options on previous page.
Enter the zone number to be used for telco line
fault reports. This zone assignment must be
unique from the open/close zone selected in
Prompt 30.
Zone Trigger Mode:
If any zone is programmed
for "report only if armed," zone 7 cannot be
used. If Lynx Panic is enabled, zone 3 cannot
be used.
4204 Mode:
If any zone is programmed for
"report only if armed," zone 4 cannot be used.
2-4204 Mode:
If any zone is programmed for
"report only if armed," or if tamper is enabled,
zone 8 cannot be used.
NOTE:
Connect the telco line fault output (or
relay output programmed for "telco line fault") to
the telco zone.