4-1
.
S E C T I O N 4
Registration
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
Registering the 7845i-GSM
♦
Interactive Registration
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
Registering the 7845i-GSM
Once you have initialized and programmed the 7845i-GSM, it must be registered to enable
the account. An unregistered 7845i-GSM is indicated on the Status Display as: Status lit,
Message slow blinking, and Fault not lit.
FAULT, RED
MESSAGE, YELLOW
STATUS, GREEN
Figure 10. Unregistered 7845i-GSM Status Display In Normal Operation
Throughout this document, the following key is used to describe LED state:
ON
7845i-GSM-014-V0
OFF
FAST BLINK
SLOW BLINK
Figure 11. LED Key
To complete the registration process, a 7845i-GSM transmits a registration message and
receives a registration validation indicating that the account is now enabled.
Initiate the registration sequence by either clicking the Tamper Switch three times or by
pressing [shift] and the up arrow [
↑
] on the 7720P. If you are using a 7720P, skip to the
"Interactive Registration" paragraph in this section.
You can monitor the registration process by viewing the Status Display. The Message
(yellow) LED and the Status (green) LED will blink slowly in unison while registration is in
progress.
Once the registration has been completed successfully, the 7845i-GSM enters normal
operating mode; the Status (green) LED goes out and the Message (yellow) LED is lit to
indicate that the power-on / reset message is waiting to be sent. This message will appear at
the receiving station as “E339 8xx”, where “xx” is the ECP device address. The description
may read “Trouble – Exp. Mod. Reset”. If registration is not validated within 90 seconds,
the 7845i-GSM times out, and the (green) LED will be lit (solid).
The power-on/reset message will be sent in Ademco High-Speed format if the module is
programmed for zone trigger, 4204 or 2x4204 modes.