AQ255 AND AQ257 SERIES EXPANSION ZONING PANELS

69-1981—06

10

TROUBLESHOOTING

The following information helps the installer correctly identify 

system problems, making troubleshooting much faster. Table 3 

describes the possible error codes that can be communicated 

on the AQ155 / AQ157 Zoning Modules' DIAGNOSTIC LEDs.

Troubleshooting When Using 

Expansion Zoning Panels with an 

AQ2000 Series Control Panel

Communications Loss

Because all AQ2000 Series components communicate with 

each other via the dedicated AQUATROL network when 

controlling a hydronic system, one possible failure mode of an 

AQ25A, AQ251, or AQ252 Control Panel would be loss of 

communication between the Control Module and any 

connected Zoning Modules, or between a Zoning Module and 

any zone thermostats connected to the AQUATROL network. 

In general, the Control Module: 

• Periodically tries to re-establish communication with any lost 

components on the network.

• Initializes any component that re-establishes its 

communication.

• Displays an error code on the Control Panel’s System 

Status page, until the error is corrected and/or 

communication is re-established.

Control Module Reaction 

When the AQ25A, AQ251, or AQ252 control loses 

communication with any number of zones for more than one 

minute (as long as there’s still at least one zone communicating 

on the AQUATROL network), its Control Panel continues to 

deliver heat to the other non-communicating zones and the 

address of each lost zone (e.g., A-7, B-4) displays on the 

Control Panel’s System Status page.

When communication is lost with all zones, the AQ25A, 

AQ251, or AQ252 enters BOILER FREEZE PROTECTION 

mode, in which it fires the boiler and then activates the Boiler 

(supply) pump and zone equipment for a period of 10 minutes 

every hour. This should provide sufficient heat to the system to 

prevent a building from freezing up until communication is re-

established between the AQ2000 Series components.

Zoning Module Reaction 

When a Zoning Module loses communication with the Control 

Module (as long as there is at least one other Zoning Module 

communicating with the Control Module), the Zoning Module 

operates its pumps or valves in a conventional, non-

synchronized zoning fashion. That is, it operates according to 

the demands from the thermostats, without zone 

synchronization or waiting for permission from the Control 

Module to operate. This allows the zones to extract any heat 

provided by the boiler. 

When communication is lost between a Zoning Module and 

any of its thermostats, that zone is invisible to the Control 

Module. The Zoning Module stops serving that zone and the 

zone’s pump or valve de-energizes. Under this condition, the 

AQ2000 Series control operates in the same way as 

non-networked heating systems.

• The AQ250 provides Control Module diagnostic information 

via the DIAGNOSTIC LEDs located above the DIP switches 

on the AQ1500 Control Module. 

• The AQ25A, AQ251 or AQ252 presents Control Module 

diagnostic information on the Home Page display of its LCD. 

All AQ2000 Series Control Panels provide Zoning Module 

diagnostic information via the DIAGNOSTIC LEDs located 

above the DIP switches on their Zoning Module(s). 

Troubleshooting When Using 

Expansion Zoning Panels with 

AQ25A, AQ251, or AQ252 models

If a zone loses communication with the Control Module or is 

malfunctioning, this can be seen in the AQ25A/AQ251/AQ252 

Control Panel’s System Status Page. The System Status Page 

display indicates which zone has lost communication with the 

Control Panel (for diagnostics and troubleshooting).

If a zone has been permanently, and intentionally, 

disconnected from the network, turn off the Control Panel at 

the distribution panel and wait 10 seconds. Power the control 

back up and, as part of it’s boot up routine, the AQ25A/AQ251/

AQ252 will detect all equipment connected to the network. In 

doing this, the control no longer recognizes the disconnected 

zone and the LOST ZONE message disappears from the 

System Status page.

Table 3. AQ155 / AQ157 Zoning Module LED Display and System Condition.

DIAGNOSTIC LED Status

System Condition

Action Required

Steady (no blinking)

No system problem detected

None

Fast blinking (4 blinks per second)

Auto Test is in operation

None. Allow the control to finish its Auto Test 

routine.

Slow blinking (2 blinks every 3 seconds)

Auto Test has been paused.

Press the Test button to resume the Auto Test 

routine.

Coded blinking = ERROR 2 blinks,

then pause

Freeze protection activated 

across the entire AQUATROL 

network

All zones have lost communication with the 

Control Module. Check B–B wiring between the 

Control Module and each Zoning Module.

3 blinks,

then pause

Communication lost with all 

thermostats on the Zoning 

Module

Check thermostat wiring to each Zoning 

Module.

Summary of Contents for AQ15540B

Page 1: ...ransformer power supply module which connects to 120 Vac power and supplies 24 Vac power to the Zoning Module Communications between components via the AQUATROL network using communication bus wiring Any panel can be configured to activate a group pump when zones are active Zone valve models can be used with Normally Open or Normally closed valves Can be installed up to 500 ft away from main AQ200...

Page 2: ...o 110 C Inputs Outputs R C Input 24 Vac Class II R C Output on transformer AQ25742B and AQ25744B only 38 VA 24 Vac Class II Thermostat Compatibility Digital non communicating thermostats and or AQ1000 Series 2 wire communicating thermostats Dimensions HxWxD 8 0 x 9 4 x 3 3 in 20 3 x 23 8 x 8 5 cm approximate Weight 3 9 lb 1 8 kg Approvals Canadian Standards Association Certified File No LR76030 1 ...

Page 3: ...otally new family of hydronic controls And although they and other AQ2000 system components are very easy to install and operate they are different than other hydronic controls that you have previously installed Take a moment to read through this document before beginning the installation Failure to follow these instructions could damage the product or cause a hazardous condition Familiarize Yours...

Page 4: ...ert them into their slot to from a wiring channel between the Main Control Panel and the Expansion Zoning Panel see Fig 3 and to connect the two panels together 4 Install two top screws of the Expansion Zoning Panel ensuring it is level with the adjoining Main Control Panel and install two lower screws 5 Repeat steps 1 4 for any additional Expansion Zoning Panels Fig 3 Orientation of wire channel ...

Page 5: ...rminals is connected to which of the B B Exp Bus IN terminals 4 Wire the zoning equipment to the output terminals bot tom edge of the Expansion Zoning Panel line voltage circulators or valves for the AQ25542B and AQ25582B and low voltage zone valves for the AQ25742B and AQ25744B 5 Bring power to the Expansion Zoning Panel as follows a AQ25542B run 14 AWG jumper wires from the N and L terminals on ...

Page 6: ...c For the third Zoning Module connected to an AQ2000 Series Control Module make sure that DIP switch 3 is set to the right hand position ON and DIP switches 1 2 and 4 are set to the left d For the fourth Zoning Module connected to an AQ2000 Series Control Module make sure that DIP switch 4 is set to the right hand position ON and DIP switches 1 2 and 3 are set to the left 2 Review the settings for...

Page 7: ...els Auto Test AQ155 AQ157 Zoning Modules Auto Test operation for Zoning Modules enables the installer to test all zones wired to the Zoning Module by sequentially activating the zoning equipment connected to each zone output Each step of the Auto Test routine may be paused or skipped by pressing the Test button Table 2 AQ15540B Zoning Module Pump Zoning Module DIP Switch Arrangement DIP Switch Swi...

Page 8: ... with a delay of 1 10th of a second delay between each pump to minimize the effect of inrush currents from the pumps motors along with the main boiler pump When zone valves are tested simultaneously the valves are energized immediately but the boiler pump is energized only after either a the valves end switches close or b the TIME TO OPEN value in the EQUIPMENT SETUP ZONING menu has elapsed to all...

Page 9: ... and saved in the Installing Contractor s files SAVE Feature AQ25A AQ251 and AQ252 Control Panels In addition to the hardcopy Installation Job Records the AQ25A AQ251 and AQ251 Control Panels have a convenient SAVE feature that allows the installing contractor to save the specific equipment setting for this installation in the Control Panel s memory for future recall in case the system s settings ...

Page 10: ...mostats without zone synchronization or waiting for permission from the Control Module to operate This allows the zones to extract any heat provided by the boiler When communication is lost between a Zoning Module and any of its thermostats that zone is invisible to the Control Module The Zoning Module stops serving that zone and the zone s pump or valve de energizes Under this condition the AQ200...

Page 11: ...981 06 APPENDIX This appendix provides examples for wiring Expansion Zoning Panels to AQ2000 Series Control Panels and wiring additional low voltage VA capacity Wiring Diagrams Fig 5 Wiring of AQ25542B Expansion Zoning Panel to AQ2000 Series Control Panel ...

Page 12: ...AQ10X38 TRANSFORMER FROM B B EXP BUS OUT CONNECTION ON AQ1554P2 1 FROM C ON AQ10X38 TRANSFORMER THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 TH SENSOR TH SENSOR THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4 M27833C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4 AQ15540B 1 AQ15540B 2 AQ15540B 3 TO N ON AQ10X38 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION A...

Page 13: ...or recommended wiring of additional low voltage VA capacity to AQ2000 Series Zoning Modules CAUTION Equipment Damage Hazard Can damage internal circuitry of Zoning Module The ES1 and ES2 terminals of the AQ15740B Zoning Module are powered terminals and must only be connected to a set of dry contacts such as a zone valve motor s end switch If power is applied to these contacts for example by runnin...

Page 14: ...ZONE 4 M27835C M M M M M M M M FROM B B EXP BUS OUT CONNECTION ONAQ15540B 1 AQ15540B 1 AQ15540B 2 AQ10X38 120 V AC 1 POWER SUPPL Y PROVIDE DISCONNECT MEANSAND OVERLOAD PROTECTIONAS REQUIRED 1 N L AQ25742B ZONING MODULE OFAN EXISTING AQ2000 SERIES CONTROL P ANEL OK AQ15100B THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 TH SENSOR M27836C M M M M Zone 1 Zone 2 Zone 3 Zone 4 FROM B B EXP BUS OUT CONNECTION ...

Page 15: ...AQ255 AND AQ257 SERIES EXPANSION ZONING PANELS 15 69 1981 06 ...

Page 16: ...NELS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 69 1981 06 M S Rev 08 13 Printed in United States ...

Reviews: