AQ255 AND AQ257 SERIES EXPANSION ZONING PANELS

69-1981—06

8

STATUS LEDS

Every status LED light (Zone 1, Zone 2, Zone 3, Zone 4) will be 

turned on for 15 seconds when its corresponding output is 

activated during Auto Test.

DIAGNOSTIC LED

This light is used by the AQ155 / AQ157 to communicate 

diagnostic data to the user:

• Constantly ON indicates that the unit is working properly.

• Constant, fast blinking indicates that the unit is in the Auto 

Test mode. Constant, slow blinking indicates that Auto Test 

mode has been paused.

• Coded blinking is used to communicate an error code to the 

user. Refer to the Troubleshooting section of these 

instructions for an explanation of these codes.

NOTE: NOTE: The DIAGNOSTIC LED is OFF when the 

AQ155 / AQ157 Zoning Module is not powered.

Auto Test Sequence of Operation

1.

When the Auto Test button is pressed, Zone 1 of the 

Zoning Module energizes and the DIAGNOSTIC LED on 

the AQ155 / AQ157 begins to blink quickly. Zone 1 

remains energized for 15 seconds, then shuts off

2.

Following that, each of the remaining zones energizes 

sequentially (starting with Zone 2) for 15 seconds, and 

then shuts off.

3.

After Zone 4 de-energizes, the AQ155 / AQ157 exits the 

Auto Test routine and the DIAGNOSTIC LED on the 

Module returns to steady illumination (no blinking).

NOTE: This Auto Test routine works for Zoning Modules 

when connected to any AQ2000 Series Control 

Panel.

If no errors were detected in the Auto Test routine, the AQ255 / 

AQ257 is now ready for operation. If errors were detected, refer 

to “Troubleshooting” on page 10 for details.

Test Expansion Zoning Panels used 

with AQ25A, AQ251, and AQ252 

Control Panels

If this AQ255 / AQ257 Expansion Zoning Panel is connected to 

an AQ25A, AQ251 or AQ252 Control Panel, the Test and 

Check Out procedure can be done either manually (by 

following the preceding method outlined in the “Auto Test - 

AQ155 / AQ157 Zoning Modules” on page 7 of this document), 

or through the Control Panel’s Test and Purge tools. The TEST 

feature enables the installer to checkout the system's zone 

equipment as part of system commissioning (Checkout). 

NOTE: If checking out the operation of more than the 

newly-added Expansion Zoning Module, refer to 

the Product Data document for the main AQ2000 

Series Control Panel: AQ25A (form 69-2119), 

AQ251 (form 69-1974) or AQ252 (form 69-1986).

Test Zones

When TEST ZONES is selected, the Installer can test zones 

connected to the AQ25A, AQ251 or AQ252 (space heating and 

DHW) simultaneously or individually. 

If zones are tested simultaneously (TEST: ALL ZONES), zone 

pumps energize immediately (with a delay of 1/10th of a 

second delay between each pump to minimize the effect of 

inrush currents from the pumps' motors) along with the main 

boiler pump. 

When zone valves are tested simultaneously, the valves are 

energized immediately but the boiler pump is energized only 

after either:

a. the valves end switches close, or 

b. the TIME TO OPEN value (in the EQUIPMENT 

SETUP > ZONING menu) has elapsed, to allow 

enough time for the zone valves to fully open.

A zero (0) displayed after a zone's ID address (e.g., Zone A1 0, 

A2 0, … A16 0) indicates that the Control Module has received 

confirmation that the zone's pump relay is not energized or its 

zone valve is fully closed.

Similarly, a one (1) displayed after a zone's ID address (e.g., 

Zone A1 1, A2 1, … A16 1) indicates that the Control Module 

has received confirmation that the zone's pump relay is 

energized or its zone valve is fully open.

To test zones individually, position the indicator arrow (¬) 

beside a selected zone and press the “+” button to energize it, 

and then press the “–” button to de-energize it. As each zone is 

tested, the Status LED on the Zoning Module associated with 

that zone illuminates. To test additional zones, position the 

indicator arrow (¬) beside the zone to be tested, press the “+” 

button to energize the zone's pump or valve, and then press 

the “–” button to de-energize it. When finished testing the 

zones, press the MENU button to return to the SETUP >TEST 

AND PURGE menu.

6 PURGE AIR FROM ALL 

SYSTEM AND ZONE PIPING

For Expansion Zoning Panels connected to AQ250 Control 

Panels, continue with the “AQ250 Models” section.

For Expansion Zoning Panels connected to AQ25A, AQ251, or 

AQ252 Control Panels, go to “AQ25A, AQ251 and AQ252 

models” on page 9.

AQ250 Models

Purging air from all zones in the hydronic system can be easily 

accomplished with the AQ250 by using a modification to the 

AUTO TEST feature as follows:

1.

To purge all zones on the AQ250 network at the same 

time, press the TEST button on the AQ15000B Control 

Module. All zone equipment relays energize simultane-

ously and remain energized for the duration of the Auto 

Test routine.

2.

The AQ250 then begins its Auto Test routine, starting 

with energizing the Boiler pump.

3.

When the Boiler pump LED lights up, quickly press the 

TEST button to pause the Auto Test routine. The DIAG-

NOSTIC LED blinks slowly while in paused mode.

4.

The Boiler pump and all zones continue to be energized 

(and therefore are purging their loops of air) until the 

TEST button is pressed again.

5.

When the boiler loop has been purged sufficiently, press 

the TEST button again to energize the AUX relay. If there 

is a pump connected to the AUX output, press the TEST 

button again as soon as the AUX LED is illuminated, to 

perform the purge routine on the AUX loop. If the AUX 

Summary of Contents for AQ15540B

Page 1: ...ransformer power supply module which connects to 120 Vac power and supplies 24 Vac power to the Zoning Module Communications between components via the AQUATROL network using communication bus wiring Any panel can be configured to activate a group pump when zones are active Zone valve models can be used with Normally Open or Normally closed valves Can be installed up to 500 ft away from main AQ200...

Page 2: ...o 110 C Inputs Outputs R C Input 24 Vac Class II R C Output on transformer AQ25742B and AQ25744B only 38 VA 24 Vac Class II Thermostat Compatibility Digital non communicating thermostats and or AQ1000 Series 2 wire communicating thermostats Dimensions HxWxD 8 0 x 9 4 x 3 3 in 20 3 x 23 8 x 8 5 cm approximate Weight 3 9 lb 1 8 kg Approvals Canadian Standards Association Certified File No LR76030 1 ...

Page 3: ...otally new family of hydronic controls And although they and other AQ2000 system components are very easy to install and operate they are different than other hydronic controls that you have previously installed Take a moment to read through this document before beginning the installation Failure to follow these instructions could damage the product or cause a hazardous condition Familiarize Yours...

Page 4: ...ert them into their slot to from a wiring channel between the Main Control Panel and the Expansion Zoning Panel see Fig 3 and to connect the two panels together 4 Install two top screws of the Expansion Zoning Panel ensuring it is level with the adjoining Main Control Panel and install two lower screws 5 Repeat steps 1 4 for any additional Expansion Zoning Panels Fig 3 Orientation of wire channel ...

Page 5: ...rminals is connected to which of the B B Exp Bus IN terminals 4 Wire the zoning equipment to the output terminals bot tom edge of the Expansion Zoning Panel line voltage circulators or valves for the AQ25542B and AQ25582B and low voltage zone valves for the AQ25742B and AQ25744B 5 Bring power to the Expansion Zoning Panel as follows a AQ25542B run 14 AWG jumper wires from the N and L terminals on ...

Page 6: ...c For the third Zoning Module connected to an AQ2000 Series Control Module make sure that DIP switch 3 is set to the right hand position ON and DIP switches 1 2 and 4 are set to the left d For the fourth Zoning Module connected to an AQ2000 Series Control Module make sure that DIP switch 4 is set to the right hand position ON and DIP switches 1 2 and 3 are set to the left 2 Review the settings for...

Page 7: ...els Auto Test AQ155 AQ157 Zoning Modules Auto Test operation for Zoning Modules enables the installer to test all zones wired to the Zoning Module by sequentially activating the zoning equipment connected to each zone output Each step of the Auto Test routine may be paused or skipped by pressing the Test button Table 2 AQ15540B Zoning Module Pump Zoning Module DIP Switch Arrangement DIP Switch Swi...

Page 8: ... with a delay of 1 10th of a second delay between each pump to minimize the effect of inrush currents from the pumps motors along with the main boiler pump When zone valves are tested simultaneously the valves are energized immediately but the boiler pump is energized only after either a the valves end switches close or b the TIME TO OPEN value in the EQUIPMENT SETUP ZONING menu has elapsed to all...

Page 9: ... and saved in the Installing Contractor s files SAVE Feature AQ25A AQ251 and AQ252 Control Panels In addition to the hardcopy Installation Job Records the AQ25A AQ251 and AQ251 Control Panels have a convenient SAVE feature that allows the installing contractor to save the specific equipment setting for this installation in the Control Panel s memory for future recall in case the system s settings ...

Page 10: ...mostats without zone synchronization or waiting for permission from the Control Module to operate This allows the zones to extract any heat provided by the boiler When communication is lost between a Zoning Module and any of its thermostats that zone is invisible to the Control Module The Zoning Module stops serving that zone and the zone s pump or valve de energizes Under this condition the AQ200...

Page 11: ...981 06 APPENDIX This appendix provides examples for wiring Expansion Zoning Panels to AQ2000 Series Control Panels and wiring additional low voltage VA capacity Wiring Diagrams Fig 5 Wiring of AQ25542B Expansion Zoning Panel to AQ2000 Series Control Panel ...

Page 12: ...AQ10X38 TRANSFORMER FROM B B EXP BUS OUT CONNECTION ON AQ1554P2 1 FROM C ON AQ10X38 TRANSFORMER THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 TH SENSOR TH SENSOR THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4 M27833C ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 1 ZONE 2 ZONE 3 ZONE 4 AQ15540B 1 AQ15540B 2 AQ15540B 3 TO N ON AQ10X38 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION A...

Page 13: ...or recommended wiring of additional low voltage VA capacity to AQ2000 Series Zoning Modules CAUTION Equipment Damage Hazard Can damage internal circuitry of Zoning Module The ES1 and ES2 terminals of the AQ15740B Zoning Module are powered terminals and must only be connected to a set of dry contacts such as a zone valve motor s end switch If power is applied to these contacts for example by runnin...

Page 14: ...ZONE 4 M27835C M M M M M M M M FROM B B EXP BUS OUT CONNECTION ONAQ15540B 1 AQ15540B 1 AQ15540B 2 AQ10X38 120 V AC 1 POWER SUPPL Y PROVIDE DISCONNECT MEANSAND OVERLOAD PROTECTIONAS REQUIRED 1 N L AQ25742B ZONING MODULE OFAN EXISTING AQ2000 SERIES CONTROL P ANEL OK AQ15100B THERMOSTATS ZONE 1 ZONE 2 ZONE 3 ZONE 4 TH SENSOR M27836C M M M M Zone 1 Zone 2 Zone 3 Zone 4 FROM B B EXP BUS OUT CONNECTION ...

Page 15: ...AQ255 AND AQ257 SERIES EXPANSION ZONING PANELS 15 69 1981 06 ...

Page 16: ...NELS Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2013 Honeywell International Inc 69 1981 06 M S Rev 08 13 Printed in United States ...

Reviews: