Table 1. L4188/L6188 and L4191/L6191 models

INSTALLATION

IMPORTANT

Take care that installer is a trained experienced 

service man.

The L4188/L6188 and L4191/L6191 aquastats do 

not require lubrication.

Mounting 

Follow the mounting instructions supplied by the boiler or 

burner manufacturer when available.

Where no special instruction is given, follow the procedure as 

outlined below:

Drain the water from the heating system.

Screw the immersion well into a 

1

/

4

” or 

1

/

2

” pipe tapping 

and tighten (use a good wrench, do not use the device 

for this purpose).

Refill the heating system with water and test the 

immersion well for water tightness.

Insert the temperature sensor(s) into the well untill it 

bottoms and hold in position while securing with the 

screw provided.

Wiring

CAUTION

Disconnect power supply to prevent electrical shock 

and/or equipment damage.

Wiring must be in accordance with local regulations.

The appliance manufacturer’s instructions should 

always be followed when provided.

Remove the front cover and conduit box(es) and insert 

the cable through the conduit box(es).

Wire the thermostat into the circuit.

Mount the conduit box(es) and screw on the front 

cover.

ADJUSTMENTS 

WARNING

Adjustments must be made by qualified persons only.

If the appliance manufacturer supplies checkout and/ 

or service and maintenance instructions carefully 

follow them. If these instructions are not provided 

then use the procedure outlined below.

The L4188/L6188 and L4191/L6191 aquastats have 

been factory calibrated, field calibration should not be 

attempted.

Type

Temperature range (

°

C)

Switching  differential (

°

C)

Switch type

Setting means

L4188A

25 ... 95     
40 ... 110

4

SPST

Knob setting

L4188B

Internal setting

L6188A

25 ... 95    
40 ... 110    
70 ... 140

4 ... 10 (adjustable)

SPDT

Knob setting

L6188B

4    
4 ... 10 (adjustable)

Internal setting

L6188C

25 ... 95    
70 ... 140   

Manual reset

SPDT

Internal setting

L4191A

Controller
Limiter

25 ... 95

4

SPST

Knob setting
Internal setting

L4191B

Controller
Limiter

25 ... 95     
70 ... 140

4

SPST

Knob setting

Manual reset

SPDT

Internal setting

L6191A

Controller
Limiter

25 ... 95     
50 ... 95    
40 ... 110   

4     
4 ... 10 (adjustable)

SPDT

Knob setting

4

SPDT

Internal setting

L6191B  

Controller

Limiter

25 ... 95    
40 ... 110     
70 ... 140

4     
4 ... 10 (adjustable)

SPDT

Knob setting

50 ... 95    
40 ... 110    
70 ... 140

Manual reset

Internal setting

1
2

3

4

1

2
3