L7224U OIL ELECTRONIC AQUASTAT

®

 CONTROLLER

69-1720—03

6

Fig. 7. Explanation of display readout.

*Settings viewable on the 3-digit display only if the 
“Outdoor Reset Module” is installed.

Operation

The L7224U can be in any of four operational states: 
Normal, High Limit, Low Limit and Error. The controller 
moves back and forth from High Limit to Normal to Low 
Limit state as part of normal operation. The operating 
states are:

1.

Normal: Boiler temperature went below the High 
Limit setting (minus the Differential) and has not 
exceeded the High Limit setting; or, the boiler tem-
perature went above the Low Limit setting and has 
not gone below the Low Limit setting (minus the Dif-
ferential).

2.

High Limit: Boiler temperature went above the High 
Limit setting and has not dropped below the High 
Limit setting (minus the Differential).

3.

Low Limit: Boiler temperature went below the Low 
Limit setting (minus the Low Limit Differential) and 
has not gone above the Low Limit setting.

4.

Error: The controller has detected an error condition 
(e.g., open sensor) and has shut down the burner 
output. The Zone Control (ZC) output is energized. 
The controller continues to monitor the system and 
automatically restarts if the error condition clears. 
Refer to Table 4–6.

The operating sequence for the L7224U is shown in Table 
3.

High Limit Controller

The High Limit opens and turns off the burner when the 
water temperature reaches the setpoint. The High Limit 
automatically resets after the water temperature drops 
past the setpoint and through the adjustable Differential.

Low Limit and Circulator Controller

On a temperature rise, the burner circuit breaks and the 
circulator circuit makes (assuming no call for heat is 
present) at the Low Limit setpoint. On a temperature drop 
of 10° F (6° C) below the Low Limit setpoint (with the 
adjustable Differential at the minimum setting of 10° F 
(6° C)), the burner circuit makes and the circulator circuit 
breaks. Refer to Fig. 7.

Fig. 8. Setpoints and differentials.

Boiler Temperature

Description

Display

Shows

High Limit Differential 

Low Limit (L7224 only)

Low Limit Differential (L7224 only)

Local Thermostat Status

EnviraCOM Thermostat Status

Boost Step

Warm Weather Shutdown Temperature

M29552

ZR Configured as Domestic Hot Water 
Request (L7224, L7248L only)

Anti Short-Cycle Timeout

Outdoor Temperature Low

Outdoor Temperature High

Boiler Temperature Low

Boost Period

DISPLAY SHOWS LOCAL SETTING; NOT THE SETTING
AS MODIFIED BY AN EXTERNAL ENVIRACOM CONTROL.

SETTINGS ARE VIEWABLE ONLY IF THE OUTDOOR
RESET MODULE AND OUTDOOR TEMPERATURE
SENSOR ARE INSTALLED AND FUNCTIONING PROPERLY.

SETTINGS ARE VIEWABLE ONLY IF THE DOMESTIC
HOT WATER MODULE AND SENSOR ARE INSTALLED
AND FUNCTIONING PROPERLY.

1

2

3

Text

bt

HdF

LL

Ldf

tt

ttE

External Low Limit Enabled (L7248L only)

ELL

B1 (Burner) output (ON or OFF)

C1 (Circulator) output (ON or OFF)

ZR (Zone Request) Call for HEAT (ON or OFF)

ZC (Zone Control) output (ON or OFF)

brn

Cir

ZC

Zr

duu

ASC

otL

otH

btL

bP

bS

UUS

2

2

2

2

Input or Output is OFF

Input or Output is ON

Units are displayed in degrees Fahrenheit

Units are displayed in degrees Celsius

°F

°C

OFF

On

2

2

Outdoor Temperature

ot

2

DHW Module Connected (YES or NO)

dhc

3

2

Boiler Setpoint

bSP

High Limit

HL

1

Error Code (if one is present)

Err

LOW LIMIT 

SETTING

HIGH LIMIT

SETTING

SWITCH BREAKS ON 

TEMPERATURE RISE. 

BURNER TURNS OFF. 

CIRCULATOR OPERATES 

ON A CALL FOR HEAT.

SWITCH MAKES ON 

TEMPERATURE FALL.

BURNER OPERATES ON A 

CALL FOR HEAT.

WITH NO HEATING 

DEMAND, SWITCH  BREAKS 

ON TEMPERATURE RISE.

SWITCH MAKES ON 

TEMPERATURE FALL, 

BURNER IS ON TO 

MAINTAIN MINIMUM 

WATER TEMPERATURE. 

CIRCULATOR IS OFF.

M23365

WHEN WATER REACHES LOW LIMIT SETTING, THE BURNER SHUTS 

OFF OR THE CIRCULATOR PUMP STARTS (WHEN CALLING FOR HEAT).

1

1

10ºF (6ºC) 

DIFFERENCE

10ºF (6ºC) 

DIFFERENCE

Summary of Contents for Aquastat L7224U

Page 1: ...Relay 7 4 A at 120 Vac FLA 44 4 A inrush LRA Zone Controller ZC 7 4 A at 120 Vac FLA 44 4 A inrush LRA NOTE All loads combined cannot exceed 2000 VA Environmental Ratings Temperature 30 F to 150 F 34 C to 66 C Humidity 0 to 95 relative humidity noncondensing Approvals Underwriters Laboratories Inc Component Recognized Canadian Underwriters Laboratories Inc Component Recognized Accessories Ordered ...

Page 2: ... position or flush mounted remote from the well IMPORTANT Immersion well must fit sensing element and sensor must rest against bottom of well New Installation Order well assemblies separately refer to Table 1 and form no 68 0040 Immersion Wells and Compression Fittings for Temperature Controllers Boilers usually have tappings that allow the well to be mounted horizontally so boiler water of averag...

Page 3: ...f bag and work the open end of the bag all the way into the well Slowly pull out the bag while squeezing it firmly to distribute compound evenly in the well Bend the wiring if necessary to hold the sensor against the bottom of the well and to hold outer end of the sensor in firm contact with the side of the well See Fig 3 Wipe excess compound from the outer end of the well Fig 3 Position of sensor...

Page 4: ... connections to prevent electrical shock or equipment damage All wiring must comply with local electrical codes and ordinances Do not exceed the specifications in the Application section when wiring this controller IMPORTANT The terminals on these Aquastat Controllers are approved for use with copper wire only Follow the appropriate wiring diagrams shown on the inside of the front cover of the L72...

Page 5: ...econds Press the I button until the feature requiring adjustment is displayed HL_ High Limit Hdf High Limit Differential LL_ Low Limit Ldf Low Limit Differential duu ZR input configured as external Domestic Hot Water DHW request ON OFF ASC Anti Short Cycle Timeout seconds OFF is disabled otL Outdoor Temperature Low minimum parameter for the outdoor reset curve F or C otH Outdoor Temperature High m...

Page 6: ...t setpoint with the adjustable Differential at the minimum setting of 10 F 6 C the burner circuit makes and the circulator circuit breaks Refer to Fig 7 Fig 8 Setpoints and differentials Boiler Temperature Description Display Shows High Limit Differential Low Limit L7224 only Low Limit Differential L7224 only Local Thermostat Status EnviraCOM Thermostat Status Boost Step Warm Weather Shutdown Temp...

Page 7: ...mand ZR Domestic Hot Water DHW Request The ZR terminal on the L7224U can be selected to service an indirect water heater heat request This parameter is set via the 3 digit display see Adjusting Settings section of this document A heat request via the ZC terminal will have priority over all other features such as the Anti Short Cycle feature or those enabled by the Outdoor Reset Module See form69 2...

Page 8: ...with outdoor reset parameters enabled as programmed Error cleared automatically Error condition 11 System continues to run with boiler temp set to High Limit Table 4 L7224 Controller Operating Sequence with multiple zones connected through the ZR terminal Action System Response Zone Request ZR terminal is connected to L1 Zone calls for heat Boiler temperature is checked Burner starts when water te...

Page 9: ...leared WARNING Electrical Shock Hazard Can cause severe injury or death All circuits must have a common disconnect to prevent the possibility of electrical shock Aquastat Error Code Cause Action EnviraCOM Alarm Err1 Aquastat sensor fault check water sensor 18 Err2 ECOM fault check EnviraCOM wiring 18 Err3 Excessive electrical noise or frequency out of range Hardware fault replace controller 18 58 ...

Page 10: ...y is ON TT LED is ON B1 LED is ON 120 Vac at B1 B2 If no replace controller If yes check burner and wiring Display is ON TT LED is ON Refer to Err on display Boiler is hot house is cold Display is ON TT LED is ON C1 LED is ON 120 Vac at C1 C2 120 Vac at C1 C2 check wiring to pump Wiring ok is pump running If not replace the pump If pump is running check for trapped air or closed zone valves Displa...

Page 11: ...ING SCREW PROVIDED 2 3 L1 HOT L2 1 2 1 4 5 6 ZONE 2 LOW VOLTAGE THERMOSTAT R845A RELAY ZONE 2 ZONE 2 CIRCULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES C1 B1 ZC L2 LINE C2 ZR L1 B2 T T 3 2 1 SENSOR LINE VOLTAGE CIRCULATOR LINE VOLTAGE OIL BURNER RELAY 2 LOW VOLTAGE THERMOSTAT L7248L ENVIRACOM TERMINALS OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR SHOWN 3 4 1 2 3 OT OT C7089U OUTDOOR SENSOR ...

Page 12: ... 2 2 2 1 1 1 SENSOR LINE VOLTAGE CIRCULATOR L7224 3 4 3 3 5 BURNER MOTOR IGNITOR VALVE BURNER MOTOR IGNITOR VALVE CAD CELL JUNCTION BOX TO REMOTE ALARM CIRCUIT ENVIRACOM TERMINAL TH9421C R7184 LIMIT L1 L2 2 CAD CELL T T3 2 1 L1 HOT L2 1 LEGEND SCREW TERMINAL 1 4 IN 6 MM QUICK CONNECT TERMINAL SOLDERLESS WIRE CONNECTION VALVE IS OPTIONAL ON SPECIFIED MODELS ENVIRACOM TERMINAL 3 IS ALSO THE FIRST TH...

Page 13: ... lubricant compounds Section 3 Hazard Identification Acute Health Effects Skin Excessive contact may cause skin irritation and dermatitis Eye Direct contact with eye will cause irritation Inhalation No adverse effects are expected Ingestion Ingestion of product may cause nausea vomiting and diarrhea Chronic Health Effects Existing skin rash or dermatitis may be aggravated by repeated contact OSHA ...

Page 14: ...gles or faceshield if potential for eye contact exists especially if material is heated Hand Clothing Protection Not normally required Protective gloves and clothing are recommended as material is difficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility ...

Page 15: ...L7224U OIL ELECTRONIC AQUASTAT CONTROLLER 15 69 1720 03 ...

Page 16: ...olutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 69 1720 03 M S Rev 08 09 ...

Reviews: