background image

L7224U OIL ELECTRONIC AQUASTAT

®

 CONTROLLER

69-1720—03

8

Table 3. L7224/L7248 Controller Operating Sequence.

* Error condition only available when the Outdoor Reset 

Module is installed.

Action

System Response

Thermostat 
calls for heat.

Circulator starts when water temperature is 
above Low Limit setting (if applicable). 
Boiler temperature is checked. Burner 
starts when water temperature is below 
High Limit setting.
If Anti-short Cycle Time is enabled, the 
burner does not start until the set Anti-
short Cycle Time between cycles expires 
after the previous call for heat was 
satisfied.

Boiler 
temperature 
exceeds the 
High Limit.

Burner is turned off. Burner restarts when 
the water temperature drops below the 
High Limit setting minus the Differential.

Thermostat is 
satisfied.

Circulator and burner turn off.

Boiler 
temperature 
drops below 
the Low Limit 
setting minus 
the 
differential (if 
applicable).

Burner is turned on, Circulator is turned 
off. Burner stops when the water 
temperature exceeds the Low Limit 
setting.

Error 
conditions 
1-5.

If an error condition is detected, all outputs 
except ZC are shut down. Burner is off. 
The controller continues to function and 
restarts when error is corrected.
During the error check sequence, the 
system checks for drift in the sensor and 
corrosion in the connections.

Error 
condition 6.

EnviraCOM communication is not 
available.

Error 
condition 7.

The controller has reset the High Limit, 
Low Limit and Differential Setting to a 
default setting and will continue to run at 
those settings. Performance of the system 
will be degraded.

Error 
condition 8.

If the error condition is detected, all 
outputs except ZC are shut down. Burner 
is off.The controller continues to function 
and restarts when all three user keys have 
been pressed longer than 60 seconds.

Error 
condition 9*.

System continues to run with no outdoor 
reset functionality

Error 
condition 10*.

System continues to run with outdoor reset 
parameters enabled as programmed. 
Error cleared automatically.

Error 
condition 11*.

System continues to run with boiler temp 
set to High Limit.

Table 4. L7224 Controller Operating Sequence with 

multiple zones connected through the ZR terminal

Action

System Response

Zone Request (ZR) 
terminal is 
connected to L1 
(Zone calls for 
heat).

Boiler temperature is checked. 
Burner starts when water 
temperature is below High Limit 
setting. Anti Short-Cycle Time is 
applied, see Table 3.

Boiler temperature 
exceeds the High 
Limit.

Burner is turned off. Burner restarts 
when the water temperature drops 
below the High Limit setting minus 
the Differential.

Zone Request input 
is de-energized 
(Zones are 
satisfied).

Burner turns off.

Boiler temperature 
drops below the 
Low Limit setting 
minus the 
differential (if 
applicable).

Burner turns on and Zone Control 
is de-energized. Burner turns off 
and Zone Control is re-energized 
when the water temperature 
exceeds the Low Limit setting.

Table 5. Controller Operating Sequence with External 

Low Limit device connected trough the ZR terminal.

Action

System Response

Zone Request (ZR) 
terminal is 
connected to L1 
(External Low Limit 
call for heat).

Boiler temperature is checked. 
Burner starts when water 
temperature is below High Limit 
setting. Circulator turns off.

Boiler temperature 
exceeds the High 
Limit.

Burner is turned off. Burner restarts 
when the water temperature drops 
below the High Limit setting minus 
the Differential.

Zone Request input 
is de-energized 
(External Low Limit 
is satisfied).

Burner is turned off.

Table 6. L7224 Controller Operating Sequence with 

Domestic Hot Water connected trough the ZR 

terminal.

Action

System Response

Zone Request (ZR) 
terminal is connected to 
L1 (Domestic Hot Water 
calls for heat).

Boiler temperature is checked. 
Burner starts when water 
temperature is below High 
Limit setting.

Boiler temperature 
exceeds the High Limit.

Burner is turned off. Burner 
restarts when the water 
temperature drops below the 
High Limit setting minus the 
Differential.

Zone Request input is 
de-energized (Domestic 
Hot Water is satisfied).

Burner is turned off.

Summary of Contents for Aquastat L7224U

Page 1: ...Relay 7 4 A at 120 Vac FLA 44 4 A inrush LRA Zone Controller ZC 7 4 A at 120 Vac FLA 44 4 A inrush LRA NOTE All loads combined cannot exceed 2000 VA Environmental Ratings Temperature 30 F to 150 F 34 C to 66 C Humidity 0 to 95 relative humidity noncondensing Approvals Underwriters Laboratories Inc Component Recognized Canadian Underwriters Laboratories Inc Component Recognized Accessories Ordered ...

Page 2: ... position or flush mounted remote from the well IMPORTANT Immersion well must fit sensing element and sensor must rest against bottom of well New Installation Order well assemblies separately refer to Table 1 and form no 68 0040 Immersion Wells and Compression Fittings for Temperature Controllers Boilers usually have tappings that allow the well to be mounted horizontally so boiler water of averag...

Page 3: ...f bag and work the open end of the bag all the way into the well Slowly pull out the bag while squeezing it firmly to distribute compound evenly in the well Bend the wiring if necessary to hold the sensor against the bottom of the well and to hold outer end of the sensor in firm contact with the side of the well See Fig 3 Wipe excess compound from the outer end of the well Fig 3 Position of sensor...

Page 4: ... connections to prevent electrical shock or equipment damage All wiring must comply with local electrical codes and ordinances Do not exceed the specifications in the Application section when wiring this controller IMPORTANT The terminals on these Aquastat Controllers are approved for use with copper wire only Follow the appropriate wiring diagrams shown on the inside of the front cover of the L72...

Page 5: ...econds Press the I button until the feature requiring adjustment is displayed HL_ High Limit Hdf High Limit Differential LL_ Low Limit Ldf Low Limit Differential duu ZR input configured as external Domestic Hot Water DHW request ON OFF ASC Anti Short Cycle Timeout seconds OFF is disabled otL Outdoor Temperature Low minimum parameter for the outdoor reset curve F or C otH Outdoor Temperature High m...

Page 6: ...t setpoint with the adjustable Differential at the minimum setting of 10 F 6 C the burner circuit makes and the circulator circuit breaks Refer to Fig 7 Fig 8 Setpoints and differentials Boiler Temperature Description Display Shows High Limit Differential Low Limit L7224 only Low Limit Differential L7224 only Local Thermostat Status EnviraCOM Thermostat Status Boost Step Warm Weather Shutdown Temp...

Page 7: ...mand ZR Domestic Hot Water DHW Request The ZR terminal on the L7224U can be selected to service an indirect water heater heat request This parameter is set via the 3 digit display see Adjusting Settings section of this document A heat request via the ZC terminal will have priority over all other features such as the Anti Short Cycle feature or those enabled by the Outdoor Reset Module See form69 2...

Page 8: ...with outdoor reset parameters enabled as programmed Error cleared automatically Error condition 11 System continues to run with boiler temp set to High Limit Table 4 L7224 Controller Operating Sequence with multiple zones connected through the ZR terminal Action System Response Zone Request ZR terminal is connected to L1 Zone calls for heat Boiler temperature is checked Burner starts when water te...

Page 9: ...leared WARNING Electrical Shock Hazard Can cause severe injury or death All circuits must have a common disconnect to prevent the possibility of electrical shock Aquastat Error Code Cause Action EnviraCOM Alarm Err1 Aquastat sensor fault check water sensor 18 Err2 ECOM fault check EnviraCOM wiring 18 Err3 Excessive electrical noise or frequency out of range Hardware fault replace controller 18 58 ...

Page 10: ...y is ON TT LED is ON B1 LED is ON 120 Vac at B1 B2 If no replace controller If yes check burner and wiring Display is ON TT LED is ON Refer to Err on display Boiler is hot house is cold Display is ON TT LED is ON C1 LED is ON 120 Vac at C1 C2 120 Vac at C1 C2 check wiring to pump Wiring ok is pump running If not replace the pump If pump is running check for trapped air or closed zone valves Displa...

Page 11: ...ING SCREW PROVIDED 2 3 L1 HOT L2 1 2 1 4 5 6 ZONE 2 LOW VOLTAGE THERMOSTAT R845A RELAY ZONE 2 ZONE 2 CIRCULATOR TO ADDITIONAL R845A RELAYS FOR OTHER ZONES C1 B1 ZC L2 LINE C2 ZR L1 B2 T T 3 2 1 SENSOR LINE VOLTAGE CIRCULATOR LINE VOLTAGE OIL BURNER RELAY 2 LOW VOLTAGE THERMOSTAT L7248L ENVIRACOM TERMINALS OPTIONAL OUTDOOR RESET MODULE AND OUTDOOR SENSOR SHOWN 3 4 1 2 3 OT OT C7089U OUTDOOR SENSOR ...

Page 12: ... 2 2 2 1 1 1 SENSOR LINE VOLTAGE CIRCULATOR L7224 3 4 3 3 5 BURNER MOTOR IGNITOR VALVE BURNER MOTOR IGNITOR VALVE CAD CELL JUNCTION BOX TO REMOTE ALARM CIRCUIT ENVIRACOM TERMINAL TH9421C R7184 LIMIT L1 L2 2 CAD CELL T T3 2 1 L1 HOT L2 1 LEGEND SCREW TERMINAL 1 4 IN 6 MM QUICK CONNECT TERMINAL SOLDERLESS WIRE CONNECTION VALVE IS OPTIONAL ON SPECIFIED MODELS ENVIRACOM TERMINAL 3 IS ALSO THE FIRST TH...

Page 13: ... lubricant compounds Section 3 Hazard Identification Acute Health Effects Skin Excessive contact may cause skin irritation and dermatitis Eye Direct contact with eye will cause irritation Inhalation No adverse effects are expected Ingestion Ingestion of product may cause nausea vomiting and diarrhea Chronic Health Effects Existing skin rash or dermatitis may be aggravated by repeated contact OSHA ...

Page 14: ...gles or faceshield if potential for eye contact exists especially if material is heated Hand Clothing Protection Not normally required Protective gloves and clothing are recommended as material is difficult to remove from skin and clothing Other Protective Equipment None required Section 9 Physical and Chemical Properties Appearance Odor Aluminum color semi solid material pleasant odor Solubility ...

Page 15: ...L7224U OIL ELECTRONIC AQUASTAT CONTROLLER 15 69 1720 03 ...

Page 16: ...olutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 69 1720 03 M S Rev 08 09 ...

Reviews: