TECHNICIAN’S QUICK REFERENCE GUIDE

69-1957—1

L7224 Series

Oil Electronic 

Aquastat® Controller

The following service procedure provides a quick overview for 

L7224 Series Controllers. For more information, refer to form 

69-1384.

On the L7224U the High Limit, High Limit Differential, Low Limit, 

and Low Limit Differential can be adjusted to the settings 

recommended by the boiler OEM.

Adjusting Settings

To discourage unauthorized changing of Aquastat® settings, a 

procedure to enter the adjustment mode is required. To enter the 

adjustment mode, press the 

UP

DOWN

, and 

I

 buttons 

simultaneously for three seconds. Press the

 I

 button until the 

feature requiring adjustment is displayed:

HL—High Limit.

LL—Low Limit.

Ldf—Low Limit differential.

F - C—°F or °C.

Then press the 

UP

 and/or 

DOWN

 buttons to move the set point to 

the desired value. After 60 seconds without any button inputs, the 

control will automatically return to the READ mode.

To use the L7224U in a cold start boiler application, disable the 

Low Limit function by pressing the 

UP

 arrow button, 

DOWN

 arrow 

button and 

I

 buttons simultaneously for three seconds. Then push 

the 

I

 button until 

LL

 is displayed. Then press the down arrow 

button until 

OFF

 is displayed.

Display

In the RUN mode, the Aquastat® will flash “bt” (boiler temp) 

followed by the temperature (i.e., 220), followed by °F or °C.

To read boiler settings, press the 

I

 key to read the parameter of 

interest. For example, press 

I

 (HL) High Limit is displayed, 

followed by a three-digit number, i.e., 220, followed by °F or °C. 

69-1957-1.fm  Page 1  Tuesday, June 20, 2006  11:06 AM

Summary of Contents for AQUASTATIC L7224 Series

Page 1: ... High Limit LL Low Limit Ldf Low Limit differential F C F or C Then press the UP and or DOWN buttons to move the set point to the desired value After 60 seconds without any button inputs the control will automatically return to the READ mode To use the L7224U in a cold start boiler application disable the Low Limit function by pressing the UP arrow button DOWN arrow button and I buttons simultaneo...

Page 2: ...nviraCOM wiring Err3 Hardware fault replace control Err4 B1 fault check B1 wiring voltage Err5 Low Line Check L1 L2 110 Vac Err6 Fuse Check ECOM wires Replace fuse Err7 EEPROM HL LL Hdf Ldf Reset to default values Err8 Repeated B1 fault voltage present at B1 when output is turned off check B1 wiring voltage Boiler Temperature Text Description Display Shows bt High Limit HL Low Limit LL High Limit ...

Page 3: ...unction and restarts when error is corrected During the error check sequence the system checks for drift in the sensor and corrosion in the connections Error conditions 6 7 If error condition 6 or 7 occurs the control has reset the High Limit Low Limit and Differential Setting to a default setting and will continue to run at those settings Performance of the system will be degraded Error condition...

Page 4: ...at C1 C2 120 Vac at C1 C2 check wiring to pump Wiring ok is pump running If not replace the pump If pump is running check for trapped air or closed zone valves Display is ON TT LED is ON C1 LED is OFF ZC LED is ONb Boiler below the Low Limit temperature wait for boiler to go above Low Limit temperature Display is ON TT LED is ON ZC LED is OFFc Boiler above LL If yes check for 120 Vac between ZC an...