69-1957—1

2

L7224 SERIES

Pressing the I button again will display the 

LL

 (Low Limit) followed 

by a three-digit number and the corresponding degree designator. 

See the table below for an explanation of display readout.

After approximately 60 seconds without any key presses, the 

display will enter a dim display mode. To return to the bright 

display mode, simply press and release any key.

Table 1. LED Error Codes

Error Code

Cause/Action

Err1

Sensor fault; check sensor.

Err2

ECOM fault; check EnviraCOM. wiring.

Err3

Hardware fault; replace control.

Err4

B1 fault; check B1 wiring/voltage.

Err5

Low Line; Check L1-L2, 110 Vac.

Err6

Fuse; Check ECOM wires, Replace fuse.

Err7

EEPROM, HL, LL, Hdf, Ldf, Reset to default values.

Err8

Repeated B1 fault (voltage present at B1 when 

output is turned off); check B1 wiring/voltage.

Boiler Temperature

Text

Description

Display

Shows

bt

High Limit

HL

Low Limit

LL

High Limit Differential

Hdf

Low Limit Differential

Ldf

Local Thermostat Status

tt

Enviracom Thermostat Status

tte

Burner Status

brn

Circulator Status

cir

Zone Control

Zc

Zone Request

Zr

Error Code

err

Degrees Fahrenheit

 f

Degrees Celsius

M22149

 c

69-1957-1.fm  Page 2  Tuesday, June 20, 2006  11:06 AM

Summary of Contents for AQUASTATIC L7224 Series

Page 1: ... High Limit LL Low Limit Ldf Low Limit differential F C F or C Then press the UP and or DOWN buttons to move the set point to the desired value After 60 seconds without any button inputs the control will automatically return to the READ mode To use the L7224U in a cold start boiler application disable the Low Limit function by pressing the UP arrow button DOWN arrow button and I buttons simultaneo...

Page 2: ...nviraCOM wiring Err3 Hardware fault replace control Err4 B1 fault check B1 wiring voltage Err5 Low Line Check L1 L2 110 Vac Err6 Fuse Check ECOM wires Replace fuse Err7 EEPROM HL LL Hdf Ldf Reset to default values Err8 Repeated B1 fault voltage present at B1 when output is turned off check B1 wiring voltage Boiler Temperature Text Description Display Shows bt High Limit HL Low Limit LL High Limit ...

Page 3: ...unction and restarts when error is corrected During the error check sequence the system checks for drift in the sensor and corrosion in the connections Error conditions 6 7 If error condition 6 or 7 occurs the control has reset the High Limit Low Limit and Differential Setting to a default setting and will continue to run at those settings Performance of the system will be degraded Error condition...

Page 4: ...at C1 C2 120 Vac at C1 C2 check wiring to pump Wiring ok is pump running If not replace the pump If pump is running check for trapped air or closed zone valves Display is ON TT LED is ON C1 LED is OFF ZC LED is ONb Boiler below the Low Limit temperature wait for boiler to go above Low Limit temperature Display is ON TT LED is ON ZC LED is OFFc Boiler above LL If yes check for 120 Vac between ZC an...

Reviews: