Appendix
BC-200 Manual
– P/N DOC-01-013
101
9.4 R
ECOMMENDED
C
ABLING
R
EQUIREMENTS
9
9
.
.
4
4
.
.
1
1
R
R
S
S
-
-
4
4
8
8
5
5
R
R
I
I
N
N
G
G
C
C
O
O
M
M
M
M
U
U
N
N
I
I
C
C
A
A
T
T
I
I
O
O
N
N
C
C
A
A
B
B
L
L
I
I
N
N
G
G
Applies to:
Ring 1 communication lines
Annunciator communication lines
Requirements:
Style
Minimum 0.75mm
2
x 2 core Twisted Pair Shielded
communications cable
(+ separate 2 core cable for 24VDC module power )
Max distance
Communications cable: 1000M between modules with 1.5mm
2
cable
(24VDC power cable distance will be determined by voltage drop)
Notes:
Maximum of 16 annunciators between any two modules
Fire rated cables may be required as per AS1670, AS1668, AS2118
Note:
When annunciators or Field Modules are powered from external power supplies, use a separate conductor to
connect the main power supply common terminal (-0V) to the remote power supplies common terminal (-0V).
The EIA-485 circuit MUST be wired using a twisted-pair shielded cable. Do not run cable adjacent to, or in the
same conduit as, 240-volt AC service, noisy electrical circuits that are powering mechanical bells or horns, audio
circuits above 25 V
RMS
or motor control circuits. All enclosures, including the FIP cabinet, must be connected to
electrical earth! Never use the shield as an earthing conductor.
Terminate the shield at the outside of the FIP cabinet (ground). Where this is not possible, the shield must be
terminated to physical ground immediately adjacent to cable entry. Between Field modules, connect shields
together outside of their respective enclosures. Make sure that the shield is only grounded at the FIP and not at
the modules or annunciators. Do not ground both ends of the shield; one end should be left floating.
FIP Cabinet
Shield
Data Cable
Terminate the
shield at the
outside of the FIP
cabinet (ground).
Do not ground both
ends of the shield;
one end should be
left floating.
Do not connect
shields to modules or
annunciators.
Wire shields together
outside of the
respective
enclosures.
FIM
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......