background image

Appendix

BC-200 Manual

– P/N DOC-01-013

137

9

9

.

.

1

1

1

1

.

.

7

7

L

L

C

C

D

D

8

8

0

0

D

D

I

I

S

S

P

P

L

L

A

A

Y

Y

I

I

N

N

T

T

E

E

R

R

F

F

A

A

C

C

E

E

Note:

Both Operating Mode switches (SW4 & SW5) on the PCB must be set for ACS Mode (the UP position).

Event sounder:

Setting DIP Switch 1 of SW1 to OFF will disable the buzzer for alarms. Setting DIP Switch 2 of SW1 to OFF will
disable the buzzer for faults. Setting DIP Switch 3 of SW1 to OFF will disable the buzzer for Isolates. If the buzzer
is enabled, pressing the “MUTE” button will silence the buzzer until a new event is received.

Addressing Terminal Mode:

SW2 & SW3 set the address as per the table below. Note that “200” is added to the actual values of SW2 & SW3
to give an address in the range 201 – 239. Setting all switches to off will take the LCD-80 offline.

SW3-1

SW3-2

SW2

Actual Address

OFF

OFF

1 – 9

201 – 209

ON

OFF

0 – 9

210 – 219

OFF

ON

0 – 9

220 – 229

ON

ON

0 – 9

220 – 239

Addressing Annunciator Mode:

SW2 & SW3 set the address as per the table below. Note that “100” is added to the actual values of SW2 & SW3
to give an address in the range 101 – 139. Setting all switches to off will take the LCD-80 offline.

SW3-1

SW3-2

SW2

Actual Address

OFF

OFF

1 – 9

101 – 109

ON

OFF

0 – 9

110 – 119

OFF

ON

0 – 9

120 – 129

ON

ON

0 – 9

120 – 139

RS485 Comms
connector

24V Power
connector

SW3

SW2

SW1

SW4

SW5

Display

Isolates

Display

Alarms

Display

Faults

Next

Previous

Mute

10 SEPT 12:34

1/1

EAST WING
1.2.Z6

FAULT

A=0

F=1

I=0

Summary of Contents for BC-200

Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...

Page 2: ... version number if applicable Manual part number and revision found on the front cover Page number Brief description of the content you think should be improved or corrected Your suggestion for how to correct improve documentation Send email messages to techpubs notifier com au Please note this email address is for documentation feedback only If you have any technical issues please contact your ne...

Page 3: ...printed circuit board location Do not over tighten screw terminals Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging...

Page 4: ...r 15 4 3 12 LCD 80 Display interface 15 5 COMPATIBLE DEVICES 16 5 1 COMPATIBLE BATTERIES 16 6 SYSTEM CAPACITY AND EXPANDABILITY 17 6 1 BASE SYSTEM 17 6 2 EXPANSION PCBS 17 6 3 ANALOG ADDRESSABLE LOOPS 18 6 4 ANNUNCIATORS 18 6 5 FIELD MODULES 18 6 6 DISPLAY INTERFACES 19 7 PANEL OPERATION 20 7 1 FRONT PANEL DISPLAY 20 7 1 1 Selecting Screen Items 20 7 1 2 Scrolling Through Lists 20 7 1 3 Entering I...

Page 5: ...Main Termination Board FIM 110 9 6 2 CPU 114 9 6 3 Loop Interface Module LIM 115 9 6 4 Analog LCM and LEM Terminations 116 9 6 5 Networking 120 9 7 MODEM PRINTER HLI INTERFACE 124 9 7 1 Modem Interface 124 9 7 2 Printer Pager HLI Interface 125 9 8 BATTERY CALCULATIONS 127 9 8 1 Quiescent Current Calculation 127 9 8 2 Alarm Current Calculation 127 9 8 3 Battery Capacity Requirements 127 9 8 4 Power...

Page 6: ...ntional Zone Interface Module 148 9 13 11 6 x Relay Module 149 9 13 12 6 x Control Module 150 9 13 13 2 x Monitor 2 x Relay 151 9 13 14 Fan Controls Connection Diagram 152 9 14 NPS POWER SUPPLY CONNECTIONS 153 9 14 1 Connection to IFS 714 Termination Board 153 9 14 2 Connection to IFS 724 Termination Board 154 ...

Page 7: ... Alarm Select the Alarm using the PREV NEXT buttons Press ACK to acknowledge This will individually acknowledge alarms Once all alarms are acknowledged the alarm LED will go steady Resetting an Alarm Select the Alarm using the PREV NEXT buttons Press RESET then press ACK to confirm the resetting This will individually acknowledge and reset alarms Resets zone in alarm and clears all alarm inputs in...

Page 8: ... ready to power up the BC 200 Fire Indicator Panel Note When re booting the panel power off for at least 10 seconds or LCM modules might not operate correctly 2 2 POWER UP CHECKLIST Ensure batteries are disconnected Turn mains switch To ON After a few seconds some power up information should be displayed on the LCD screen which will then clear and display the alarm screen Under normal conditions t...

Page 9: ...al P N DOC 01 013 9 2 3 FAULT RECORD FAULT CORRECTION DATE TESTS SATISFACTORILY COMPLETED TESTED BY SIGNATURE DATE OF TEST If all faults have been rectified and all tests are completed satisfactorily the panel is now ready for operation ...

Page 10: ...n designing the system In addition to the RS 485 communication ring the panel can support up to 4 loops of Analog addressable points using Honeywell CLIP protocol Each loop can support 99 detectors and 99 modules In its maximum configuration the BC 200 can support 2 conventional zones and 72 programmable outputs on the main termination board 396 addressable detectors and 396 addressable modules wh...

Page 11: ...idity IP Rating IP 30 4 2 EMC INFORMATION WARNING This equipment may radiate radio frequency energy It may also be affected by radio frequency energy and if not installed and operated in accordance with the manufacturer s instructions may cause interference to radio communications It has been tested and found to comply with the Class A radiated and conducted EMI requirements of AS NZ 3548 1995 inc...

Page 12: ...l 105 to 135 of rated power auto recovery after fault removal Secondary Transformer Fuse 5A 15A N A N A N A Max Ripple 150mV p p 150mV p p 120mV p p 150mV p p 200mV p p Load Regulation 2 2 0 5 0 5 0 5 Line Regulation 2 2 0 5 0 5 0 2 Efficiency 80 80 82 84 88 Battery Test Internal 15 ohms Internal 15 ohms External Load External Load External Load Battery Test Relay Contact Rating 10A 15A N A N A N ...

Page 13: ...r and ground fault 4 4 3 3 3 3 P PA AN NE EL L E EX XP PA AN NS SI IO ON N R RE EL LA AY YS S Panel Expansion Relays XR IFS 717 Up to 64 x 30Vdc 1A non monitored relay contact outputs via 8 x IFS 717 relay boards 4 4 3 3 4 4 L LC CM M L LE EM M A AD DD DR RE ES SS SA AB BL LE E L LO OO OP P C CO ON NT TR RO OL LL LE ER R M MO OD DU UL LE ES S Minimum Nominal Maximum Operating voltage V dc 20 6 24 ...

Page 14: ...0mA max no relays energised 155mA max all relays energised IFS 711 15 to 28V DC 80mA max no relays energised 125mA max all relays energised 238mA max all AZF relays energised 43mA max no relays energised all AZF disabled Inputs 8 conventional alarm inputs Monitoring Open Circuit Alarm Fault Outputs 4 x ELV 1A relay contact outputs Max 30 VDC or 24 VAC Communications Link EIA485 on dual ports Indic...

Page 15: ...s Link EIA485 multi dropped 4 4 3 3 1 11 1 L LD DM M R R3 32 2 A AN NN NU UN NC CI IA AT TO OR R Supply Input 20V to 28Vdc 40mA Standby 200mA Alarm 32 relays energised Communications Link EIA485 multi dropped Relay contacts max 1A 30Vdc 4 4 3 3 1 12 2 L LC CD D 8 80 0 D DI IS SP PL LA AY Y I IN NT TE ER RF FA AC CE E Supply Input 20V to 28Vdc 100mA Standby 100mA Alarm Communications Link EIA485 mu...

Page 16: ...ries SLA CJ12 26 12 26 2 Olympic Batteries SLA CJ12 33 12 33 2 Olympic Batteries SLA CJ12 40 12 40 2 Olympic Batteries SLA CJ12 85 12 85 2 Olympic Batteries SLA CJ12 100 12 100 2 NOTES Automotive batteries must not be used There is a risk of explosion if battery is replaced by an incorrect type Dispose of used batteries according to Manufacturer Instructions The use of Nickel Cadmium batteries is ...

Page 17: ...d if total module load exceeds 2A Power supplies up to 11 7A are available 2 Local AZF s AZF 1 AZF 2 2 RS232 communication ports Laptop interface System event printer Remote terminal mode Keyboard Interface PS2 QWERTY IBM PC keyboard System Memory Approx 4300 Named points Approx 4000 Control scripts 4000 History events 6 2 EXPANSION PCBS Item Description Notes Loop Interface Module LIM Interface m...

Page 18: ...tor 32 x LED outputs Open Collector LDM R32 Annunciator 32 x Relay outputs rated to 1A 30Vdc 6 5 FIELD MODULES Item Description Notes AZM 8 8 x AZF inputs 4k7 EOL resistor 4 x Programmable Relay Outputs A maximum of 100 field modules can be connected to the communications ring Larger external power supplies and separate feeds are required for systems with a large number of modules or long cable ru...

Page 19: ...s LCD80 Terminal mode display interface see LCD 80 manual A maximum of 32 display interfaces can be installed on the communications ring Address 201 to 239 LCD80 Annunciator mode display interface see LCD 80 manual A maximum of 32 display interfaces can be installed on the communications ring Address 101 to 139 ...

Page 20: ...sist Fire fighters during a response The thick red border signifies the fire fighters area and provides alarm based functions for the fire fighter The mode select buttons bottom right will toggle the system in between fire fighters mode and the service menu where routine service and diagnostic tests can be performed If there are any active and unacknowledged alarms on the system the system will sw...

Page 21: ...d ring and the Analog addressable loops are real points Distributed points on field modules are controlled and referred to in R M IO format i e Ring Module I O where I O can consist of input output or AZF Analog addressable points on the addressable loops are controlled and referred to in Loop I O format i e Loop I O where I O can consist of module or detector number Virtual points are referred to...

Page 22: ...n 1 1 I1 3 Din Per Fan Control Module Dout 1 1 O1 4 Dout Per AZM 8 3 Dout Per Fan Control Module Description Syntax Comments Annunciator Up to 50 Annunciators Inputs 1 101 I1 16 Din per 16AT 24 Din Per SCS 8 Outputs 1 101 O1 32 Dout Per 16AT 24 Dout Per SCS 8 32 Dout Per ACM32A Analog Addressable Devices Up to 4 Loops Detectors L1D1 99 Detectors Per Loop Modules L1M1 99 Modules Per Loop Virtual Po...

Page 23: ...s have 100 added to them I e an annunciator set to address 1 is recognised as module address 101 Annunciators are simply treated as digital inputs and digital outputs to the system Each button press or switch position is considered as an input each LED is considered as an output Example 1 If an ACM32A annunciator is installed and addressed as 1 The last red LED on it would be referred to as 1 101 ...

Page 24: ... per AS4428 you will be requested to press ACKN to confirm the reset Any other button will abort the reset The point is automatically acknowledged by this action Once an alarm is reset it will be removed from the screen however if the alarm condition is still present it will re alarm after a 15 second time out ISOL Will perform a point isolate function on the currently highlighted alarm As per AS4...

Page 25: ...st 1 Alarm 2 Fault 3 Isolated 4 Active 5 Prealarm 6 List 1 Zone 2 Azf 3 Dout 4 Din 5 Virtual 7 Analog 7 History 8 Shadow 9 Group 1 Isolated 2 Zone 3 Azf 4 Dout 5 Din 6 Virtual 1 List 2 Status 3 Change 4 Remove 5 Loop 6 Netpoint 9 Module 7 Analog 8 Range 6 Walk 3 Fault 4 Dout 5 Battery 2 Azf 3 Dout 4 Din 5 Virtual 8 Change 7 Analog 1 Zone 2 Alarm 1 Azf 8 Ring 6 Netpoint 6 Analog 7 Fault 0 Network ...

Page 26: ...Time 3 Day Night 4 Passwords 1 Alarm List 2 Fault List 3 Isolate List 4 Active List 5 History 6 Script 1 Network 2 Status 3 Node 4 Receive 1 Stats 9 History 7 Analog 8 Ring Modules 3 Flash 4 Relay 5 Xrelay 6 Led 8 Local 7 Module 2 Dbase Erase Sectors Restart System Service Menu Deisol All Isol 5 Options 6 Print ...

Page 27: ...NU button at any time will return you to this main menu screen unless there are unacknowledged alarms present in the Fire Fighters screen 1 LIST LIST POINT INFORMATION 2 ISOLATE ISOLATE DEISOLATE POINTS 3 CONFIG CONFIGURE MODULES POINTS 4 ANALOG ADDRESSABLE LOOP FUNCTIONS 5 TEST TEST FUNCTIONS 6 GLOBAL CONFIGURE SYSTEM PARAMETERS 7 PRINT VARIOUS PRINTING UTILITIES 8 DIAG VARIOUS DIAGNOSTIC TESTS 9...

Page 28: ... order and allows you to acknowledge reset and isolate fault points using the soft buttons ISOLATED Displays all currently isolated points on the system and provides a soft button for de isolation ACTIVE Displays all active Non Alarm events on the system in chronological order and allows you to acknowledge reset and isolate points using the soft buttons PREALARM Displays all active Pre Alarm event...

Page 29: ...T FAULT This list will display all system faults in chronological order If faults are set as non latching they will self clear from this list If faults are set to latching a reset action from this list is the only way to clear them Once a fault is isolated it remains in the fault list but does not operate the fault outputs Faults on Analog points will also indicate a fault code as shown in the exa...

Page 30: ...points that are currently active If points are set as latching this is where they will need to be manually reset If points are non latching they will self clear ACTIVE LIST 20 JULY 2002 14 44 37 RESET ACKN NEXT PREV ISOL TIME TYPE STATUS NUMBER 20 JULY 10 00 SMOKE ACTIVE 1 OF 2 L1D1 PENTHOUSE 20 JULY 12 15 HEAT ISOL ACTIVE 2 OF 2 1 10 Z1 STAIRWELL A 0 F 0 I 1 N 2 DAY MODE Actions Use the PREV and ...

Page 31: ...THOUSE 20 JULY 12 15 HEAT ISOL ACTIVE 2 OF 2 L1D2 STAIRWELL A 0 F 0 I 1 N 2 DAY MODE Actions Use the PREV and NEXT buttons to scroll through the list Use ACKN to acknowledge currently selected active pre alarm point Use RESET to reset the currently selected pre alarm point You will be asked to press ACKN to confirm press any other button to abort Use ISOL to isolate the currently highlighted activ...

Page 32: ...O SELECT A ZONE A 0 F 0 I 0 N 0 CHANGE DAY MODE Actions Use the UP and DOWN buttons to scroll through the zone list Use the CHANGE button to edit a zone name and to view its membership Use the BACK button to return to the previous screen Note You can also use the arrow keys the Page Up and Page Dn keys on an external keyboard for scrolling functions 7 3 3 6 1 SERVICE MENU LIST LIST ZONE CHANGE On ...

Page 33: ...TO SELECT LOOP DAY MODE BACK UP DOWN Actions Use the UP and DOWN buttons to scroll through the Analog loop list Use the SELECT button to select the loop to list Alternatively press 1 through 4 Once you have selected the loop you will be prompted to select detectors or modules as follows SELECT DEVICE ON LOOP 1 1 DETECTOR 2 MODULE ANALOG LIST DETECTOR MODULE 20 JULY 2002 14 44 37 A 0 F 0 I 0 N 0 SE...

Page 34: ...1D4 APARTMENT 1 BEDROOM L1D5 APARTMENT 2 BATHROOM L1D6 APARTMENT 2 LIVING AREA L1D7 APARTMENT 2 BEDROOM L1D7 SECURITY OFFICE L1D8 CARPARK DETECTOR 1 I L1D9 CARPARK DETECTOR 2 L1D10 CARPARK DETECTOR 3 L1D11 LIFT MOTOR ROOM L1D12 NOT INSTALLED L1D13 NOT INSTALLED L1D14 NOT INSTALLED L1D15 NOT INSTALLED L1D16 NOT INSTALLED ANALOG LIST DETECTORS A 1 F 1 I 1 N 0 01 OCT 1999 14 44 37 DOWN UP 01 OCT 1999...

Page 35: ...ST Menu NEXT RESET Note Zxxx is displayed after the descriptor xxx is the zone number mapped to the detector A zone number of 0 is an indication that the detector is not mapped to a zone Actions Press the PREV buttons to move to the previous installed point Press the NEXT buttons to move to the next installed point Press the TEST button to enter test menu for the detector Press the RESET button to...

Page 36: ...o return to the read status screen Note Each time a test is performed the screen will automatically return to the STATUS screen so the data becomes live once again To perform another test simply press TEST again 7 3 3 7 1 3 Service Menu List List Analog Detectors Change This screen will allow you to change Analog addressable detector information and options on a point by point basis SELECTED POINT...

Page 37: ...LLED L1M6 NOT INSTALLED L1M7 NOT INSTALLED L1M8 NOT INSTALLED L1M9 NOT INSTALLED L1M10 EWIS OUTPUT 1 L1M11 EWIS OUTPUT 2 L1M12 NOT INSTALLED L1M13 NOT INSTALLED L1M14 NOT INSTALLED L1M15 NOT INSTALLED L1M16 NOT INSTALLED ANALOG LIST MODULES A 0 F 0 I 0 N 0 01 OCT 1999 14 44 37 DOWN UP 01 OCT 1999 14 44 37 UP 20 JULY 2002 14 44 37 DOWN UP STATUS CHANGE BACK DAY MODE Actions Use the UP and DOWN butt...

Page 38: ...u NEXT RESET Actions Press the PREV buttons to move to the previous installed point Press the NEXT buttons to move to the next installed point Press the TEST button to enter test menu for the detector Press the RESET button to re initialise the detector Press MENU to return to the Analog Menu screen Explanations of terms Variable Range Description Poll Mode CLIP Shows the current polling protocol ...

Page 39: ...useful for locating detector detectors at same address Press the OFF button to return module LED s to the Automatic Polling Mode Press the ALARM button to perform an ALARM TEST on the module Press the FAULT button to perform an FAULT TEST on the module Press the STATUS button to return to the read status screen If the module is an Output Module L1M10 EWIS OUPUT 1 Poll Mode FlashScan Mode Programme...

Page 40: ...can be used for number entries only When entering device type an option pick list will appear at the bottom of the screen Refer to appendix for more information on options You will be prompted Yes No to save changes when finished Output modules SELECTED POINT L1M10 NAME EWIS OUTPUT 1 DEVICE TYPE FRM 1 CMX 2 RELAY O P ANALOG MENU PROG A 0 F 0 I 0 N 0 20 JULY 2002 14 44 37 BACKSP ENTER PLEASE ENTER ...

Page 41: ...ERVICE MENU LIST LIST RING MODULE LIST Once you have selected the ring the following screen will appear MODULES FOUND ON RING 1 001 002 003 004 005 006 007 101 102 103 MODULE LIST 20 JULY 2002 14 44 37 NEXT PREV SELECT USE BUTTONS TO SELECT A MODULE A 0 F 0 I 0 N 0 DAY MODE Actions Use the PREV and NEXT buttons to scroll through the list of active modules Use the SELECT button to select the curren...

Page 42: ...DE Actions Use the PREV and NEXT buttons to scroll through I O points The point s descriptor will display at the bottom of the screen when each point is highlighted When highlighting an AZF input point pressing the TEST button will take you into the test menu for AZF s refer page 71 providing the options for an Alarm Test and Fault test When highlighting an output point pressing the TEST button wi...

Page 43: ...OR 01 002 Z02 Z13 LEVEL 2 CORRIDOR 01 002 Z03 Z212 ROOM 212 01 002 Z04 Z213 ROOM 213 01 002 Z05 Z214 ROOM 214 01 002 Z06 Z10 LIFT MOTOR ROOM F 01 002 Z07 Z0 AZM8 01 002 Z08 Z0 AZM8 ALARM ZONE LIST 20 JULY 2002 14 44 37 CHANGE TEST DOWN UP BACK USE UP DOWN BUTTONS TO SELECT A ZONE A 0 F 1 I 1 N 1 DAY MODE Actions Use the UP and DOWN buttons to scroll through AZF points When highlighting an AZF inpu...

Page 44: ...UTPUT 01 001 O4 AZM8 01 002 O1 AZM8 01 002 O2 AZM8 01 002 O3 AZM8 01 002 O4 AZM8 DIGITAL OUTPUT LIST 20 JULY 2002 14 44 37 CHANGE TEST DOWN UP USE UP DOWN BUTTONS TO SELECT AN O P A 0 F 2 I 1 N 0 BACK DAY MODE Actions Use the UP and DOWN buttons to scroll through Output points When highlighting an output point Pressing the TEST button will take you into the test menu for outputs where you can togg...

Page 45: ...4 ON 16AT 01 101 I5 BUTTON 5 ON 16AT 01 101 I6 BUTTON 6 ON 16AT 01 101 I7 BUTTON 7 ON 16AT 01 101 I8 BUTTON 8 ON 16AT 01 101 I9 ACM16AT 01 101 I10 ACM16AT 01 101 I11 ACM16AT 01 101 I12 ACM16AT 01 101 I13 ACM16AT 01 101 I14 ACM16AT 01 101 I15 ACM16AT 01 101 I16 ACM16AT DIGITAL INPUT LIST 20 JULY 2002 14 44 37 CHANGE DOWN UP USE UP DOWN BUTTONS TO SELECT AN I P A 0 F 0 I 0 N 1 BACK DAY MODE Actions ...

Page 46: ... VP5 UNNAMED POINT VP6 UNNAMED POINT VP7 UNNAMED POINT VP8 UNNAMED POINT VP9 UNNAMED POINT VP10 UNNAMED POINT VP11 UNNAMED POINT VP12 UNNAMED POINT VP13 UNNAMED POINT VP14 UNNAMED POINT VP15 UNNAMED POINT VP16 UNNAMED POINT VP17 UNNAMED POINT VIRTUAL POINT LIST 20 JULY 2002 14 44 37 CHANGE DOWN UP USE UP DOWN BUTTONS TO SELECT AN I P A 0 F 0 I 0 N 1 BACK DAY MODE Actions Use the UP and DOWN button...

Page 47: ...ption Active points are denoted by an X after the point description NP1 COMMON ALARM ON NODE 1 X NP2 UNNAMED POINT NP3 UNNAMED POINT NP4 UNNAMED POINT NP5 UNNAMED POINT NP6 UNNAMED POINT NP7 UNNAMED POINT NP8 UNNAMED POINT NP9 UNNAMED POINT NP10 UNNAMED POINT NP11 UNNAMED POINT NP12 UNNAMED POINT NP13 UNNAMED POINT NP14 UNNAMED POINT NP15 UNNAMED POINT NP16 UNNAMED POINT NETWORK POINT LIST 20 JULY...

Page 48: ... 13 1 3 Z8 FAULT 5 03 02 99 10 50 56 1 3 Z8 FAULT SELF CLEARED 6 03 02 99 10 50 58 1 3 Z2 ISOLATED 7 03 02 99 10 52 00 L1D1 ALARM 6 03 02 99 10 50 58 L1D1 ACKD ALARM IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU HISTORY LIST 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 20 JULY 2002 14 44 37 PG UP USE BUTT...

Page 49: ...0 58 L1D1 ACKD ALARM IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU IFS DAP700 MENU SHADOW HISTORY LIST 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 28 JAN 1999 14 44 37 20 JULY 2002 14 44 37 DOWN UP USE BUTTONS NUMBERS TO SELECT A FUNCTION USE BUTTONS NUMBERS TO SELECT A FUNCTION USE BUTTONS NUMBERS TO SELECT A FUNCTION USE BUTTONS NUMBERS T...

Page 50: ...to it within the script 1 ISOLATED DISPLAY ALL ISOLATED POINTS 2 ZONE LIST ZONE GROUPS 3 AZF LIST ALARM ZONES 4 DOUT LIST DIGITAL OUTPUTS 5 DIN LIST DIGITAL INPUTS 6 VIRTUAL LIST VIRTUAL POINTS 7 ANALOG LIST ADDRESSABLE POINTS 8 RANGE ISOLATE A RANGE OF ANALOG POINTS 9 GROUP PROGRAM AN INPUT TO ISOLATE POINTS 0 NETWORK ISOLATE REMOTE ZONE OR POINT 28 JAN 1999 14 44 37 SELECT DOWN UP MENU ISOLATE D...

Page 51: ...the screen next to the point NOTE Isolating or de isolating in this screen will isolate de isolate ALL points within the zone 7 3 4 2 SERVICE MENU ISOLATE AZF LIST This screen allows the operator to isolate or de isolate a point 00 001 Z01 Z0 PANEL BREAK GLASS 00 001 Z01 Z0 PANEL DOOR OPEN x 01 001 Z01 Z4 CARPARK L4 01 001 Z02 Z3 CARPARK L3 01 001 Z03 Z2 CARPARK L2 01 001 Z04 Z1 CARPARK L1 I 01 00...

Page 52: ...int is isolated an I will appear on the right hand side of the screen next to the point 7 3 4 4 SERVICE MENU ISOLATE DIN LIST This screen allows the operator to isolate or de isolate an input point 01 010 I1 SPF 1 RUNNING x 01 010 I2 SPF 1 FAULT 01 010 I3 FANC 01 101 I1 BUTTON 1 ON 16AT I 01 101 I2 BUTTON 2 ON 16AT 01 101 I3 BUTTON 3 ON 16AT 01 101 I4 BUTTON 4 ON 16AT 01 101 I5 BUTTON 5 ON 16AT 01...

Page 53: ...T VP10 UNNAMED POINT VP11 UNNAMED POINT VP12 UNNAMED POINT VP13 UNNAMED POINT VP14 UNNAMED POINT VP15 UNNAMED POINT VP16 UNNAMED POINT VP17 UNNAMED POINT ISOLATE DE ISOLATE A POINT 20 JULY 2002 14 44 37 ISOL DOWN UP SELECT A POINT TO ISOLATE A 0 F 0 I 0 N 0 DEISOL ACKN DAY MODE Actions Use the UP and DOWN buttons to select the appropriate point and then press the ISOL button to isolate or the DEIS...

Page 54: ...2002 14 44 37 USE BUTTONS NUMBERS TO SELECT LOOP DAY MODE BACK UP DOWN Actions Use the UP and DOWN buttons to scroll through the Analog loop list Use the SELECT button to select the loop to list Alternatively press 1 through 4 Once you have selected the loop you will be prompted to select Analog addressable detectors or modules as follows SELECT DEVICE ON LOOP 1 1 DETECTOR 2 MODULE ISOLATE DETECTO...

Page 55: ...reen next to the point 7 3 4 6 2 ISOLATE ANALOG MODULES USE BUTTONS TO SELECT DEVICE L1M1 BREAK GLASS PANEL L1M2 BREAK GLASS ENTRY FOYER L1M3 NOT INSTALLED L1M4 NOT INSTALLED L1M5 NOT INSTALLED L1M6 NOT INSTALLED L1M7 NOT INSTALLED L1M8 NOT INSTALLED L1M9 NOT INSTALLED L1M10 EWIS OUTPUT 1 L1M11 EWIS OUTPUT 2 L1M12 NOT INSTALLED L1M13 NOT INSTALLED L1M14 NOT INSTALLED L1M15 NOT INSTALLED L1M16 NOT ...

Page 56: ...ll ensure ALL points are isolated Note The annunciator button that is being used to initiate the isolate must be a non latching button ie the Dip Switch on the ACM16AT annunciator must be set to OFF The minimum time between isolate and de isolate pushbutton action is 5 seconds How to configure single push button isolates From this menu option the panel will list all the Digital Inputs on the syste...

Page 57: ...ccept line and or Skip to next item ESC to leave this screen ISOLATE RANGE 20 JULY 2002 14 44 37 ENTER Please enter the information below A 0 F 0 I 0 N 1 DAY MODE Actions Use an external QWERTY keyboard to enter in the points that are to be isolated de isolated by the button press Points entered should be separated by spaces or commas and terminated with a semicolon Press ENTER once complete Zxxx ...

Page 58: ...display the AZF list as per page 43 Select the AZF you wish to change then press the Change button to enter the modify point screen or the Test button to test a point 3 Will display the Dout list as per page 44 Select the output you wish to change then press the Change button to enter the modify point screen or the Test button to test a point 4 Will display the Din list as per page 45 Select the i...

Page 59: ...ing data may be entered Item Description NAME This is the descriptor for the AZF e g LIFT MOTOR ROOM L16 Up to 28 characters are allowed ZONE NUMBER This is the Zone number assignment of the AZF One AZF per Zone Allowed Zone numbers are 1 to 999 An unnamed zone will prompt you for a zone name POINT TYPE Type of point e g FIRE HEAT SMOKE FLAME FSW MCP VMD PSW SPR This information is purely for disp...

Page 60: ... WHEN No script found for this point MODIFY POINT 20 JULY 2002 14 44 37 ENTER PLEASE ENTER THE INFORMATION BELOW Use arrows to move around INS DEL to edit lines ENTER accept line and or Skip to next item ESC to leave this screen Overwrite mode A 0 F 0 I 0 N 1 Enter condition using Zone Z3 or point numbers 1 2 I4 Operators AND OR T AND OR ESC DAY MODE Actions Type in the control script you wish the...

Page 61: ...BELOW Use arrows to move around INS DEL to edit lines ENTER accept line and or Skip to next item ESC to leave this screen Overwrite mode A 0 F 0 I 0 N 1 ENTER DAY MODE ESC Actions Use the external keyboard to enter a descriptor up to 28 characters for the output and press the ENTER button You will then be prompted to accept Press the YES button to accept or the NO button to redo A descriptor is th...

Page 62: ...cript for the point as follows SELECTED POINT VP1 VP1 OPERATES WHEN MODIFY POINT 20 JULY 2002 14 44 37 BACKSP PLEASE ENTER THE INFORMATION BELOW Overwrite mode A 0 F 0 I 0 N 0 Enter condition using local Zones and or Points or remote Net Points with node number N1 NP2 Operators AND OR T ANY TIM ENTER DAY MODE ESC Actions Type in the control script you wish the point to be controlled by and press E...

Page 63: ...e point as follows SELECTED POINT NP1 UNNAMED POINT OPERATES WHEN MODIFY POINT 20 JULY 2002 14 44 37 BACKSP PLEASE ENTER THE INFORMATION BELOW Overwrite mode A 0 F 0 I 0 N 0 Enter condition using local Zones and or Points or remote Net Points with node number N1 NP2 Operators AND OR T ANY TIM ENTER DAY MODE ESC Actions Type in the control script you wish the point to be controlled by and press ENT...

Page 64: ... N N SENSITIVITY 1 9 1 is most sensitive Day Alarm 5 Day Pre Alarm 4 Night Alarm 1 Night Pre Alarm 1 ANALOG MENU PROG A 0 F 0 I 0 N 0 20 JULY 2002 14 44 37 BACKSP ENTER DAY MODE Actions Press the BACKSP button to delete an incorrect character Press the ENTER button to step through options Press the YES or NO buttons when highlighted to answer Y N options Use external QWERTY keyboard to edit descri...

Page 65: ...u will be prompted Yes No to save changes when finished Output modules SELECTED POINT L1M10 L1M10 EWIS OUTPUT 1 DEVICE TYPE FRM 1 CMX 2 RELAY O P FLASHSCAN MENU PROG A 0 F 0 I 0 N 0 20 JULY 2002 14 44 37 BACKSP ENTER DAY MODE Actions Press the BACKSP button to delete an incorrect character Press the ENTER button to step through options Press the YES or NO buttons when highlighted to answer Y N opt...

Page 66: ... module had been physically removed from the system you can use this menu item to permanently remove it from the panel s memory How to Add Remove modules MODULES FOUND ON RING 1 001 002 003 004 005 006 007 101 102 103 ADD REMOVE MODULE 20 JULY 2002 14 44 37 NEXT PREV BACK USE BUTTONS TO SELECT A MODULE USE UP DOWN BUTTONS TO SELECT A RING A 0 F 0 I 0 N 0 ADD REMOVE DAY MODE Actions To remove a mod...

Page 67: ... LIST This menu option will list all Analog addressable loops allowing the user to then select detectors or modules and perform read status and or change a point s programming For a full explanation please refer to Service Menu List List Analog on page 33 7 3 6 2 SERVICE MENU ANALOG STATUS This menu option gives direct access to the read status screen of an Analog addressable point You will be pro...

Page 68: ...dd any new detectors and modules placed on the loop Pressing the MENU button will return you to the service menu Note Applicable to V4 xx and below firmware If the panel is powered down all loops will initialise with led blinking on Where required led blinking needs to be turned off manually after a power up the panel will not save the state of led blink after a cold reboot 7 3 6 6 SERVICE MENU AN...

Page 69: ...ws F01 NO RESPONSE F02 MISMATCHED DEVICE TYPE F03 2 DEVICES SAME ADDRESS F04 INCORRECT RESPONSE F05 OPEN CIRCUIT F06 SHORT CIRCUIT F07 LOW THRESHOLD F08 MAINTENANCE ALERT F09 MAINTENANCE URGENT F11 DETECTOR FAILED TEST F14 GROUND FAULT F18 GENERAL FAULT F21 MODULE EXTERN PWR LOSS ANALOG MENU 20 JULY 2002 14 44 37 BACK A 0 F 0 I 0 N 0 DAY MODE ANALOG FAULT CODE DEFINITIONS Actions Pressing the BACK...

Page 70: ...nd then press the TEST button to enter AZF Test Mode 2 Perform an alarm test on an Analog addressable point You will be prompted for loop number and detector or module number 3 Perform a fault test on an Analog addressable point You will be prompted for loop number and detector or module number 4 Will take you to the Digital Output List Where you can select an output from the DOUT list as per page...

Page 71: ... the previous screen Note that an isolated point is seen as inactive by the panel and hence in a logic programming script it will return the value FALSE or TRUE if the NOT function is applied to it within the script All tests will require the operator to manually reset the alarm or fault after the test If the alarm test or fault test fails a message of TIMEOUT ON ALARM FAULT or TIMEOUT ON CLEAR If...

Page 72: ...omatically exit after 10 minutes from the last button press to prevent the system remaining off line If a digital output does not have a control script and is set on during test mode the output will remain on permanently until turned off through test mode This can be a useful function for testing purposes during commissioning Note As the Dout tests activate the output at the remote module the modu...

Page 73: ... OUTPUT TARGET LIST 20 JULY 2002 14 44 37 SELECT DOWN UP SELECT AN OUTPUT FOR WALK TEST A 0 F 0 I 1 N 0 BACK DAY MODE Actions Use the UP and DOWN buttons to select the appropriate point and then press the SELECT button to select the output point After selecting the walk test output the following screen will appear You must then select the Group Zone or Loop you wish to test 1 ZONE SELECT A GROUP Z...

Page 74: ...They will all remain in alarm until the test is stopped As each one goes into alarm the Walk Test Output Target selected previously will activate for approximately 2 seconds At the conclusion of the test the points list on the display will indicate each device tested that has passed the alarm test 7 7 3 3 7 7 S SE ER RV VI IC CE E M ME EN NU U G GL LO OB BA AL L This menu items provides the abilit...

Page 75: ...ons and then use the TOGGLE button to select the toggle the highlighted option Changes are instant Explanation of Global Configuration Options Item Description Faults Latched Non Latched Determines if faults will self clear or remain latched until a manual reset FF Screen shows individual Alarms or group zones AS4428 1 has a requirement for Addressable points to show the zone to which they belong ...

Page 76: ...hours after isolation by using a VP as isolate group triggers E g VP3 can be used as the trigger for isolate group to de isolate Z1 Trigger Points to Isolate ISOLM 1 1 101 I1 Z1 1 101 I1 is a 16at button which isolates Z1 ISOLM 2 VP3 Z1 When VP3 activates Z1 will be de isolated VP3 IZ1 AND T1200 VP3 activates 1200s after Z1 is isolated 7 3 7 2 SERVICE MENU GLOBAL TIME From the Global configuration...

Page 77: ...ack to the service menu Note NP1000 can be used to force the panel into night mode On V5 02 and above firmware if NP1000 is active the panel will be forced to operate in night mode and stays in night mode as long as NP1000 is active This feature allows the programmer to use scripting for switching between day night modes 7 3 7 4 SERVICE MENU GLOBAL PASSWORDS Overview The BC 200 supports a total of...

Page 78: ...d and an 8 character alpha numeric code will be displayed on the LCD screen Note down this code and contact the customer support centre The original correct password can be calculated using this code and released to the building owner so long as the appropriate authority has been provided by the building owner in writing Please contact customer support centre for more information on releasing pass...

Page 79: ...tton to select the toggle the highlighted option Changes are instant Explanation of Global Configuration Options Item Description Event Printing Determines if the panel should print events to the printer port Alarm Only Printing This setting determines if the panel should only print alarm events or all events Zone Event Printing This setting determines if the panel should print zone events as well...

Page 80: ...scroll through options and then use the SELECT button to select the highlighted option or button 1 to 8 from the numeric keypad Press the MENU button to return to the service menu screen Warning Before selecting any of the printing functions make sure that the external keyboard is disconnected or the panel may re boot Selection Result Alarm List Prints all Alarm events currently on the system Faul...

Page 81: ... ISOLATES RESET ALL ALARMS DIAGNOSTIC MENU SELECT DOWN UP MENU USE UP DOWN BUTTONS TO SELECT A FUNCTION 20 JULY 2002 14 44 37 A 0 F 0 I 0 N 1 DAY MODE Actions Use the UP and DOWN buttons to scroll through options and then use the SELECT button to select the highlighted option or button 1 to 9 from the numeric keypad Press the MENU button to return to the service menu screen 7 3 8 1 SERVICE MENU DI...

Page 82: ...ansion relays within the panel by cycling through them one at a time Pressing any button stops the test 7 3 8 6 SERVICE MENU DIAGNOSTICS LED This mode will test the correct operation of panel LED and LCD display by randomly flashing LEDS and filling the LCD with data Pressing any button stops the test 7 3 8 7 SERVICE MENU DIAGNOSTICS MODULE This mode will perform tests on field modules to ensure c...

Page 83: ... MENU DIAGNOSTICS HISTORY This command will permanently delete ALL events in the systems history log 7 3 8 10 SERVICE MENU DIAGNOSTICS RESTART THE SYSTEM This command will perform a warm system reboot and will reprogram all LCM s Note A warm system reboot can also be performed by pressing Reset SW1 on the back of the CPU board A Warm reboot will not reboot the FIM LIM NIM or LCM modules To reboot ...

Page 84: ...2 14 44 37 A 0 F 0 I 0 N 1 DAY MODE SELECT DOWN UP BACK Actions Use the UP and DOWN buttons to scroll through options and then use the SELECT button to select the highlighted option or button 1 to 5 from the numeric keypad Press the BACK button to return to the Service Menu screen 7 3 9 1 SERVICE MENU NETWORK NETWORK This option will display a list of nodes found on the network The node list is up...

Page 85: ...DAY MODE ESC ENTER BACKSP Actions Follow the on screen prompts to enter a node number To remove the panel from the network enter Node 0 If a non zero node number is entered you will be further prompted to enter if you want the panel to transmit events to the rest of the network YES or to receive network events only without transmitting them mimic panel mode NO 7 3 9 4 SERVICE MENU NETWORK RECEIVE ...

Page 86: ...e acts as a Slave node on the network If Receive Events From Node n is Yes then alarms faults isolates pre alarms and non alarms will be received from node n In this mode the local node acts as a Master node on the network In a typical slave master network layout where only the master panel will display remote alarms and faults the slave panels receive settings from other nodes should be setup as ...

Page 87: ...knowledge of network faults is disabled enabled This option allows you to acknowledge all faults on the network with a single ACK from this panel Usually enabled on Master FIP Channel A Threshold is High Low Default value is high Low threshold should only be used for long network cable runs refer to network manual for more details Channel B Threshold is High Low Default value is high Low threshold...

Page 88: ...l point Analog addressable device software zone or system point in any combination of AND OR NOT or RANGE logic Logic equations can be built up by bracketing functions to create combinations of logic Note RANGE logic functions entered via the panel keyboard must not span more than 1 module address e g 1 1 Z1 1 1 z8 If you need to span more than 1 module address then you must enter the range via th...

Page 89: ...he specified range as a large OR or AND function This function is performed as a macro and includes only modules installed at the time of parsing If modules are added after this point they will not automatically be included in the range If you add a module and you and want it included in range scripts you must re parse the script again When using a Range Function if the point you are writing the s...

Page 90: ...e week format SU MO TU WE TH FR SA This is processed as Turn ON at date1 time1 turn OFF at date2 time2 for the following days of the week Examples 1 TIM 23 01 03 09 00 00 23 01 03 17 00 00 This script will turn on at 9 am and turn off at 5 pm on the 23rd of Jan 2003 2 TIM 09 00 00 17 00 00 This script will turn on at 9 am and turn off at 5 pm every day 3 TIM 17 00 00 09 00 00 This script will turn...

Page 91: ...e AND Range 1 1 Z1 1 1 Z8 ALL AZF s on module 1 in Alarm Alarm Active Z999 Zone 999 is in alarm only if not isolated Fault FL1D1 L1D1 is in fault Isolate IL1M1 L1M1 is isolated Pre alarm PL1D3 L1D3 in pre alarm S pre operator SZ1 Zone 1 is in alarm isolate state is ignored Combination examples Example Description L1M1 OR L2D10 AND Z3 L1M1 or L2D10 and not Zone 3 Expressions in the brackets are eva...

Page 92: ... NP100 NP100 CA The bell on Node 1 is required to activate if any of the panels in the network go into alarm The bell on Node 1 is driven off expansion relay XR1 Therefore the Node 1 Bell Output script is XR1 NP100 OR N2 NP100 OR N3 NP100 OR N4 NP100 OR N5 NP100 Example 2 There are 5 panels on an BC 200 network There is a toggle switch on Node 1 which is mapped to a non latching input module L1M1 ...

Page 93: ...s the programmer to use scripting for switching specific groups of Acclimate detectors to heat only mode as required Note that the sensitivity of non Acclimate detectors in the list will also be set to 9 which means that they will still alarm due to smoke Ensure that all detectors in the list are Acclimates to ensure there are no unwanted alarms due to smoke Example NP950 1 101 I1 NP950 follows th...

Page 94: ...within the 120 seconds it is to be treated as a real alarm 5 If the 120 second timer expires return the zone back to its normal condition 9 9 1 1 2 2 T TI IM ME ED D A AZ ZF F F FU UN NC CT TI IO ON NA AL L D DE ES SC CR RI IP PT TI IO ON N A timed AZF can be used where normal latching detectors are required to be used in a duct probe application 1 Timed AZF s function as follows 2 Once the point ...

Page 95: ...ate Ability to view system information Ability to view history Ability to view all read only data Level 1 Level 0 access Ability to change descriptors Ability to change point options Ability to change display zone options Ability to add and edit pushbutton isolate functions Ability to change global options Ability to alarm and fault test devices Level 2 Level 1 access Ability to add and remove mod...

Page 96: ... Isolates In the event that a fault is showing on the display and an alarm occurs the display will automatically change to show the alarm Totals of all Alarms Faults and Isolates are also shown and are automatically updated every 10 seconds 9 3 1 2 MANUAL OPERATION Pressing DISPLAY ALARMS will show the first alarm in the alarm list Pressing DISPLAY FAULTS will show the first fault in the fault lis...

Page 97: ...tes on the system In this example an alarm occurred on the 10 th of September at 12 37pm It is the first of two alarms and occurred in the West Wing on point number 1 1 Z7 There are 2 alarms 2 faults and 0 isolates on the system 9 3 1 5 SPECIAL MESSAGES ALL SYSTEMS NORMAL The system is 100 normal with no alarms faults or isolates COMMS FAILURE This messages flashes and appears when the LCD80 has n...

Page 98: ...show the first event point activated by the FIP The points are displayed in the order in which they were activated 9 3 2 2 MANUAL OPERATION Pressing the NEXT and PREVIOUS buttons allow the user to scroll up and down the list When the last message on the list is reached the display will wrap around to the first message on the list and vice versa Pressing Mute will silence the buzzer if active The b...

Page 99: ...buzzer until a new event is received 9 3 2 4 DISPLAY The LCD Display is made up of 4 lines of 20 characters each Events are displayed as In the above example the FIP has activated Point 6 on the LCD80 It is the first of 5 points which are active The Comms Indicator Spins when messages are being received by the LCD80 In this example The FIP has activated Point 12 on the LCD80 It is the only point a...

Page 100: ... 3 2 6 Signal Ground 5 7 7 Rx D 2 3 No Connection DTR 4 Note 1 20 No Connection DSR 6 Note 1 6 Note 1 Pin 4 DTR is connected to pin 6 DSR in the 9 pin connector housing Downloading new labels Using the PCI create an LCD 80 at the desired address Enter all the required descriptors in the PCI Set dip switch 7 to on and connect the programming cable to the LCD 80 Select download on the PCI and tick t...

Page 101: ...UST be wired using a twisted pair shielded cable Do not run cable adjacent to or in the same conduit as 240 volt AC service noisy electrical circuits that are powering mechanical bells or horns audio circuits above 25 VRMS or motor control circuits All enclosures including the FIP cabinet must be connected to electrical earth Never use the shield as an earthing conductor Terminate the shield at th...

Page 102: ...s and from any conductor to ground should not exceed 0 5 microfarads Notes Usage of shielded or flat cable for the SLC loops is not recommended and should be avoided where possible Fire rated cables may be required as per AS1670 AS1668 and AS2118 Separate 2 core cable to be run for 24VDC power to FZM 1 and FCM 1 modules Max distance of the loop is governed by the total loop resistance and will dep...

Page 103: ...aters fibre optic circuits are point to point is limited by cable choice If the distance required for a circuit segment is greater than permitted a Repeater module RPT F must be inserted into the circuit at intervals less than or equal to the attenuation length restriction Multi mode fibre 62 5 125μm cable 8dB limit 50 125μm cable 4 2dB limit Single mode fibre 9 125μm cable 8dB limit The actual at...

Page 104: ...removed for at least 15 seconds WARNING If any detector is replaced with a different type of detector for example a laser detector is replaced with a photoelectric detector the control panel must be programmed immediately with the new detector Type Code Failure to do so can cause incorrect control panel operation including false alarms 9 9 5 5 2 2 S SE EL LF F O OP PT TI IM MI IZ ZI IN NG G P PR R...

Page 105: ... Obscuration Pre Alarm Metre Obscuration Photo Optical Level 1 0 50 Auto Level 2 2 40 0 98 Level 3 3 15 1 54 Level 4 3 90 2 10 Level 5 4 69 2 66 Level 6 5 45 3 25 Level 7 6 20 3 81 Default Level 8 6 96 4 36 Level 9 7 71 4 92 Ionisation Level 1 1 64 Auto Level 2 2 46 1 31 Level 3 3 28 1 64 Level 4 4 10 2 46 Level 5 4 92 3 28 Level 6 5 74 4 10 Level 7 6 56 4 92 Default Level 8 7 38 5 74 Level 9 8 20...

Page 106: ...processed photo output Level 2 3 Clean environments Offices 6 56 per metre of smoke No delays from processed photo output Level 4 Moderately clean environments Hotel Dorm rooms 9 84 per metre of smoke No delays from processed photo output Level 5 6 Moderate environments hotel near shower boiler rooms 9 84 per metre of smoke Maximum of 10 minutes delay from processed photo output See notes Level 7 ...

Page 107: ...etermines when the drift compensation for a detector reaches an unacceptable level that can compromise detector performance When a detector reaches an unacceptable level the control panel indicates a maintenance warning The table below summarizes the three levels of Intelligent Sensing maintenance warnings Detector Fault Message Indicates Detector Compensation Percentage Range Ion Photo Laser Accl...

Page 108: ...tenance Urgent FAULT F09 Analog detector needs cleaning urgently Once the detector is in maintenance urgent fault it will no longer provide reliable detection of fire Verify Count Over 20 FAULT F010 Not used on BC 200 Detector Failed Test FAULT F011 LCM performs a test on each detector every 2 3 hours This fault can occur if the device is faulty or the loop wiring is substandard If the resistance ...

Page 109: ...M 4 20 Device Inhibit FAULT F032 Not used on BC 200 FMM 4 20 No Threshold Programmed FAULT F033 Not used on BC 200 FMM 4 20 Trouble 1 FAULT F034 Not used on BC 200 FMM 4 20 Trouble 2 FAULT F035 Not used on BC 200 FMM 4 20 Comms Loss FAULT F036 Not used on BC 200 FMM 4 20 Command Failed FAULT F037 Not used on BC 200 FMM 4 20 Thermistor Fault FAULT F038 Not used on BC 200 FlashScan mode only IR Faul...

Page 110: ...put Relay Expansion Connector IN Local AZ Connector Programming connector to Black box Serial I O connector to CPU board Power and Comm to Annunciator board Expansion to LIM NIM Board Relay Expansion Connector OUT Local relay O P connector Processor Reset button Ring Earth Fault Status LED SC A Short Circuit on Ring 1 power A SC B Short Circuit on Ring 1 power B EFLT Earth fault detected on panel ...

Page 111: ...must have V5 02 or above firmware installed 2 Set the bottom dipswitch on mode dipswitch U25 on the back of the CPU to the on position Note that the dipswitch can be marked 1 or 4 Always set the dipswitch closest to the upload download port 3 J6 on IFS 724 FIM board must be fitted NI 2012 Power Supply Interface PSI IFS 724 FIM Termination Board NI 2012 PSI Dipswitch Settings Normal operation All o...

Page 112: ...cent to cable entry Between Field modules connect shields together outside of their respective enclosures Make sure that the shield is only grounded at the FIP and not at the modules or annunciators Do not ground both ends of the shield one end should be left floating 9 6 1 4 MAIN TERMINATION BOARD CONNECTING 24VDC AZ1 AZ1 AZ2 AZ2 TERMINATION BOARD PWR A PWR A PWR B PWR B TO FIRST MODULE IN LOOP F...

Page 113: ... NO CM NC NO CM NC TERM 5 9 6 1 7 MAIN TERMINATION BOARD PANEL EXPANSION RELAYS TERMINATION BOARD J16 J17 OUT IN Note that the panel expansion relay boards must be connected in a closed serial loop between J16 and J14 on the Main Termination Board for the software to auto detect the actual number of Relay boards connected The maximum allowed is 8 x 8 way relay boards If the serial loop is left ope...

Page 114: ... Cable Specification BC 200 End CONN2 Laptop End DB9 Male DB9 Female 2 RX 2 RX 3 TX 3 TX 5 REF 5 REF 8 CTS 7 RTS 9 6 2 2 PRINTER PORT SETTINGS Caution The PS 2 keyboard and serial printer must not be connected at the same time or printing errors will result The serial printer where fitted must be disconnected whilst the keyboard is plugged in Port Information Connector Information Mode RS232 Type ...

Page 115: ...IBBON CABLE MAIN TERMINATION BOARD FIM J3 Not used on LIM Ribbon cable from FIM or NIM if fitted Power connector from FIM Not used on LIM Not used on LIM 20 way ribbon cable to LCM LEM boards Factory Programming Port Reset Switch Address Switch Address Settings Description SW1 SW2 SW3 SW4 Loop Interface Module For use with LCM s OFF ON OFF OFF Network Interface Module For use with NCM s ON ON OFF ...

Page 116: ...mmunication loss The LCM has an earth fault detection circuit with a yellow LED displaying an earth fault condition ELCM modules also include a green heartbeat LED to show that the processor is working The LEM is an expansion board that attaches to its LCM parent providing a second loop which has the same features as the parent loop MicroController Connector to LEM Ground Fault on LCM 20 Way Ribbo...

Page 117: ... operated from a separate driver Style 6 Closed loop returns to panel providing a redundant path for open circuit conditions Total Loop 3810m maximum 50 Ω resistance maximum In style 6 the processor polls the loop from one of the drivers the B side If a failure open circuit is detected it will poll through both ends Style 7 Closed loop with isolation modules providing a redundant path for short ci...

Page 118: ... module Branch A Branch B A A B B To LCM or LEM STYLE 4 Two wire addressable detector Addressable module Loop Out Loop Return A A B B To LCM or LEM STYLE 6 Two wire addressable detector Addressable module Loop Out Loop Return A A B B To LCM or LEM ISO X ISO X Isolation module STYLE 7 ...

Page 119: ...ld either be a short on the line or a device may be incorrectly wired possible reverse polarity Find the device and correct the loop connections at that device 4 Check that there are no earth faults as follows Select ohms on the multimeter and measure between each leg of the loop and earth If the reading falls below 50 000 Ω an earth fault will be indicated when the loop is connected Find the caus...

Page 120: ...up to 100 nodes The BC 200 occupies a single node address on the network Each network node requires a unique node address the node communicates with other nodes via a Network Control Module NCM The NCM connects to the BC 200 via the Network Interface Module NIM 9 6 5 1 NETWORK INTERFACE MODULE NIM To Network Interface Module 40 WAY RIBBON CABLE MAIN TERMINATION BOARD FIM J3 Ribbon cable to LIM If ...

Page 121: ... way NUP cable connects J6 connector on IFS 725 NIM to NUP 1 J3 connector on NCM NIM IFS 705 to NCM cable specification NIM end NCM end Comm B NUP Port Rx Tx Pin 5 Ref Pin 4 0v Rx Pin 3 Tx 0V Pin 2 24V Pin 1 24V 0V Network connection ports NUP NUP port connector detail Pin 1 Pin 1 NUP 1 NUP 2 ...

Page 122: ... From last node Port A To next node Port B CONNECTION DETAIL Note Wiring from the NCM W that is installed outside buildings Must be in conduit and be buried in a trench separate from any power lines Cannot cross any power lines NCM W Connections Connector Pin Signal Name TB100 1 CH A Channel A Driver Receiver TB100 2 CH A Channel A Driver Receiver TB100 3 CH B Channel B Driver Receiver TB100 4 CH ...

Page 123: ...that serve as diagnostic indicators to help in troubleshooting and system connection The table below outlines their function A HI RCD A ST AT A RECO N RESET Diagnostic LED detail B HI RCD B PULSE 1 ST AT B PO W ER LED Indicator LED Colour LED Description A HI Green Illuminates to indicate that the NCM W Port A is set for high threshold B HI Green Illuminates to indicate that the NCM W Port B is se...

Page 124: ... always asserted AT E2 Automatic speed stepping To establish connection with the modem after the above commands have been entered set HyperTerminal port settings to 115 baud rate RTS CTS handshaking After re connecting to the modem using the above settings save the configuration to hardware profile 0 using the AT W0 command Check modem configuration using AT V command Ensure that all the options a...

Page 125: ...F FA AC CE E BC 200 can be interfaced to serial printers pagers and nurse call systems using the printer port on the CPU CONN1 A global option on the FIP will enable disable printing Any standard terminal program or the BC 200 PCI history upload tool can be used to monitor the output of this port An example of this text output is included in the next section for reference 9 7 2 1 PORT SETTINGS BC ...

Page 126: ...7 FAULT CLEARED Z000 NODE100 NODE UP 03 03 11 47 FAULT Z000 N100 0 10 2 PORTA FLT 03 03 11 47 FAULT Z000 N100 0 10 3 PORTB FLT 03 03 11 47 FAULT CLEARED Z000 N100 0 10 2 PORTA UP 03 03 11 47 FAULT CLEARED Z000 N100 0 10 3 PORTB UP 03 03 11 47 FAULT CLEARED Z000 0 10 2 PORTA UP 03 03 11 49 FAULT Z000 0 2 I3 RING POWER SHORT 03 03 11 51 FAULT CLEARED Z000 0 2 I3 RING POWER SHORT 03 03 11 51 SYSTEM Z...

Page 127: ...N NT T C CA AL LC CU UL LA AT TI IO ON N Item Qty Current Each Amps Sub Total Amps Main Control Panel 1 0 220 0 210 Loop Interface Module 0 025 LCM LEM Pairs 5 max 0 200 Fan Control Module In Alarm 0 130 Fan Control Module Quiescent 0 055 AZM8 Modules In Alarm 0 155 AZM8 Modules Quiescent 0 090 Bells Analog Points In Alarm Activated Other Quiescent Load Other Alarm Load Total Alarm Current A 9 9 8...

Page 128: ...t boards by personal other than a certified factory technician will void all warranties Sub Assemblies Item Description IFS 713 BC 200 CPU board IFS 724 BC 200 Main termination board LIM BC 200 Loop Interface Module Analog addressable NIM BC 200 Network Interface Module LCM BC 200 Addressable Loop Driver Master Loops 1 3 5 7 9 LEM BC 200 Addressable Loop Driver Slave Loops 2 4 6 8 10 16AT BC 200 A...

Page 129: ...7 RESISTOR IN IN OUT OUT SHIELD COMMS CABLE FROM PREVIOUS MODULE COMMS CABLE TO NEXT MODULE SOCKET OUTPUT FUNCTION 1 OUTPUT FUNCTION 2 OUTPUT FUNCTION 3 OUTPUT FUNCTION 4 24V From Previous Module 0V From Previous Module 24V To Next Module 0V To Next Module Note Between Field modules connect shields together outside of their respective enclosures Make sure that the shield is only grounded at the FI...

Page 130: ...4V To Next Module INPUT 1 INPUT 2 INPUT 3 IN IN OUT OUT SHIELD COMMS CABLE FROM PREVIOUS MODULE COMMS CABLE TO NEXT MODULE SOCKET OUTPUT FUNCTION 1 OUTPUT FUNCTION 2 OUTPUT FUNCTION 3 Note Between Field modules connect shields together outside of their respective enclosures Make sure that the shield is only grounded at the FIP and not at the modules or annunciators ...

Page 131: ...ce Units may be connected to the local annunciator chain connector on the lower left edge of the Termination Board This connector is only to be used for annunciators and LCD80 Display Interface Units that are mounted internally to the fire panel or in a cabinet immediately adjacent to it No termination resistor is to be used for this mode of connection since there is a built in 150 ohm resistor on...

Page 132: ... 16 6A AT T 1 16 6 B BU UT TT TO ON NS S 3 32 2 L LE ED D S S Dip Switch Settings On Off 1 Bank 1 buttons 1 8 are toggle on toggle off Bank 1 buttons 1 8 are momentary 2 Bank 2 buttons 9 16 are toggle on toggle off Bank 1 buttons 1 8 are momentary 3 8 Not Used Not Used ...

Page 133: ...Appendix BC 200 Manual P N DOC 01 013 133 9 9 1 11 1 3 3 A AC CM M 3 32 2A A 3 32 2 R RE ED D L LE ED D S S Dip Switch Settings On Off 1 8 Not Used Not Used ...

Page 134: ...8 F FA AN N C CO ON NT TR RO OL LS S Dip Switch Settings On Off 1 7 Not Used Not Used 8 120 Ohm EOL resistor selected No EOL resistor selected Note EOL resistor can be enabled by dip switch 8 on SCS 8 see below When used on BC 200 ensure that the EOL resistor is not enabled ...

Page 135: ... PA AN NS SI IO ON N R RE EL LA AY Y D DR RI IV VE ER R B BO OA AR RD D J5 J6 J7 J8 J10 Connectors to relay board Power and RS 485 Connector see diagram below for connections Address switches Relay Exp Power Comms active LED Ones Tens Dip Switch Settings On Off 1 8 Not Used Not Used ...

Page 136: ...6 K15 K14 K13 K19 K20 K3 K4 K5 K6 K7 K31 K30 K29 K28 K27 K26 K8 K9 K12 K21 K22 K23 K24 K25 K10 Connections J5 J6 J7 and J8 on the LDM R32 connect to J5 J6 J7 and J8 on the LDM 32 respectively J10 on the LDM R32 connects to J10 Relay Exp on LDM 32 Relay contacts are on Terminal Blocks TB1 TB6 as shown in the diagram above Example addressing If annunciator address is 50 then relay K1 point address w...

Page 137: ... as per the table below Note that 200 is added to the actual values of SW2 SW3 to give an address in the range 201 239 Setting all switches to off will take the LCD 80 offline SW3 1 SW3 2 SW2 Actual Address OFF OFF 1 9 201 209 ON OFF 0 9 210 219 OFF ON 0 9 220 229 ON ON 0 9 220 239 Addressing Annunciator Mode SW2 SW3 set the address as per the table below Note that 100 is added to the actual value...

Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...

Page 139: ...OG ADDRESSABLE DEVICES 9 9 1 13 3 1 1 D DE ET TE EC CT TO OR R B BA AS SE ES S 501 Detector Base LPB W Sounder Strobe base Terminal Function T1 Negative T2 Positive in T3 Positive out T4 Remote LED Detector base sounders only T5 Shield Remote Indicator ...

Page 140: ...Appendix BC 200 Manual P N DOC 01 013 140 9 9 1 13 3 2 2 I IS SO OL LA AT TO OR R B BA AS SE E ...

Page 141: ...Appendix BC 200 Manual P N DOC 01 013 141 9 9 1 13 3 3 3 I IS SO OL LA AT TI IO ON N M MO OD DU UL LE E ...

Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...

Page 143: ...Appendix BC 200 Manual P N DOC 01 013 143 9 9 1 13 3 5 5 C CO ON NT TR RO OL L M MO OD DU UL LE E ...

Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...

Page 145: ...Appendix BC 200 Manual P N DOC 01 013 145 9 9 1 13 3 7 7 M MO ON NI IT TO OR R M MO OD DU UL LE E Manual Call Point ...

Page 146: ...Appendix BC 200 Manual P N DOC 01 013 146 9 9 1 13 3 8 8 M MI IN NI I M MO ON NI IT TO OR R M MO OD DU UL LE E ...

Page 147: ...Appendix BC 200 Manual P N DOC 01 013 147 9 9 1 13 3 9 9 1 10 0 X X M MO ON NI IT TO OR R M MO OD DU UL LE E ...

Page 148: ...Appendix BC 200 Manual P N DOC 01 013 148 9 9 1 13 3 1 10 0 6 6 X X C CO ON NV VE EN NT TI IO ON NA AL L Z ZO ON NE E I IN NT TE ER RF FA AC CE E M MO OD DU UL LE E ...

Page 149: ...Appendix BC 200 Manual P N DOC 01 013 149 9 9 1 13 3 1 11 1 6 6 X X R RE EL LA AY Y M MO OD DU UL LE E ...

Page 150: ...Appendix BC 200 Manual P N DOC 01 013 150 9 9 1 13 3 1 12 2 6 6 X X C CO ON NT TR RO OL L M MO OD DU UL LE E ...

Page 151: ...Appendix BC 200 Manual P N DOC 01 013 151 9 9 1 13 3 1 13 3 2 2 X X M MO ON NI IT TO OR R 2 2 X X R RE EL LA AY Y ...

Page 152: ...AN STOP REPEAT FOR EACH FAN TYPICAL FAN INDICATION CONTACT ARRANGEMENT 47K FAULT OPENCCT RUN CLOSEDCCT STOP 47K RES FAN CONTROLS FIELD I O 2800 1 1 G W 23 11 1 NIFS_FAN 28 RUN FS AFR AFR SR COMM RUN FAULT FR STOP FMM101 SR START RELAY AFR AIR FLOW RELAY FR FAN RUN RELAY FS FAN STOP RELAY FTR FTR SUPPLY POW ER MECH ANICAL SER VICES BOARD PFR PFR PFR PHASE FAIL RELAY B 24 0V 47K NOTE A FAULT CONTACT...

Page 153: ...Appendix BC 200 Manual P N DOC 01 013 153 9 14 NPS POWER SUPPLY CONNECTIONS 9 9 1 14 4 1 1 C CO ON NN NE EC CT TI IO ON N T TO O I IF FS S 7 71 14 4 T TE ER RM MI IN NA AT TI IO ON N B BO OA AR RD D ...

Page 154: ...Appendix BC 200 Manual P N DOC 01 013 154 9 9 1 14 4 2 2 C CO ON NN NE EC CT TI IO ON N T TO O I IF FS S 7 72 24 4 T TE ER RM MI IN NA AT TI IO ON N B BO OA AR RD D ...

Page 155: ......

Page 156: ...Head Office Unit 5 24 28 River Road West Parramatta NSW 2150 Ph 61 2 8837 9333 Fax 61 2 9891 6725 National Sales Number 1300 ADI ADI Email aus sales adiglobal com Technical Support 1800 220 345 ...

Reviews: