System Capacity And Expandability
BC-200 Manual
– P/N DOC-01-013
17
6 S
YSTEM
C
APACITY
A
ND
E
XPANDABILITY
6.1 B
ASE
S
YSTEM
Item
Description
Notes
Communications Ring
RS485 communications ring to support
Up to 100 Field Modules
Up to 50 Annunciators
8 System Outputs
4 x Monitored Outputs.
Bell Output
3 Additional
programmable outputs
4 x Clean contact relays
General Alarm Output
General Fault Output
2 x programmable outputs
Fault output is normally
energised using V5.00
and above firmware.
Max contact rating of all
relays 1A @ 30Vdc.
Power Supply
2.6 A power supply and battery
charger
Fused 27.3Vdc outputs
A larger power supply
may be required if total
module load exceeds
2A. Power supplies up
to 11.7A are available.
2 Local AZF’s
AZF 1
AZF 2
2 RS232 communication
ports
Laptop interface
System event printer
Remote terminal mode
Keyboard Interface
PS2 QWERTY IBM PC keyboard
System Memory
Approx. 4300 Named points
Approx. 4000 Control scripts
4000 History events
6.2 E
XPANSION
PCB
S
Item
Description
Notes
Loop Interface Module
(LIM)
Interface module to communicate with
up to 5 x pairs of LCM/LEM modules.
I.e. total of 4 CLIP Analog addressable
loops
Each Analog
addressable loop
supports up to 99
detectors and 99
addressable modules
using the CLIP protocol
Network Interface
Module (NIM)
Interface module to communicate with
the Network Control Module (NCM)
Panel Expansion Relays
(IFS-717)
Relay card with 8 relays – contact
rating is 1A @ 24Vdc
Up to 8 IFS-717 8-way
relay boards can be
added
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......