Panel Operation
BC-200 Manual
– P/N DOC-01-013
38
7.3.3.7.2.1
Service Menu – List – List – Analog – Modules – Status
This screen will show a reading of the selected Analog addressable module updated every 3 seconds, 255 times.
The modules current configuration is displayed together with “live readings” as shown below.
L1M1
(Z000) > BREAK GLASS ON PANEL
Poll Mode
> Flashscan Mode
Programmed As
> FMM-101-MMX-101 MINI MON
Actual Device
> FMM-101 MINI MON
Device State
> NORMAL
Device Status
> NORMAL
LED Status
> Polling
Device Scanned 255 Times
.
ANALOG MENU – STATUS
A = 0
F = 0
I = 0
N = 0
20 JULY 2002 14:44:37
DAY MODE
PREV
TEST
Menu
NEXT
RESET
Actions:
Press the
PREV
buttons to move to the previous
installed point.
Press the
NEXT
buttons to move to the next
installed point.
Press the
TEST
button to enter test menu for the
detector.
Press the
RESET
button to re-initialise the
detector.
Press
MENU
to return to the Analog Menu
screen.
Explanations of terms:
Variable
Range
Description
Poll Mode
CLIP
Shows the current polling protocol being used. CLIP = 1
module at a time. Polling mode is auto sensed at start-up
Programmed As
9 Types
Module type programmed into panel
Actual Device
5 Types
Module type physically seen on loop
Device State
Normal/Active/Alarm
Shows alarm or activated condition of point
Device Status
23 fault types
Detailed description of fault condition. I.e. “No Response”
LED Status
4 Types
Polling, On, Off, Polling ID
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......