Emergency Operation
BC-200 Manual
– P/N DOC-01-013
7
1 E
MERGENCY
O
PERATION
Isolate Bells
Press: EXT BELL ISOLATE
EXT BELL ISOLATE LED will light
The Bells & Buzzer will stop
A subsequent alarm will restart the Buzzer but not the bells
The bell isolate can be toggled by pressing the button a second time
Isolate Warning System
Press: WARN SYS ISOLATE
WARN SYS ISOLATE LED will light
The warning system will stop
A subsequent alarm will restart the Buzzer but not the warning
system
The warning system isolate can by toggled by pressing the button a
second time
Acknowledging an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ACK to acknowledge
This will individually acknowledge alarms
Once all alarms are acknowledged the alarm LED will go steady
Resetting an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: RESET then press ACK to confirm the resetting
This will individually acknowledge and reset alarms
Resets zone in alarm and clears all alarm inputs in the zone
If alarm is still present, the zone(s) will either stay in alarm or re-
alarm again after about 15 seconds
Isolate an Alarm
Select the Alarm using the PREV , NEXT buttons
Press: ISOL then press ACK to confirm the isolation
Isolates the point or zone in alarm and clears it’s alarm outputs
Isolating a zone automatically acknowledges and isolates all points
in the zone
Summary of Contents for BC-200
Page 1: ...BC 200 OPERATION INSTALLATION PROGRAMMING MANUAL P N DOC 01 013 ECN11 0058 23 Aug 12 Rev 5 07 ...
Page 138: ...Appendix BC 200 Manual P N DOC 01 013 138 9 12 PANEL EXPANSION RELAYS ...
Page 142: ...Appendix BC 200 Manual P N DOC 01 013 142 9 9 1 13 3 4 4 R RE EL LA AY Y M MO OD DU UL LE E ...
Page 144: ...Appendix BC 200 Manual P N DOC 01 013 144 9 9 1 13 3 6 6 Z ZO ON NE E M MO OD DU UL LE E ...
Page 155: ......