background image

FIREYE 26RJ8 1002, 1003, 1008, 1011, 1018, 6008, 6018

29RF5 1000, 1002, 1005, 1015, 1104
29RF5 6015

TO

B PM720G2005

Summary of Contents for BC7000L1000

Page 1: ... prevent electrical shock and equipment damage 3 All wiring must comply with applicable local electrical codes ordinances and regulations 4 Voltage and frequency of the power supply and flame detector s connected to this control must agree with those marked on the device 5 Loads connected to the control terminals must not exceed those listed in the SPECIFI CATIONS section 6 All external timers mus...

Page 2: ...es as they are marked 4 Remove old subbase 5 Mount Q520A subbase 6 Connect wires to subbase per attached cross reference Pay close attention to footnotes For example To convert a Fireye 70D10 to a BC7000 the wire marked P would connect to terminal 3 on the Q520 The wire marked 8 would connect to Q520 terminal 15 7 The symbol designates a footnote Study these footnotes carefully 8 Plug in the BC700...

Page 3: ...E1214A FIREYE 70D10 26CF6 5022 26 CU6 5065 EP160 EP161 EP170 TO BC7000L PM720L2004 or 1030 ...

Page 4: ...E1215B FIREYE 24CJ5 5010 5011 3010 3011 25CU6 5062 5063 RS 2E 70D30 26CF6 5020 5021 1010 1011 EP380 EP381 EP390 TO BC7000L PM720M2002 ...

Page 5: ...E1216E FIREYE 24CJ5 5015 70D20 26CF6 5023 25 CU65055 EP260 EP261 EP270 TO BC7000L PM720G2005 ...

Page 6: ...ct wires as they are marked Remove old subbase Mount Q520A subbase Connect wires to subbase per attached cross reference Pay close attention to footnotes For example To convert a Fireye 26RJ81016 to a BC7000 the wire marked B would connect to terminal 10 on the Q520 The wire marked W would connect to Q520 terminal 14 The symbol designates a footnote Study these footnotes carefully Plug in the BC70...

Page 7: ...E1221A FIREYE 26RJ8 1016 1016T 26RJ8 1012 1012T 6012 6012T TO BC7000L PM720G2005 ...

Page 8: ...E1693 FIREYE 25RLJ84580 TO BC700L PM720L1030 ...

Page 9: ...E1217B FIREYE 25RU8 6560 6570 6580 26RJ8 6060 6070 6080 6160 TO BC7000L PM720L1030 ...

Page 10: ...E1218A FIREYE 29RF5 1001 1009 6009 TO BC7000L PM720G2013 ...

Page 11: ...E1219A 26RJ8 6058 6066 6068 25RU8 6558 6566 TO BC7000L PM720G2005 ...

Page 12: ...E1220A FIREYE 26RJ8 1002 1003 1008 1011 1018 6008 6018 29RF5 1000 1002 1005 1015 1104 29RF5 6015 TO BC7000L PM720G2005 ...

Page 13: ...Disconnect wires as they are marked Remove old subbase Mount Q520A subbase Connect wires to subbase per attached cross reference Pay close attention to footnotes For example To convert an R4126A1172 to a BC7000 the wire marked F2 would connect to terminal 3 on the Q520 The wire marked 3 would connect to Q520 terminal 14 The symbol designates a footnote Study these footnotes carefully Plug in the B...

Page 14: ...E1222A R4126A1172 1180 1198 TO BC7000L PM720L2004 ...

Page 15: ...E1223A R4126A1008 1016 1024 1032 1040 1057 1081 1149 R4126B1006 1014 1022 TO BC7000L PM720G2005 ...

Page 16: ...E1224A R4126A1073 1164 TO BC7000L PM720L2004 ...

Page 17: ...E1753 R4127A1155 AND R4127A1197 TO BC7000L PM720G2005 ...

Page 18: ...E1225A R4127 ALL MODELS EXCEPT R4127A1171 R4127A1155 R4127A1197 R4127B1039 AND R4127B1047 TO BC7000L PM720G ...

Page 19: ...E1724A R4127A1171 R4127B1039 R4127B1047 TO BC7000L PM720G2005 ...

Page 20: ...E1226A R4181A1000 R4181A1026 TO BC7000L PM720G2005 ...

Page 21: ...E1227A R4181A1018 R4181A1034 TO BC7000L PM720L2004 ...

Page 22: ...E1228A R4181A1042 R4181A1059 TO BC7000L PM720L2004 ...

Page 23: ...oks Vapor or Peabody Gordon Piatt models Preignition Interlock Models R4140G1007 R4140G1015 R4140G1106 R4140G1130 R4140G1148 R4140L All Models R4140M1145 R4140M1152 R4140M1160 R4140M1 178 R4150G1186 R4150L All Models All others have start interlocks If existing R4150 has 13 or 15 terminal subbase the subbase must be replaced with a 20 terminal Q520A See Section V 23 ...

Page 24: ...ERLOCKS 2 DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10 CONNECT IT TO TERMINAL 11 3 REMOVE JUMPER FROM TERMINAL BETWEEN TERMINAL 11 AND 12 on some models 4 IF LOW FIRE SWITCH IS NOT USED CONNECT JUMPER WIRE BETWEEN TERMINALS 8 AND 13 5 JUMPER 8 TO 15 FOR 30 SECOND PREPURGE 6 IF OLD CONTROL HAD 12 TO 11 JUMPERED ADD A JUMPER FROM 12 TO 16 E1235B ...

Page 25: ...002 2 DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10 AND CONNECT IT TO TERMINAL 11 3 4 5 REMOVE JUMPER FROM TERMINAL BETWEEN TERMINAL 11 AND 12 on some models IF LOW FIRE SWITCH IS NOT USED CONNECT JUMPER WIRE BETWEEN TERMINALS 8 AND 13 JUMPER TERMINALS 8 TO 15 FOR 30 SECOND PURGE E1237 ...

Page 26: ...INTERLOCKS BECOME PREIGNITION INTERLOCKS 2 3 4 FOR PM720G2005 ONLY JUMPER 15 TO 8 FOR 30 SECOND TRIAL FOR MAIN FLAME AT TERMINAL NO 6 TERMINAL 16 MUST BE USED ON THE BC7000 IF AN EXTERNAL TIE POINT WAS PREVIOUSLY USED ON THE R4140G OR R4150G TO BE REPLACED IT MUST BE LOCATED AND WIRED TO TERMINAL NO 16 FOR INTERMITTENT PILOT USE PM720G2013 E1234 1 26 ...

Page 27: ...L FOR Ji c MAIN AT TERMINAL 6 J BC7000L PM720G2005 PM720G2013 STEPS FOR CONVERSIO 1 IDENTIFY AND REMOVE BURNER CONTROLLER AND LIMITS CIRCUIT WIRE FROM TERMINAL NO 4 ON THE Q520A SUBBASE AND CONNECT TO TERMINAL NO 16 2 FOR PM720G2005 ONLY JUMPER 8 TO 15 FOR 30 SECOND TRIAL FOR MAIN FLAME AT TERMINAL 6 3 FOR INTERMITTENT PILOT USE PM720G2013 El 233 27 ...

Page 28: ...AND REMOVE BURNER CONTROLLER AND LIMITS CIRCUIT WIRE FROM TERMINAL NO 4 ON THE Q520A SUBBASE AND CONNECT TO TERMINAL NO 16 IDENTIFY AND REMOVE HIGH FIRE PROVING SWITCH WIRES FROM TERMINAL NO 8 AND CONNECT THEM TO TERMINAL L1 THE LOW FIRE SWITCH WIRE MAY BE CONNECTED TO TERMINAL NO 15 REMOVE FROM TERMINAL NO 15 AND CONNECT TO 8 E1236A FOR ENERGY SAVING PREPURGE USE PM720L2004 2 T 28 ...

Page 29: ...utor Mark all wires on subbase i e wires connected to terminal 9 should be marked 9 Disconnect wires as they are marked Remove old subbase Install 20 terminal Q520A subbase Connect wires to subbase per attached cross reference Pay close attention to footnotes Plug in the BC7000 Make sure you select the proper amplifier detector and program module for the application 29 ...

Page 30: ...E1229A CONVERSION FOR R4150A B AND C MODELS 120 VOLT ONLY USE BC7000L PM720M2002 ...

Page 31: ...E1230A CONVERSION FOR R4150G1004 G1020 G1046 G1103 G1111 G1145 G1178 MODELS 120 VOLT ONLY USE BC7000L PM720G2013 ...

Page 32: ...E1231A CONVERSION FOR R4150G1012 AND G1079 MODELS 120 VOLT ONLY USE BC7000L PM720M2002 ...

Page 33: ...E1232A CONVERSION FOR R4150M USE BC7000L PM720M2002 ...