background image

60-2159—8

2

C645A-E PRESSURE SWITCHES

SPECIFICATIONS

Models:

C645A,C,D Pressure Switches—break a circuit when

pressure falls to scale setting minus the differential.
Refer to Table 1.

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or your distributor, refer to the
TRADELINE® catalog or price sheets for complete ordering number, or specify—

1. Order number.

3. Optional specifications.

2. Air or gas control on C645A,B models.

4. Accessories, if desired.

If you have additional questions, need further information, or would like to comment on our products or services please write or phone:

1. Your local Honeywell Home and Building Control Sales Office (check white pages of your phone directory).
2. Honeywell Home and Building Control Customer Relations

Honeywell, 1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International sales and
service offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico,
Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

C645B Pressure Switches—break a circuit when pressure

rises to scale setting. Refer to Table 1.

C645E—breaks circuit when pressure falls to scale setting

minus the differential. Refer to Table 1.

Table 1. Pressure switch model selection.

a

Locks out when pressure falls to setpoint minus differential; can be reset manually after pressure rises to setpoint.

b

Locks out when pressure rises to setpoint; can be manually reset after pressure falls to setpoint minus differential.

c

Without indicator on Auto Recycle; with indicator on Lockout model.

d

With surge orifice.

Switch Ratings (Amperes):

Model

120 Vac

240 Vac

C645A

Full Load

7.4

3.7

C645B

Locked Rotor

44.4

22.2

C645D

C645C

Full Load

8.0

5.1

Locked Rotor

48.0

30.6

C645E

Full Load

7.4

3.7

Locked Rotor

44.4

22.2

All models also rated 2A at 30 Vac.

Alternate Electrical Ratings when used with Honeywell
Flame Safeguard Programmers (all C645 models):

Ignition
Transformer

540 VA

Pilot Valve

50

Main Valve

250 VA with 10 times inrush.  
400 VA with 2-1/2 times inrush.

Scale

Range  

Scale

Range  

Natural

or LP  

Switching  

Switch

Position  

Differential

Range  

(in. wc)

Differential

Range  

(kPa)

Maximum

Surge

Pressure  

Maximum

Surge

Pressure

Cover  

Models

(in. wc)

(kPa)

Gas

Air

Action

Indicator   Nom.

Max.   Nom.

Max.

(psi)  

 (kPa)

Window

C645A

3 to 21

0.7 to
5.2

Yes

Yes

Auto Recycle
or Lockout

a

Optional

1

3

0.2

0.7

5

34.5

Optional

5 to 35

1.2 to
8.7

Yes

Yes

c

1

4

0.2

1.0

5

34.5

Yes

C645B

3 to 21

0.7 to
5.2

Yes

Yes

Lockout

b

Yes

1

3

0.2

0.7

5

34.5

Optional

5 to 35

1.2 to
8.7

Yes

Yes

Yes

1

4

0.2

1.0

5

34.5

Yes

C645C

0.6 to
5.3  

0.1 to
1.3

No

Yes   Auto Recycle

or Lockout

a

  

Optional

0.2

0.8

0.05

0.02

1.5

10.3

No

2 to 20

d

0.5 to 5

No

Yes

Auto Recycle No

1

3

0.2

0.7

5

34.5

No

C645D

3 to 21

0.7 to
5.2

No

Yes   Auto Recycle No

1

3

0.2

0.7

5

34.5

No

C645E

3 to 21

0.7 to
5.2

No

Yes   Auto Recycle No

1

3

0.2

0.7

5

34.5

No

Summary of Contents for C645A-E

Page 1: ... optional in A and C models Removable zinc plated cover protects scaleplate and adjusting screw Lockout models have external manual reset lever Pipe tappings allow selection of positive pressure differential pressure or venting connections Optional switch position indicator available Models of C645A B available with cover window for setpoint visibility Buna N fiber reinforced material for increase...

Page 2: ... Locks out when pressure falls to setpoint minus differential can be reset manually after pressure rises to setpoint b Locks out when pressure rises to setpoint can be manually reset after pressure falls to setpoint minus differential c Without indicator on Auto Recycle with indicator on Lockout model d With surge orifice Switch Ratings Amperes Model 120 Vac 240 Vac C645A Full Load 7 4 3 7 C645B L...

Page 3: ...atories Inc Factory Mutual Approved Industrial Risk Insurers C645A D models with window in cover approvable for applications on burners over 5 million Btuh 5 thousand cfh input Optional Specifications 1 C645A with position indicator and manual reset 2 C645A operation to 1 5 in WC with position indicator and manual reset 3 C645B with position indicator and manual reset 4 C645C with position indicat...

Page 4: ...tion Installer must be a trained experienced service technician After installation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before beginning installation to prevent electrical shock or equipment damage Mounting The C645 has a hexagonal fitting with a 1 4 in NPT tapping which is the high pressure connection in differential application...

Page 5: ...nt damage All wiring must agree with applicable codes ordinances and regulations An opening is provided to accommodate rigid conduit or armored cable for line voltage operation Fig 3 and 4 Do not overload the switch contacts see Switch Ratings in Specifications section The switching schematic is shown in Fig 5 SET POINT ADJUSTMENT SCREW SCALE PLATE BLEED FITTING COVER SCREW OPENING FOR 1 2 INCH CO...

Page 6: ...8 a Nominal differential 1 in of water 0 2 kPa b Differential between 1 and 3 in of water 0 2 and 0 7 kPa c Maximum differential 3 in of water 0 7 kPa d Maximum differential 4 in of water 1 0 kPa e Maximum differential 5 7 in of water 1 4 kPa a Nominal differential 0 2 in of water 0 05 kPa b Differential between 0 2 and 0 8 in of water 0 05 and 1 2 kPa c Maximum differential 0 8 in of water 0 2 kP...

Page 7: ...hould break R W make R B when pressure drops to cutoff point Manual reset models lock out Remove obstruction Depress reset lever and allow system to operate through at least one complete cycle to make certain all components are functioning properly C645E1002 Distillate Fuel Oil Switch The C645E1002 is the same as the C645A1006 Gas Pressure Switch except the C645E1002 has a 0 125 in NPT main connec...

Page 8: ...e and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley Minnesota 55422 Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 2159 8 F P Rev 5 95 www honeywell com bbc ...

Reviews: