background image

60-2159—8

3

C645A-E PRESSURE SWITCHES

Switching:
Spdt Micro Switch snap-acting switch (Fig. 3).

Minimum Ambient Temperature:
-20

°

F (- 29

°

C).

Maximum Ambient Temperature:
125

°

F (52

°

C).

Connections:

1/4-18 NPT female tapping for main or high pressure

connection.

1/8-27 NPT female tapping for venting or low-pressure

connection.

Approvals:

Underwriters Laboratories Inc. listed: C645AE File

no. MP2168, Guide no. MFHX; for use in ambient
temperatures normally prevailing in occupiable spaces,
which usually are not higher than 77

°

F (25

°

C) but can

occasionally be as high as 104

°

F (40

°

C) for brief periods.

Canadian Standards Association listed: C645A-E, File no.

LR1620-369, Guide no. 140-A-2; for use subject to
same ambient temperature restrictions as Underwriters
Laboratories Inc.

Factory Mutual Approved.
Industrial Risk Insurers: C645A-D models with window in

cover approvable for applications on burners over
5 million Btuh (5 thousand cfh) input.

Optional Specifications:

1. C645A with position indicator and manual reset.
2. C645A operation to 1.5 in. WC with position indicator

and manual reset.

3. C645B with position indicator and manual reset.
4. C645C with position indicator and manual reset.
5. C645D with 2 in. (50.8 mm) differential.

Accessories:

1. C645A,B,D: Mounting Bracket: part no. 15865AC.
2. C645C: Mounting Bracket: part no. 112657A.
3. C645A: Cover with Window: part no. 137637B.
4. C645B: Cover with Window: part no. 137637C.

2-7/8 (73)

3-1/2
(88.9)

3/8
(9.5)

1-1/8
(28.6)

4
(101.6)

4-3/4
(120.6)

3-1/2 (88.9)

3/16 (2)
(4.8)

2-1/2 (63.5)

1-5/16
(33.3) 

5/8
(15.9)

1/4-18 NPT

1/8-27  NPT

MOUNTING
BRACKET
(OPTIONAL)

M7564

3/8 (9.5)

1

1

IMPORTANT: FOR MODELS WITH LOCKOUT, DO NOT OBSTRUCT MANUAL RESET LEVER.

Fig. 1. Dimensions of C645A,B,D, and E in in. (mm).

Summary of Contents for C645A-E

Page 1: ... optional in A and C models Removable zinc plated cover protects scaleplate and adjusting screw Lockout models have external manual reset lever Pipe tappings allow selection of positive pressure differential pressure or venting connections Optional switch position indicator available Models of C645A B available with cover window for setpoint visibility Buna N fiber reinforced material for increase...

Page 2: ... Locks out when pressure falls to setpoint minus differential can be reset manually after pressure rises to setpoint b Locks out when pressure rises to setpoint can be manually reset after pressure falls to setpoint minus differential c Without indicator on Auto Recycle with indicator on Lockout model d With surge orifice Switch Ratings Amperes Model 120 Vac 240 Vac C645A Full Load 7 4 3 7 C645B L...

Page 3: ...atories Inc Factory Mutual Approved Industrial Risk Insurers C645A D models with window in cover approvable for applications on burners over 5 million Btuh 5 thousand cfh input Optional Specifications 1 C645A with position indicator and manual reset 2 C645A operation to 1 5 in WC with position indicator and manual reset 3 C645B with position indicator and manual reset 4 C645C with position indicat...

Page 4: ...tion Installer must be a trained experienced service technician After installation is complete check out product operation as provided in these instructions CAUTION Disconnect power supply before beginning installation to prevent electrical shock or equipment damage Mounting The C645 has a hexagonal fitting with a 1 4 in NPT tapping which is the high pressure connection in differential application...

Page 5: ...nt damage All wiring must agree with applicable codes ordinances and regulations An opening is provided to accommodate rigid conduit or armored cable for line voltage operation Fig 3 and 4 Do not overload the switch contacts see Switch Ratings in Specifications section The switching schematic is shown in Fig 5 SET POINT ADJUSTMENT SCREW SCALE PLATE BLEED FITTING COVER SCREW OPENING FOR 1 2 INCH CO...

Page 6: ...8 a Nominal differential 1 in of water 0 2 kPa b Differential between 1 and 3 in of water 0 2 and 0 7 kPa c Maximum differential 3 in of water 0 7 kPa d Maximum differential 4 in of water 1 0 kPa e Maximum differential 5 7 in of water 1 4 kPa a Nominal differential 0 2 in of water 0 05 kPa b Differential between 0 2 and 0 8 in of water 0 05 and 1 2 kPa c Maximum differential 0 8 in of water 0 2 kP...

Page 7: ...hould break R W make R B when pressure drops to cutoff point Manual reset models lock out Remove obstruction Depress reset lever and allow system to operate through at least one complete cycle to make certain all components are functioning properly C645E1002 Distillate Fuel Oil Switch The C645E1002 is the same as the C645A1006 Gas Pressure Switch except the C645E1002 has a 0 125 in NPT main connec...

Page 8: ...e and Building Control Honeywell Inc 1985 Douglas Drive North Golden Valley Minnesota 55422 Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 60 2159 8 F P Rev 5 95 www honeywell com bbc ...