6.3.2 Tuning Analog input
Warning:
this procedure can be done just by specialized personnel
.
UNIT OFF
START TUNE
END
TUNE
Mantain Kay CAL pushed
and Switch ON
SSR input (3-30V)
is tuned
Analog input
is tuned
Wait for more than 10 sec.
from start flashing
yellow and red leds
Within 10 sec. from start
flashing yellow and red leds
push again momentary
CAL Key
Yellow led only is
flashing, apply
0 input Signal
I.E.: 0V for 0-10V
4mA for 4-20mA
Red led only is
flashing, apply
10V for 0-10V input
or
20mA for 4-20mA input
Now press CAL Key again
Now press CAL Key again
The leds will
stop flashing
Release key
when red and yellow
led are ON
Yello and red leds
are flashing
SSR
ANALOG
INPUT TYPE
ON
ON
ON
2sec.
S/C
S/C
S/C
H.B.
H.B.
H.B.
ON
S/C
H.B
ON
S/C
H.B
0 Signal
Max Signal