Terminal Assignment
Table 8. Terminal assignment
te
rmina
l no.
signal
Description
CL
EA2014Bxx
CL
EA2026Bxx
CL
EA2000Bxx
1
24V-0
supply voltage (GND), internally connected with term. 31 and system GND (term. 19+37)
X
X
X
2
24V~
supply voltage (24V)
X
X
X
3,4 -
not
used
- - -
5
BO1
Binary output 1. N.O. relay contact switching input power connected to terminal 8
-
X
-
6
BO2
Binary output 2. N.O. relay contact switching input power connected to terminal 8
-
X
-
7
BO3
Binary output 3. N.O. relay contact switching input power connected to terminal 8
-
X
-
8
IN1,2,3
Common relay contact for BO1, BO2, and BO3
-
X
-
9
IN4
Common relay contact for BO4
X
X
-
10
BO4
Binary output 4. N.O. relay contact switching input power connected to terminal 9
X
X
-
11
BO5
Binary output 5. N.O. relay contact switching input power connected to terminal 12
-
X
-
12
IN5
Common relay contact for BO5
-
X
-
13
IN6
Common relay contact for BO6
X
X
-
14
BO6
Binary output 6. N.O. relay contact switching input power connected to terminal 13
X
X
-
15
BO7
Binary output 7. N.O. relay contact switching input power connected to terminal 16
X
X
-
16
IN7
Common relay contact for BO7
X
X
-
17
IN8
Common relay contact for BO8
-
X
-
18
BO8
Binary output 8. N.O. relay contact switching input power connected to terminal 17
-
X
-
19
GND
Ground terminal (see NOTE below)
X
X
-
20
AO1
Analog output 1
X X -
21
AO2
Analog output 2
X X -
22
AO3
Analog output 3
- X -
23
AO4
Analog output 4
- X -
24
GND-1
ref. GND of RS485-1
(isolated)
X X X
25
485-1+
“+” signal for RS485-1 (isolated)
X
X
X
26
485-1-
“-” signal for RS485-1 (isolated)
X
X
X
27,28
not used
-
-
-
29
485-2+
“+” signal for RS485-2
(non-isolated)
X X X
30
485-2-
“-” signal for RS485-2 (non-isolated)
X
X
X
31
GND-2
ref. GND of RS485-2, int. connected with 24V-0 (term. 1) and system GND (term. 19+37)
X
X
X
32 -
not
used
- - -
33
BI1
Binary input 1 (static dry contact) / pulse counter (fast totalizer)
X
X
-
34
BI2
Binary input 2 (static dry contact) / pulse counter (fast totalizer)
X
X
-
35
BI3
Binary input 3 (static dry contact) / pulse counter (fast totalizer)
X
X
-
36
BI4
Binary input 4 (static dry contact) / pulse counter (fast totalizer)
X
X
-
37
GND
Ground terminal (see NOTE below)
X
X
-
38
UI9
Universal input 9 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
39
UI10
Universal input 10 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
40
UI1
Universal input 1 (for NTC20k
Ω
/ 0..10V / slow BI)
X
X
-
41
UI2
Universal input 2 (for NTC20k
Ω
/ 0..10V / slow BI)
X
X
-
42
UI3
Universal input 3 (for NTC20k
Ω
/ 0..10V / slow BI)
X
X
-
43
UI4
Universal input 4 (for NTC20k
Ω
/ 0..10V / slow BI)
X
X
-
44
UI5
Universal input 5 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
45
UI6
Universal input 6 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
46
UI7
Universal input 7 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
47
UI8
Universal input 8 (for NTC20k
Ω
/ 0..10V / slow BI)
-
X
-
NOTE: