background image

HAWK 8000 CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS 

EN1Z-1016GE51 R0218 

1

2

3

4

5

 

Fig. 8. Communication ports 

 

Legend 

1.

  RS485-B port and bias / termination switch 

2.

  RS485-A port and bias / termination switch 

3.

  PRI (primary) LAN1, 10/100-Mbit Ethernet connection 

(RJ45) 

4.

  SEC (secondary) LAN2, 10/100-Mbit Ethernet 

connection (RJ45) 

5.

  WiFi settings switch and WiFi antenna 

 

WiFi 

The HAWK 8000 is equipped with an integrated WiFi adapter 
(see Fig. 9) providing wireless connectivity using the IEEE 
802.11a/b/g/n standard. The RP-SMA antenna connector is 
for the connection of the tilt-and-swivel 2.4 GHz antenna 
included in the shipment. 
 

WiFi Configuration Switch 

Adjacent to the WiFi antenna is a 3-position configuration 
switch, with the following settings: 

OFF

 

(Default, middle position) WiFi adapter is disabled. 

ACC

 

(Left position) Controller provides operation as a 
WiFi access point for up to 20 clients. 

CLT

 

(Right position) Controller operates as a client to an 
existing 802.11a/b/g/n router or access point. 

To use, either screw in the antenna directly (see Fig. 9) or use 
an optional coax cable extension kit (CBL-WIFI-EXT) to locate 
the antenna up to 2 m away. An associated LED remains lit 
whenever the WiFi is enabled. 

ACC

OFF

CL

T

WLAN

 

Fig. 9. Attachment of WiFi antenna 

Refer to the HAWK 8000 – Installation & Startup Guide 
(EN1Z-1027GE51) for details on WLAN configuration and 
factory-default IP settings. 
 

Bus and Port Connections 

Overview 

Table 1. Overview of bus interfaces 

description

 

max. 

cable 

length

 

no. 

RS485-A and RS485-B, isolated: BACnet MS/TP, 
Panel Bus, or Modbus RTU Master or Slave com-
munication 

*1200 m 

Ethernet / RJ45 socket

 

SEC: e-mail communi-
cation, browser access 

100 m 

PRI: IP communication 

100 m 

WiFi antenna 

-- 

*Depending upon baud rate (see Table 2). 

 

Summary of Contents for Centra Line CLNXHAW-5K

Page 1: ...uded in Shipment 2 Overview of Features 3 Materials and Tools Required 4 Preparation 4 Mounting 4 Environmental Requirements 4 Dimensions Tab Mounting 4 Mounting on a DIN Rail 5 Wiring 5 Bus and Port Connections 6 Order Numbers 11 Drivers 11 Included Drivers 11 Optional Drivers 11 Specifications 12 Power 12 Environmental Specifications 12 Approvals Certifications etc 12 Related Technical Literatur...

Page 2: ...ety are invalidated Rules regarding electrostatic discharge should be followed Use only accessory equipment which comes from or has been approved by Honeywell Construction The HAWK 8000 Controller is an independently mounted electronic control unit with fixed wiring Mounting Method The HAWK 8000 Controller is suitable for mounting as follows in cabinets in fuse boxes conforming with standard DIN43...

Page 3: ...DC 50 60HZ 24W MAX OPERATING TEMPERATURE 20C to 60C REQ USE OF CLASS 2 24VAC TRANSFORMER OR EQUIVALENT 12977 8 Fig 1 HAWK 8000 overview of features 1 Earth ground 6 PRI primary LAN1 10 100 Mbit Ethernet connection 2 Terminal block for 24 VAC DC power supply 7 SEC secondary LAN2 10 100 Mbit Ethernet connection 3 RS485 A port and bias termination switch 8 Access shutter for microSD card slide to ope...

Page 4: ...ecial system password stored in the controller base software If you swap in a card from a previously configured unit you must re enter this same password using a serial connection to the controller s Debug port WARNING Risk of electric shock or equipment damage Disconnect the power supply before removing or inserting the microSD flash memory card Failure to do so is likely to damage the equipment ...

Page 5: ...ination 6 Carefully secure both ends of the final assembly with DIN rail end clips provided by the DIN rail vendor Wiring WARNING Risk of electric shock or equipment damage Before making power terminations de energize the 24V power source Do not restore power until completing all other mounting and wiring See also section Power Up and Initial Checkout on pg 8 Wiring Earth Ground and Power Earth gr...

Page 6: ...ition WiFi adapter is disabled ACC Left position Controller provides operation as a WiFi access point for up to 20 clients CLT Right position Controller operates as a client to an existing 802 11a b g n router or access point To use either screw in the antenna directly see Fig 9 or use an optional coax cable extension kit CBL WIFI EXT to locate the antenna up to 2 m away An associated LED remains ...

Page 7: ... baud and uses a 3 position screw terminal connector A A S RS485 A HAWK 8000 RS485 B DEVICE 1 DEVICE 1 DEVICE 2 DEVICE 2 DEVICE N DEVICE N B B S S S S S S S Fig 10 RS485 wiring example NOTE RS485 devices on the same network should use the same communication protocol and the same baud rate Up to 32 or more devices may be supported depending upon device specifications Use shielded twisted pair 18 22...

Page 8: ...predictable behavior if other electrically non isolated devices are connected and the potential difference is too high In the case of the installation of HAWK 8000 con trollers in already existent RS485 two wire systems e g when replacing PANTHER or LION controllers with HAWK 8000 controllers not using a separate signal ground wire will probably have no undesirable effects The cable length affects...

Page 9: ...at boot up also occurs during other critical operations such as a firmware upgrade to the controller and or any attached modules To be safe do not remove power from the controller while its BEAT LED is flashing in a 90 10 ON OFF duty cycle Instead wait for the normal 50 50 flash to return before removing power If the BEAT LED remains ON constantly does not light up or flashes very fast contact T A...

Page 10: ...s door opened Legend 1 BACKUP button and corresponding BACKUP LED 2 PROG USB 2 0 for use with USB flash thumb drive 3 DEBUG Micro A USB for serial debugging communications 4 SHT DWN Recessed pushbutton for initiating a controlled shutdown The DEBUG port is a standard Micro A type USB port for serial debugging communications to the controller You can use a serial terminal program for example PuTTY ...

Page 11: ...5 HAWK8 PLUS 1250 POINTS UPGRADE CLNX DEVICE UP 50 HAWK8 PLUS 2500 POINTS UPGRADE Table 8 Software upgrade licenses OS number description CLNX SMA 8005 1YR HAWK8 1YR SW UPDATE 250 499 PTS CLNX SMA 8005 3YR HAWK8 3YR SW UPDATE 250 499 PTS CLNX SMA 8005 5YR HAWK8 5YR SW UPDATE 250 499 PTS CLNX SMA 8010 1YR HAWK8 1YR SW UPDATE 500 1249 PTS CLNX SMA 8010 3YR HAWK8 3YR SW UPDATE 500 1249 PTS CLNX SMA 8...

Page 12: ... MTTF 10 years Dimensions See Fig 3 to Fig 5 APPROVALS CERTIFICATIONS ETC UL 916 Energy Management Equipment Edition 4 CE 2014 53 EU RED 2011 65 EU RoHs FCC Part 15 Subpart B Class B Part 15 Subpart C C UL listed to Canadian Standards Assoc CSA C22 2 No 205 M1983 Signal Equipment Ethernet IEEEC 802 3 Purpose of the device is multifunctional non safety control intended for HVAC in home residential ...