EAGLEHAWK NX CONTROLLER – INSTALLATION & COMMISSIONING INSTRUCTIONS
7
EN1Z-1039GE51 R1218
RS232 / RJ45 Socket
Via its RS232 / RJ45 socket, the EAGLEHAWK NX controller
can be connected (using an XW586 cable) to a PW M-Bus
Adapter and thus to M-Bus networks. See also section "M-
Bus Connection" on pg. 46.
EN
D
BIA
S
MI
D
RS232-RJ45 SOCKET
Fig. 4. RS232 / RJ45 socket
Configuring the RS232 Interface in COACH NX
When you configure the RS232 interface (for M-Bus) in
COACH NX, the corresponding Port Name will appear as
shown in Fig. 5.
Fig. 5. Configuring the RS232 Interface in COACH NX
USB 2.0 Host Interface
Via its USB 2.0 Host interface, the EAGLEHAWK NX con-
troller can be connected to, e.g., the IF-LON2 External Inter-
face Adapter and thus to L
ON
W
ORKS
networks. Max. 200 mA,
high speed. See also section "LonWorks Communications" on
pg. 39.
EN
D
BIAS MI
D
USB 2.0 HOST INTERFACE
Fig. 6. USB 2.0 Host interface
USB 2.0 Device Interface
All models of the EAGLEHAWK NX controller are equipped
with a USB 2.0 Device Interface at the front. This interface is
for connection to COACH NX and web browsers, or 3
rd
-party
touch panels.
USB 2.0 DEVICE INTERFACE
Fig. 7. USB 2.0 Device Interface
A standard USB type-B connector can be inserted into this
USB 2.0 Device Interface. This USB 2.0 Device Interface is
the recommended interface for connection to COACH NX.
Ethernet / RJ45 Sockets
The EAGLEHAWK NX controller is equipped with two
Ethernet / RJ45 sockets, each featuring two LEDs.
EN
D
BIAS MI
D
ETHERNET / RJ45 SOCKETS
INTER-
FACE 2
INTER-
FACE 1
Fig. 8. Ethernet / RJ45 sockets
The two Ethernet / RJ45 sockets are 10/100-Mbit/s Ethernet
interfaces permitting communication (as per IEEEC 802.3) on
any supported IP network, e.g.: BACnet (IP), FOX, etc.