R0315
I/O Module Overview
Panel Bus
module
L
ON
W
ORKS
Bus module
Description
Inputs Outputs
Manual controls LEDs
1)
CLIOP821A
CLIOL821A
Analog input module
8
–
–
–
CLIOP822A
CLIOL822A
Analog output module
–
8
–
8 status LEDs
CLIOPR822A CLIOLR822A Analog output module
–
8
8 Manual overrides 8 status LEDs
CLIOP823A
CLIOL823A
Binary input module
12
–
–
12 status LEDs
CLIOP824A
CLIOL824A
Relay output module
–
6
2)
–
6
status
LEDs
CLIOPR824A CLIOLR824A Relay output module
–
6
2)
6 Manual overrides 6 status LEDs
CLIOPR825A –
Floating output module
–
3
3 Manual overrides 3 pairs of status LEDs
CLIOP830A
--
Mixed I/O module
20
14
--
18 status LEDs
CLIOP831A
--
Mixed I/O module
20
14
--
18 status LEDs
1)
In addition to the power LED and service LED
2)
Changeover outputs
Table 3
Overview of I/O modules
Manual Overrides as per EN ISO 16484-2:2004
The manual override switches and potentiometers of the output modules (…R822A, …R824A, and CLIOPR825A) support direct
operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units."
Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the
LION Controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the cor-
responding output LED will blink continuously, and the output module will send a feedback signal with the status "manual
override" and the given override position to the LION Controller (which will then also store this information in its alarm memory).
NOTE:
When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Corresponding Terminal Sockets
I/O module
CLIOP/CLIOL…
Socket
Scope of delivery
…821
XS821-22
XSU821-22
1 terminal socket,
1 bridge connector
1 swivel label holder
…822
…823
XS823
XSU823
1 terminal socket,
1 bridge connector
1 swivel label holder
…824
XS824-25
XSU824-25
1 terminal socket,
1 bridge connector
1 swivel label holder
1 cross connector
…825
Table 4
Pluggable I/O modules and corresponding
terminal sockets
NOTE:
In the following, e.g., …822 is used to summarize
all analog output modules (Panel Bus/L
ON
W
ORKS