LION System
Planning
9
EN1Z-0921GE51
R0315
CentraLine 1450 Series (North America)
50/60 Hz
Insulated accessory outputs
Built-in fuses
Line transient /surge protection
AC convenience outlet
NEC Class-2
Part number
1450 7287
Primary side
Secondary side
-001
120 VAC
24 VAC, 50 VA
-002 120
VAC
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
-003 120
VAC
24 VAC, 100 VA,
and 24 VDC; 600 mA
-004
240/220 VAC 24 VAC, 50 VA
-005 240/220
VAC
2 x 24 VAC, 40 VA,
and 100 VA from separate
transformer
-006 240/220
VAC
24 VAC, 100 VA, and
24 VDC, 600 mA
Table 12 CentraLine 1450 series transformers data
Standard Transformers (Europe, North America)
Standard commercially available transformers used to
supply power to LION Systems must fulfill the following
specifications:
Output voltage
Impedance
AC current
24.5 VAC to 25.5 VAC
1.15
Ω
max. 2 A
24.5 VAC to 25.5 VAC
0.40
Ω
max. 6 A
24.5 VAC to 25.5 VAC
0.17
Ω
max. 12 A
Table 13 Requirements for standard transformers
RIN-APU24 Uninterruptable Power Supply
The RIN-APU24 Uninterruptable Power Supply can be wired
to power LION Systems.
See also RIN-APU24 Uninterruptable Power Supply –
Mounting Instructions (MU1B-0258GE51) for detailed wiring
diagrams.
Power Supply of Field Devices
Depending upon the power consumption of the field devices
used, it is possible to use either a single transformer to
power both the CLLIONLC01 and attached field devices, or
it may be necessary to employ an additional transformer.
See also section "Field Device Cables" on page 12 and
connection examples on page 28.
Fusing Specifications
Please observe the following when selecting fusing (F1 / F2)
for the CLLIONLC01, I/O modules, and active field devices:
Use separate fusing for different loads (e.g., for the
CLLIONLC01 and I/O modules on one hand versus for
active field devices on the other).
Fuse ratings must always be calculated according to the
loads connected. Refer to the load tables appearing in
the documentation of your devices (Table 10 provides
information on LION device loads).
Use slow-acting fuses; this is because the CLLIONLC01,
the I/O modules, and active field devices have a high in-
rush current due to their built-in capacitors (current
typically limited by one internal 2 Ohm resistor per
device).
Fuses should be calculated to protect the transformer
against overloading and the wiring against short-
circuiting. The CLLIONLC01 and the I/O modules are
protected by an internal fuse (not user-replaceable)
against internal component defects.
For connection examples see description of the I/O modules
on page 38 and following.
System Protective Earth Grounding
LION Systems comply with SELV (Safety Extra-Low
Voltage). Earth grounding is therefore not recommended.
However, if compliance with EN60204-1 is required, see
Appendix 1.
Lightning Protection
Please contact your local CentraLine representative for
information on lightning protection.
Panel Bus Topologies
Up to 16 Panel Bus I/O modules can be controlled by a
single CLLIONLC01.
Panel Bus I/O modules must be addressed using the
HEX switch on the terminal socket.
Max. Panel Bus length: 40 meters. Any type of cabling
and topology (including star and loop topology) permitted.
Bus termination unnecessary
Polarity-insensitive