background image

LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA 

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Rolle, Z.A. La Pièce 16, Switzerland by its Authorized Representative:

 

 
CentraLine 
Honeywell GmbH 
Böblinger Strasse 17 
71101 Schönaich, Germany 
Phone  +49 (0) 7031 637 845 
Fax 

+49 (0) 7031 637 740 

info@centraline.com

 

www.centraline.com 

 

 
 
 
 
 
 
Subject to change without notice 
EN0Z-0959GE51 R0615 

 

 

 

 

 

Controller Replacement (AS-models) 

For AS-models (which are hard-wired to an actuator), perform 
the following actions to replace the complete assembly 
(controller and actuator): 
1)  Remove all power from the controller. 
2)  Remove the two air flow pickup connections from the 

pressure sensor. 

3)  Remove the terminal blocks (see section “Terminal Block 

Removal”). 

4)  Remove the old controller and actuator assembly from its 

mounting. 
a)  Loosen the two bolts on the actuator clamp to 

release the actuator from the shaft. 

b)  Remove the controller’s mounting screws. 
c)  Gently pull the controller and actuator assembly 

straight out, until the assembly is clear of the 
actuator shaft. 

5)  Mount the new controller and actuator assembly (see 

section “Installation” on page 2). 

6)  Reconnect the two air flow pickup tubes to the pressure 

sensor (see section “Piping (AS- and NS-models)” on 
page 5). 

7)  Replace the terminal blocks: 

a)  Insert each terminal block onto its alignment pins. 
b)  Press straight down to firmly seat it. 
c)  Repeat for each terminal block. 

8)  Restore power to the controller. 
9)  Perform procedure described in section “Checkout” on 

page 14. 

 

Controller Replacement (NS-models) 

To replace NS-models, proceed as follows: 
1)  Remove all power from the controller. 
2)  Remove the two air flow pickup connections from the 

pressure sensor. 

3)  Remove the terminal blocks (see section “Terminal Block 

Removal”). 

4)  Remove the old controller from its mounting. 
 

IMPORTANT 
(IN THE CASE OF CONTROLLERS MOUNTED TO A DIN 
RAIL): 

1)  Push straight up from the bottom to release the top 

pins. 

2)  Rotate the top of the controller outwards to release the 

bottom flex connectors (see Fig. 7). 

 
5)  Mount the new controller (see section “Installation” on 

page 2). 

6)  Reconnect the two air flow pickup tubes to the pressure 

sensor (see section “Piping (AS- and NS-models)” on 
page 5). 

7)  Replace the terminal blocks: 

a)  Insert each terminal block onto its alignment pins. 
b)  Press straight down to firmly seat it. 
c)  Repeat for each terminal block. 

8)  Restore power to the controller. 
9)  Perform procedure described in section “Checkout” on 

page 14. 

 

Controller Replacement (S-models) 

To replace S-models, proceed as follows: 
1)  Remove all power from the controller. 
2)  Remove the terminal blocks (see section “Terminal Block 

Removal”). 

3)  Remove the old controller from its mounting. 
 

IMPORTANT 
(IN THE CASE OF CONTROLLERS MOUNTED TO A DIN 
RAIL): 

1)  Push straight up from the bottom to release the top 

pins. 

2)  Rotate the top of the controller outwards to release 

the bottom flex connectors (see Fig. 7). 

 
4)  Mount the new controller (see section “Installation” on 

page 2). 

5)  Replace the terminal blocks: 

a)  Insert each terminal block onto its alignment pins. 
b)  Press straight down to firmly seat it. 
c)  Repeat for each terminal block. 

6)  Restore power to the controller. 
7)  Perform procedure described in section “Checkout” on 

page 14. 

 
BACnet® is a registered trademark of ASHRAE. 
BTL® is a registered trademark of the BACnet International. 
N

IAGARA 

F

RAMEWORK

® and the Niagara framework logo are 

registered trademarks of Tridium, Inc. 
 

Summary of Contents for CentraLine LYNX BACnet CLLYUB1012S

Page 1: ...nications Each controller has flexible universal inputs for wall modules digital inputs and a mix of analog and digital triac outputs see Table 1 The models CLLYVB6436AS CLLYVB0000AS and CLLYVB4022AS include an actuator Table 1 Controller configurations model type Universal Inputs UI Digital Inputs DI Analog Out puts AO Digital Out puts DO velocity pressure sensor Microbridge floating actuator CLL...

Page 2: ... Analog voltage outputs Voltage output range 0 10 Vdc Max output current 10 0 mA UNIVERSAL INPUT UI CIRCUITS See Table 2 for UI circuit specifications Table 2 Universal input circuit specifications input type sensor type operating range Room Zone Discharge Air Outdoor Air Temp NTC 20kOhm 40 93 C Outdoor Air Temperature PT1000 IEC751 3850 40 93 C Resistive Input Generic 100 Ω 100 kΩ Voltage Input T...

Page 3: ...ersal shaft adapter see Fig 1 UNIVERSAL SHAFT CLAMPING BOLTS 2 UNIVERSAL SHAFT ADAPTER MECHANICAL END LIMIT SET SCREWS 2 DECLUTCH BUTTON Fig 1 Floating actuator IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 and Fig 3 for examples DAMPER DAMPER SHAFT ROTATES CW TO OPEN Fig 2 Damper with 90 clockwise rotation to open IMPORTANT Mount actuator flush with dam...

Page 4: ...gether to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 3 0 3 5 Nm torque d Using the DECLUTCH button rotate the universal shaft adapter fully CCW e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 8 10 Nm torque g When the actuator closes the damper rotates CW either 45 or 60 to fully cl...

Page 5: ...10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20 Fig 6 Panel mounting dimensions in mm S and NS models NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts using four screws inserted through the corners of the base plate Fasten securely with four screws The controller can be mounted ...

Page 6: ...ionships early in the job engineering process to ensure proper implementation when configuring the controllers See the controller Application Guides Power Budget A power budget must be calculated for each device to deter mine the required transformer size for proper operation A power budget is simply the sum of the max power draw ratings in VA of all the devices to be controlled This includes the ...

Page 7: ...wiring recommendations see section Power on page 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 9 9 OUTPUT DEVICE POWER TRANSFORMER 120 240 VAC COM 24 VAC EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND WHEN CONNECTING POWER TO THE LYNX BACnet CONTROLLER CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND CONNECT POWER TO TERMINALS 1 A...

Page 8: ...e rated characteristic impedance of the installed cable E g if the installed MS TP cable has a listed characteristic impedance of 120 Ω install 120 Ω matched precision resistors NOTE LYNX controllers do not provide network biasing Shield Terminating Following proper MS TP cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by ...

Page 9: ...t present The actuator is internally hardwired to these terminals C Analog outputs may be configured as digital outputs and operate as follows FALSE 0 0 Vdc 0 mA TRUE 100 the max 11 Vdc 22 mA D Digital inputs open circuit FALSE closed circuit TRUE UI 1 is selectable as a fast digital pulse meter Table 5 Description of wiring terminals CLLYVB0000AS CLLYVB4022AS and CLLYVB6436AS TERMINAL LABEL CONNE...

Page 10: ...gital inputs see Fig 17 Typical controller wiring for 4 20 mA heating cooling and model ML6161 floating motor control see Fig 18 Typical controller wiring for a pneumatic transducer model RP7517B see Fig 19 24VAC BACnet MS TP BACnet MS TP SHIELD 24VAC COM REHEAT STAGE 3 REHEAT STAGE 2 OR CLOSE REHEAT STAGE 1 OR OPEN DAMPER CLOSE DAMPER OPEN C770A AIR TEMP SENSOR AIR FLOW PICK UP WINDOW CONTACTS CO...

Page 11: ...LVE ACTUATOR PWM VALVE ACTUATOR PWM OUTPUT FROM CONTROLLER PWM H 24 VAC T5 T6 C B W R 24 N 24 H 2 3 3 3 2 1 3 4 ON OFF ML7984B CONFIGURATION DIP SWITCHES LOCATED ADJACENT TO THE INPUT TERMINAL BLOCK PERIPHERAL HEAT VALVE ACTUATOR ML7984B REHEAT VALVE ACTUATOR CLLYUB6438S DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 ...

Page 12: ...her 4 20 mA signal devices Place this resistor as close as possible to the driven device CLCM4T111 WALL MODULE GND SENSOR SET POINT BYPASS LED 5 6 7 4 3 2 1 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 1 2 3 4 5 6 7 8 1 1 1 1 1 1 1 1 1 1 2 1 2 3 4 5 6 7 8 9 0 0 9 CLLYUB6438S 24 VAC 24 VAC COM E GND SHLD SBUS1 SBUS2 NET 1 NET 2 DO 1 DO 2 COM COM COM COM DO 3 DO 4 ...

Page 13: ...g diagram CLLYUB6438S shown with 4 20 mA heating cooling and ML6161 damper actuator NOTE 1 Earth ground wire length should be held to a minimum Use the heaviest gauge wire available up to 14 AWG 2 0 mm 2 with a minimum of 18 AWG 1 0 mm 2 for earth ground wire NOTE 2 Ensure that all transformer power wiring is as shown Reversing terminations will result in equipment malfunction 1 2 3 4 5 6 7 8 9 0 ...

Page 14: ...ee Fig 11 Correct placement of the end of line termination resistors is required for proper BACnet MS TP Bus communications Step 2 Startup See Fig 20 and the following text for startup information CLLYVB6438NS DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 COM COM COM DI 3 DI 4 20VDC UI 1 COM UI 2 UI 3 COM UI 4 UI 5 C...

Page 15: ...vere injury death or property damage Do not attempt to modify the physical or electrical characteristics of this device in any way If trouble shooting indicates a malfunction replace the controller WARNING Electrical Shock Hazard Can cause severe injury death or property damage To prevent electrical shock or equipment damage disconnect power supply before beginning controller replacement Terminal ...

Page 16: ... proceed as follows 1 Remove all power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks see section Terminal Block Removal 4 Remove the old controller from its mounting IMPORTANT IN THE CASE OF CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards...

Reviews: