background image

LYNX BACNET PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA 

EN0Z-0959GE51 R0615 

NOTE 1:

  If controllers are mounted in unusually dusty or 

dirty environments, an inline, 5-micron disposable 
air filter (use 5-micron filters compatible with 
pneumatic controls) is recommended for the high-
pressure line (marked as +) connected to the air 
flow pickup. 

NOTE 2:

  The tubing from the air flow pickup to the controller 

should not exceed 1 m. Any length greater than 
this will degrade the flow sensing accuracy. 

NOTE 3:

  Use caution when removing tubing from a con-

nector. Always pull straight away from the con-
nector or use diagonal cutters to cut the edge of 
the tubing attached to the connector. Never 
remove by pulling at an angle. 

1 2 3 4 5 6 7 8 9 0 1

2 2 2 2 2 2 2 2 2 2 3

NS- and AS-models

P

AIR FLOW

PICK-UP

RESTRICTOR

PORTS

 

Fig. 8. Air flow pick-up connections 

 

Power 

Before wiring the controller, determine the input and output 
device requirements for each controller used in the system. 
Select input and output devices compatible with the controller 
and the application. Consider the operating range, wiring 
requirements, and the environment conditions when selecting 
input/output devices. When selecting actuators for modulating 
applications, consider using floating control. In direct digital 
control applications, floating actuators will generally provide 
control action equal to or better than an analog input actuator 
for lower cost. 
Determine the location of controllers, sensors, actuators, and 
other input/output devices and create wiring diagrams. See 
Fig. 14 through Fig. 20 for typical controller wiring con-
figurations. 
The application engineer must review the control job require-
ments. This includes the sequences of operation for the con-
troller, and for the system as a whole. Usually, there are 
variables that must be passed between the controller and 
other controllers that are required for optimum system wide 
operation. Typical examples include the outdoor air tem-
perature, the demand limit control signal, and the smoke 
control mode signal. 

It is important to understand these interrelationships early in 
the job engineering process, to ensure proper implementation 
when configuring the controllers. See the controller 
Application Guides. 
 

Power Budget 

A power budget must be calculated for each device to deter-
mine the required transformer size for proper operation. A 
power budget is simply the sum of the max. power draw 
ratings (in VA) of all the devices to be controlled. This 
includes the controller itself and any devices powered from 
the controller, such as equipment actuators and various 
contactors and transducers. 
 

IMPORTANT 

When multiple controllers operate from a single 
transformer, connect the same side of the transformer 
secondary to the same power input terminal in each 
device. The earth ground terminal (terminal 3) must be 
connected to a verified earth ground for each controller 
in the group (see Fig. 10). 
Half-wave devices and full-wave devices must not use 
the same AC transformer. If a LYNX controller is to 
share its power supply with another device, make sure 
the other device utilizes a half-wave rectifier and that 
the polarity of the wiring is maintained. 

 

Wiring 

All wiring must comply with applicable electrical codes and 
ordinances, or as specified on installation wiring diagrams. 
Controller wiring is terminated to the screw terminal blocks 
located on the top and the bottom of the device. 
 

 WARNING 

Electrical Shock Hazard. 

Can cause severe injury, death or property 

damage.

 

To prevent electrical shock or equipment damage, 

disconnect power supply before beginning wiring or 
making wiring connections. 

NOTE 1:

  For multiple controllers operating from a single 

transformer, the same side of the transformer 
secondary must be connected to the same power 
input terminal in each controller. Controller con-
figurations will not necessarily be limited to three 
devices, but the total power draw, including 
accessories, cannot exceed 100 VA when powered 
by the same transformer (U.S., only). For power 
and wiring recommendations, See section “Power” 
on page 6. The earth ground terminal (terminal 3) 
must be connected to a verified earth ground for 
each controller in the group (see Fig. 10). 

NOTE 2: 

All loads on the controller must be powered by the 
same transformer powering the controller itself. A 
controller can use separate transformers for con-
troller power and output power. 

Summary of Contents for CentraLine LYNX BACnet CLLYUB1012S

Page 1: ...nications Each controller has flexible universal inputs for wall modules digital inputs and a mix of analog and digital triac outputs see Table 1 The models CLLYVB6436AS CLLYVB0000AS and CLLYVB4022AS include an actuator Table 1 Controller configurations model type Universal Inputs UI Digital Inputs DI Analog Out puts AO Digital Out puts DO velocity pressure sensor Microbridge floating actuator CLL...

Page 2: ... Analog voltage outputs Voltage output range 0 10 Vdc Max output current 10 0 mA UNIVERSAL INPUT UI CIRCUITS See Table 2 for UI circuit specifications Table 2 Universal input circuit specifications input type sensor type operating range Room Zone Discharge Air Outdoor Air Temp NTC 20kOhm 40 93 C Outdoor Air Temperature PT1000 IEC751 3850 40 93 C Resistive Input Generic 100 Ω 100 kΩ Voltage Input T...

Page 3: ...ersal shaft adapter see Fig 1 UNIVERSAL SHAFT CLAMPING BOLTS 2 UNIVERSAL SHAFT ADAPTER MECHANICAL END LIMIT SET SCREWS 2 DECLUTCH BUTTON Fig 1 Floating actuator IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 and Fig 3 for examples DAMPER DAMPER SHAFT ROTATES CW TO OPEN Fig 2 Damper with 90 clockwise rotation to open IMPORTANT Mount actuator flush with dam...

Page 4: ...gether to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 3 0 3 5 Nm torque d Using the DECLUTCH button rotate the universal shaft adapter fully CCW e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 8 10 Nm torque g When the actuator closes the damper rotates CW either 45 or 60 to fully cl...

Page 5: ...10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20 Fig 6 Panel mounting dimensions in mm S and NS models NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts using four screws inserted through the corners of the base plate Fasten securely with four screws The controller can be mounted ...

Page 6: ...ionships early in the job engineering process to ensure proper implementation when configuring the controllers See the controller Application Guides Power Budget A power budget must be calculated for each device to deter mine the required transformer size for proper operation A power budget is simply the sum of the max power draw ratings in VA of all the devices to be controlled This includes the ...

Page 7: ...wiring recommendations see section Power on page 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 9 9 OUTPUT DEVICE POWER TRANSFORMER 120 240 VAC COM 24 VAC EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND WHEN CONNECTING POWER TO THE LYNX BACnet CONTROLLER CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND CONNECT POWER TO TERMINALS 1 A...

Page 8: ...e rated characteristic impedance of the installed cable E g if the installed MS TP cable has a listed characteristic impedance of 120 Ω install 120 Ω matched precision resistors NOTE LYNX controllers do not provide network biasing Shield Terminating Following proper MS TP cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by ...

Page 9: ...t present The actuator is internally hardwired to these terminals C Analog outputs may be configured as digital outputs and operate as follows FALSE 0 0 Vdc 0 mA TRUE 100 the max 11 Vdc 22 mA D Digital inputs open circuit FALSE closed circuit TRUE UI 1 is selectable as a fast digital pulse meter Table 5 Description of wiring terminals CLLYVB0000AS CLLYVB4022AS and CLLYVB6436AS TERMINAL LABEL CONNE...

Page 10: ...gital inputs see Fig 17 Typical controller wiring for 4 20 mA heating cooling and model ML6161 floating motor control see Fig 18 Typical controller wiring for a pneumatic transducer model RP7517B see Fig 19 24VAC BACnet MS TP BACnet MS TP SHIELD 24VAC COM REHEAT STAGE 3 REHEAT STAGE 2 OR CLOSE REHEAT STAGE 1 OR OPEN DAMPER CLOSE DAMPER OPEN C770A AIR TEMP SENSOR AIR FLOW PICK UP WINDOW CONTACTS CO...

Page 11: ...LVE ACTUATOR PWM VALVE ACTUATOR PWM OUTPUT FROM CONTROLLER PWM H 24 VAC T5 T6 C B W R 24 N 24 H 2 3 3 3 2 1 3 4 ON OFF ML7984B CONFIGURATION DIP SWITCHES LOCATED ADJACENT TO THE INPUT TERMINAL BLOCK PERIPHERAL HEAT VALVE ACTUATOR ML7984B REHEAT VALVE ACTUATOR CLLYUB6438S DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 ...

Page 12: ...her 4 20 mA signal devices Place this resistor as close as possible to the driven device CLCM4T111 WALL MODULE GND SENSOR SET POINT BYPASS LED 5 6 7 4 3 2 1 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 1 2 3 4 5 6 7 8 1 1 1 1 1 1 1 1 1 1 2 1 2 3 4 5 6 7 8 9 0 0 9 CLLYUB6438S 24 VAC 24 VAC COM E GND SHLD SBUS1 SBUS2 NET 1 NET 2 DO 1 DO 2 COM COM COM COM DO 3 DO 4 ...

Page 13: ...g diagram CLLYUB6438S shown with 4 20 mA heating cooling and ML6161 damper actuator NOTE 1 Earth ground wire length should be held to a minimum Use the heaviest gauge wire available up to 14 AWG 2 0 mm 2 with a minimum of 18 AWG 1 0 mm 2 for earth ground wire NOTE 2 Ensure that all transformer power wiring is as shown Reversing terminations will result in equipment malfunction 1 2 3 4 5 6 7 8 9 0 ...

Page 14: ...ee Fig 11 Correct placement of the end of line termination resistors is required for proper BACnet MS TP Bus communications Step 2 Startup See Fig 20 and the following text for startup information CLLYVB6438NS DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 COM COM COM DI 3 DI 4 20VDC UI 1 COM UI 2 UI 3 COM UI 4 UI 5 C...

Page 15: ...vere injury death or property damage Do not attempt to modify the physical or electrical characteristics of this device in any way If trouble shooting indicates a malfunction replace the controller WARNING Electrical Shock Hazard Can cause severe injury death or property damage To prevent electrical shock or equipment damage disconnect power supply before beginning controller replacement Terminal ...

Page 16: ... proceed as follows 1 Remove all power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks see section Terminal Block Removal 4 Remove the old controller from its mounting IMPORTANT IN THE CASE OF CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards...

Reviews: