background image

LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA 

  

EN0Z-0959GE51 

R0615 

7

NOTE 3:

  A jumper should be installed between 24 VAC 

COM (term. 2) and EGND (term. 3). Further, 
EGND (term. 3) should be connected to a verified 
earth ground, and kept as short as possible. 

NOTE 4:

  Do not connect the universal input COM terminals, 

analog output COM terminals or the digital 
input/output COM terminals to earth ground. See 
Fig. 13 through Fig. 18 for wiring examples. 

The 24 Vac power from an energy limited Class II power 
source must be provided to the controller. To conform to 
Class II restrictions (U.S., only), the transformer must not be 
larger than 100 VA. 
Fig. 9 depicts a single controller using one transformer. 
 

IMPORTANT 

Power must be OFF prior to connecting to or removing 
connections from the 24 Vac power (24 Vac/24 Vac 
COM), earth ground (EGND), and 20 Vdc power (20 
Vdc) terminals. 

 

IMPORTANT 

Use the heaviest gauge wire available, up to 2.0 mm

2

with a min. of 1.0 mm

2

, for all power and earth ground 

wiring. 
Screw-type terminal blocks are designed to accept up 
to one 2.0 mm

2

 conductor or up to two 1.0 mm

2

 con-

ductors. More than two wires that are 2.0 mm

2

 can be 

connected with a wire nut. Include a pigtail with this 
wire group and attach the pigtail to the terminal block. 

 

IMPORTANT 

Connect terminal 2, (the 24 Vac common [24 VAC 
COM] terminal) to earth ground (see Fig. 9). 

NOTE:

 

Unswitched 24 Vac power wiring can be run in the 
same conduit as the BACnet MS/TP cable. 

1 2 3 4 5 6 7 8

9

OUTPUT

DEVICE POWER

TRANSFORMER

LINE VOLTAGE

> 150 VAC

COM

24 VAC

EARTH GROUND

(TERMINAL 3)

EARTH

GROUND

WHEN CONNECTING POWER TO THE LYNX BACnet

CONTROLLER, CONNECT THE COM LEG OF THE VAC

SECONDARY CIRCUIT TO A KNOWN EARTH GROUND.

CONNECT POWER TO

TERMINALS 1 AND 2.

 

Fig. 9. Power wiring details for one LYNX controller per 

transformer 

More than one controller can be powered by a single trans-
former. Fig. 10 shows power wiring details for multiple con-
trollers. 

NOTE:

 

Controller configurations are not necessarily limited 
to three devices, but the total power draw, 
including accessories, cannot exceed 100 VA 
when powered by the same transformer (U.S., 
only). For power wiring recommendations, see 
section “Power” on page 6. 

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

9

9

9

OUTPUT DEVICE POWER

TRANSFORMER

120/240 VAC

COM

24 VAC

EARTH GROUND

(TERMINAL 3)

EARTH GROUND

(TERMINAL 3)

EARTH GROUND

(TERMINAL 3)

EARTH

GROUND

WHEN CONNECTING POWER TO THE LYNX BACnet

CONTROLLER, CONNECT THE COM LEG OF THE VAC

SECONDARY CIRCUIT TO A KNOWN EARTH GROUND.

CONNECT POWER TO

TERMINALS 1 AND 2.

CONNECT POWER TO

TERMINALS 1 AND 2.

CONNECT POWER TO

TERMINALS 1 AND 2.

 

Fig. 10. Power wiring details for two or more LYNX 

controllers per transformer 

 

Communications 

Each LYNX controller uses a BACnet MS/TP communications 
port. The controller’s data is presented to other controllers 
over a twisted-pair MS/TP network, which uses the EIA-485 
signaling standard capable of the following baud rates: 9.6, 
19.2, 38.4, 76.8 or 115.2 kilobits per sec (configured at global 
controller). The LYNX controllers are master devices on the 
MS/TP network. Each LYNX controller uses a high-quality 
EIA-485 transceiver and exerts ¼ unit load on the MS/TP 
network. 
Cabling should be selected that meets or exceeds the 
BACnet Standard which specifies the following: An MS/TP 
EIA-485 network shall use shielded, twisted-pair cable with 
characteristic impedance of 100…130 

. Distributed 

capacitance between conductors shall be less than 100 pF 
per meter. Distributed capacitance between conductors and 
shield shall be less that 200 pF per meter. Foil or braided 
shields are acceptable. The Honeywell tested and 
recommended MS/TP cable is Honeywell Cable 3322 (18 
AWG, 1-Pair, Shielded, Plenum cable), alternatively 
Honeywell Cable 3251 (22 AWG, 1-Pair, Shielded, Plenum 
cable) is available and meets the BACnet Standard require-
ments (www.honeywellcable.com). 
The max. BACnet MS/TP network Bus segment length is 
1,219 m using recommended wire. Repeaters must be used 
when making runs longer than 1,219 m. A max. of three 
repeaters can be used between any two devices. 
 

Setting the MS/TP MAC Address 

The MS/TP MAC address for each device must be set to a 
unique value in the range of 0-127 on an MS/TP network 
segment (address 0, 1, 2, & 3 should be avoided as they are 
commonly used for the router, diagnostic tools, and as spare 
addresses). DIP switches on the LYNX controller are used to 
set the controller's MAC address. 
To set the MS/TP MAC address of a LYNX controller: 

Summary of Contents for CentraLine LYNX BACnet CLLYUB1012S

Page 1: ...nications Each controller has flexible universal inputs for wall modules digital inputs and a mix of analog and digital triac outputs see Table 1 The models CLLYVB6436AS CLLYVB0000AS and CLLYVB4022AS include an actuator Table 1 Controller configurations model type Universal Inputs UI Digital Inputs DI Analog Out puts AO Digital Out puts DO velocity pressure sensor Microbridge floating actuator CLL...

Page 2: ... Analog voltage outputs Voltage output range 0 10 Vdc Max output current 10 0 mA UNIVERSAL INPUT UI CIRCUITS See Table 2 for UI circuit specifications Table 2 Universal input circuit specifications input type sensor type operating range Room Zone Discharge Air Outdoor Air Temp NTC 20kOhm 40 93 C Outdoor Air Temperature PT1000 IEC751 3850 40 93 C Resistive Input Generic 100 Ω 100 kΩ Voltage Input T...

Page 3: ...ersal shaft adapter see Fig 1 UNIVERSAL SHAFT CLAMPING BOLTS 2 UNIVERSAL SHAFT ADAPTER MECHANICAL END LIMIT SET SCREWS 2 DECLUTCH BUTTON Fig 1 Floating actuator IMPORTANT Determine the damper rotation and opening angle prior to installation See Fig 2 and Fig 3 for examples DAMPER DAMPER SHAFT ROTATES CW TO OPEN Fig 2 Damper with 90 clockwise rotation to open IMPORTANT Mount actuator flush with dam...

Page 4: ...gether to reduce the rotation travel c Tighten the two mechanical end limit screws Phillips 2 screwdriver 3 0 3 5 Nm torque d Using the DECLUTCH button rotate the universal shaft adapter fully CCW e Mount the actuator to the VAV damper box and shaft f Tighten the two bolts on the centering clamp 8 mm wrench 8 10 Nm torque g When the actuator closes the damper rotates CW either 45 or 60 to fully cl...

Page 5: ...10 11 12 13 14 15 16 17 18 19 20 9 10 11 12 13 14 15 16 17 18 19 20 Fig 6 Panel mounting dimensions in mm S and NS models NOTE The controller is designed so that the cover does not need to be removed from the base plate for either mounting or wiring The controller mounts using four screws inserted through the corners of the base plate Fasten securely with four screws The controller can be mounted ...

Page 6: ...ionships early in the job engineering process to ensure proper implementation when configuring the controllers See the controller Application Guides Power Budget A power budget must be calculated for each device to deter mine the required transformer size for proper operation A power budget is simply the sum of the max power draw ratings in VA of all the devices to be controlled This includes the ...

Page 7: ...wiring recommendations see section Power on page 6 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 9 9 9 OUTPUT DEVICE POWER TRANSFORMER 120 240 VAC COM 24 VAC EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND TERMINAL 3 EARTH GROUND WHEN CONNECTING POWER TO THE LYNX BACnet CONTROLLER CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND CONNECT POWER TO TERMINALS 1 A...

Page 8: ...e rated characteristic impedance of the installed cable E g if the installed MS TP cable has a listed characteristic impedance of 120 Ω install 120 Ω matched precision resistors NOTE LYNX controllers do not provide network biasing Shield Terminating Following proper MS TP cabling shield grounding procedures is important to minimize the risk of communication problems and equipment damage caused by ...

Page 9: ...t present The actuator is internally hardwired to these terminals C Analog outputs may be configured as digital outputs and operate as follows FALSE 0 0 Vdc 0 mA TRUE 100 the max 11 Vdc 22 mA D Digital inputs open circuit FALSE closed circuit TRUE UI 1 is selectable as a fast digital pulse meter Table 5 Description of wiring terminals CLLYVB0000AS CLLYVB4022AS and CLLYVB6436AS TERMINAL LABEL CONNE...

Page 10: ...gital inputs see Fig 17 Typical controller wiring for 4 20 mA heating cooling and model ML6161 floating motor control see Fig 18 Typical controller wiring for a pneumatic transducer model RP7517B see Fig 19 24VAC BACnet MS TP BACnet MS TP SHIELD 24VAC COM REHEAT STAGE 3 REHEAT STAGE 2 OR CLOSE REHEAT STAGE 1 OR OPEN DAMPER CLOSE DAMPER OPEN C770A AIR TEMP SENSOR AIR FLOW PICK UP WINDOW CONTACTS CO...

Page 11: ...LVE ACTUATOR PWM VALVE ACTUATOR PWM OUTPUT FROM CONTROLLER PWM H 24 VAC T5 T6 C B W R 24 N 24 H 2 3 3 3 2 1 3 4 ON OFF ML7984B CONFIGURATION DIP SWITCHES LOCATED ADJACENT TO THE INPUT TERMINAL BLOCK PERIPHERAL HEAT VALVE ACTUATOR ML7984B REHEAT VALVE ACTUATOR CLLYUB6438S DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 ...

Page 12: ...her 4 20 mA signal devices Place this resistor as close as possible to the driven device CLCM4T111 WALL MODULE GND SENSOR SET POINT BYPASS LED 5 6 7 4 3 2 1 1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0 2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4 1 2 3 4 5 6 7 8 1 1 1 1 1 1 1 1 1 1 2 1 2 3 4 5 6 7 8 9 0 0 9 CLLYUB6438S 24 VAC 24 VAC COM E GND SHLD SBUS1 SBUS2 NET 1 NET 2 DO 1 DO 2 COM COM COM COM DO 3 DO 4 ...

Page 13: ...g diagram CLLYUB6438S shown with 4 20 mA heating cooling and ML6161 damper actuator NOTE 1 Earth ground wire length should be held to a minimum Use the heaviest gauge wire available up to 14 AWG 2 0 mm 2 with a minimum of 18 AWG 1 0 mm 2 for earth ground wire NOTE 2 Ensure that all transformer power wiring is as shown Reversing terminations will result in equipment malfunction 1 2 3 4 5 6 7 8 9 0 ...

Page 14: ...ee Fig 11 Correct placement of the end of line termination resistors is required for proper BACnet MS TP Bus communications Step 2 Startup See Fig 20 and the following text for startup information CLLYVB6438NS DO 1 DO 2 DO 4 DO 6 DO 8 COM COM COM COM DO 3 DO 5 DO 7 BAC BAC 24VAC 20VDC EGND S BUS S BUS 24VAC COM AO 1 DI 1 DI 2 AO 2 AO 3 COM COM COM DI 3 DI 4 20VDC UI 1 COM UI 2 UI 3 COM UI 4 UI 5 C...

Page 15: ...vere injury death or property damage Do not attempt to modify the physical or electrical characteristics of this device in any way If trouble shooting indicates a malfunction replace the controller WARNING Electrical Shock Hazard Can cause severe injury death or property damage To prevent electrical shock or equipment damage disconnect power supply before beginning controller replacement Terminal ...

Page 16: ... proceed as follows 1 Remove all power from the controller 2 Remove the two air flow pickup connections from the pressure sensor 3 Remove the terminal blocks see section Terminal Block Removal 4 Remove the old controller from its mounting IMPORTANT IN THE CASE OF CONTROLLERS MOUNTED TO A DIN RAIL 1 Push straight up from the bottom to release the top pins 2 Rotate the top of the controller outwards...

Reviews: