Commissioning of a Standalone System Setup
Ensite Pro to CIU 888 Migration Manual
Part No.: 4417593_Rev09
2 - 24
CIU 888
$*6
a) Click
(
Tank viewer
button) in the Ensite Pro tool bar.
The
Tank Viewer
window is displayed (see FIGURE 2-24).
FIGURE 2-24
Ensite Pro -
Tank Viewer
window
b) Check if the red indicator lights in the lower left side of the window
are blinking. If the lights are blinking data is being sent and
received.
c) Select the CIU Plus from the drop-down list.
d) Select the tank from the drop-down list.
The data of the selected tank will be displayed.
e) Check the tank data for the following:
- Do the measured items match the gauge readings?
- Is the TOV correct (based on level and STRAP tables of this
tank?
- Are WVol, GOV and GSV reasonable?
f) Repeat steps d through e for all tanks associated with the
CIU 888.
g) Click
Close
to close the
Tank Viewer
window.
7. Click
(
Close
button) in the Ensite Pro tool bar to close
application.