Commissioning of a Redundant System Setup
Ensite Pro to CIU 888 Migration Manual
Part No.: 4417593_Rev09
3 - 14
CIU 888
$*6
When HostPort 1 of the primary CIU Prime has been linked to
FieldPort 1 of the primary CIU Plus, the HostPort 1 of the secondary
CIU Prime is automatically linked to FieldPort 1 of the secondary
CIU Plus (see FIGURE 3-13).
FIGURE 3-13
Ensite Pro: site overview of a redundant system setup
3.3.4 Generating INI files
When the site configuration has been set up according to one of the
supported topologies of deployment, the next step is to generate the
INI files needed for Entis Pro.
Refer to the
Instruction manual
Ensite Pro Configuration Tool version
3.0
(Part No. 4416593) for detailed information about generating INI
files using Ensite Pro.
3.4 Uploading the site configuration to the primary CIU 888
When the site configuration has been set up and the INI files have been
generated, the next step is to upload the site configuration to the
primary CIU 888 using the Ensite Pro to CIU 888 Migration tool. See
section 2.4 for more information.
3.5 Configuring the additional configuration settings of the CIU 888
When the Ensite Pro site configuration has been uploaded to the
primary CIU 888, the next step is to the configure the additional
configuration settings of the primary CIU 888. See section 2.5 for more
information.