background image

CN05, CN10 SERIES 

NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS FOR 
FLOATING AND TWO-POSITION CONTROL 

                                                                                                                                 PRODUCT DATA 

 

GENERAL 

This non-spring return direct-coupled damper actuator 

provides floating and two-position control for: 
•  

air dampers, 

•  

VAV units, 

•  

air handlers, 

•  

ventilation flaps, 

•  

louvers, and 

•  

reliable control for air damper applications with up to 10  

       sq ft / 44 lb-in. (5 Nm) and 20 sq ft / 88 lb-in. (10 Nm)  
       (seal- less damper blades; air friction-dependent). 

FEATURES  

•  

Declutch for manual adjustment 

•  

Adjustable mechanical end limits 

•  

Removable access cover for direct wiring 

•  

Mountable in any orientation 

•  

Rotation direction and service/OFF switch  

 

SPECIFICATIONS 

Supply voltage

 

CN6105/CN6110 

24 Vac/dc -15%/+20%, 50/60 Hz 

CN4605/CN4610                 230 Vac -15%/+20%, 50/60 Hz 

Nominal voltage

 

CN6105/CN6110 

24 Vac/dc, 50/60 Hz 

CN4605/CN4610                 230Vac, 50/60 Hz 

All values stated hereinafter apply to operation under 
nominal voltage conditions.
 
Power consumption

 

CN6105/CN6110 

5 VA / 2 W 

CN4605                               22 VA / 2 W at 50 Hz 
CN4610                               25 VA / 2 W at 60 Hz 

Ambient limits

 

Ambient operating limits 

-5...+140 °F (20...+60 °C) 

Ambient storage limits 

-22...+176 °F (-30...+80 °C) 

Relative humidity 

5...95%, non-condensing 

Safety

 

Protection standard 

IP54 

Protection class 

II as per EN 60730-1 

Overvoltage category 

II 

Lifetime

 

Full strokes 

60000 

Repositions 1.5 

million 

Mounting

 

Round damper shaft 

3/8 in…5/8 in. 

Square damper shaft 

1/4 in…1/2 in.; 45° steps 

Shaft length 

min. 1-5/8 in. 

End switches (when included)

 

Rating Class 

II 

Triggering points 

5° / 85° 

Torque rating

 

44 lb-in. (5Nm) / 88 lb-in. (10 Nm) 

Runtime for 90°

 

CN6105 

90 sec (dc / 60 Hz ac) 

CN6110  

 

 90 sec (dc / 50 Hz ac) 

CN4605                               65…110 s (60/50 Hz) 
CN4610                               65…140 s (60/50 Hz) 

Rotation stroke

 95° 

+ 3°  

Dimensions

 

see “Dimensions” on page 6 

Weight (without cables)

 1 

lbs. 

Noise rating

                        35 dB(A) max. at 1 m 

                                             40 dB(A) for 230 Vac at 
                                             65 sec runtime 

Certification  

CN6105/CN6110    

 CE & UL 

CN4605/CN4610    

 CE      

CN0B-0544CH33 R0805B

Summary of Contents for CN05 Series

Page 1: ... All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN6105 CN6110 5 VA 2 W CN4605 22 VA 2 W at 50 Hz CN4610 25 VA 2 W at 60 Hz Ambient limits Ambient operating limits 5 140 F 20 60 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Safety Protection standard IP54 Protection class II as per EN 60730 1 Overvoltage category...

Page 2: ...ator into any one of two different modes Service Off or the floating 2 position run mode Dir for CCW closing dampers or Rev for CW closing dampers Fig 2 Function selection switch Power Off Behavior If power is removed the shaft adapter remains in position Service Off If the function selection switch is set to the Service Off position then all rotary movement is cancelled and all control signals ar...

Page 3: ...ection switch setting only one manner of wiring is permitted see Fig 9 Table 2 Behavior of CN4605 CN4610 control signal at switch setting term 1 term 3 Dir Service Off Rev open open stops stops stops open 230 Vac stops stops stops 230 Vac open CW stops CCW 230 Vac 230 Vac CCW stops CW MANUAL ADJUSTMENT IMPORTANT To prevent equipment damage before manual adjustment you must remove power or set the ...

Page 4: ...nti rotation bracket is 3 35 in a max of 4 25 in is allowed see also Fig 11 Depending upon the specifics of your mounting site the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter The anti rotation bracket features a T piece with a 5 mm long shank to accommodate for this movement It is important to ensure that this play is not impeded Universal Sh...

Page 5: ... these terminals must be equipped with spark suppression Table 4 Signals at terminals for CN4605 CN4610 terminal signal 1 L 230 V 2 N 230 V 3 control signal NOTE All cables connected to these terminals must be equipped with spark suppression Table 5 Internal end switches SSW2 terminal type of switch S1 common lead for switches A and B S2 S3 change over switch A S1 S2 opens and S1 S3 closes when sh...

Page 6: ...nal Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C Printed in China on recycled paper containing at least 10 post consumer paper fibers CN05 CN10 SERIES DAMPER ACTUATORS FOR FLOATING 2 POSITON CONTROL CN0B 0544CH33 R0805B ...

Reviews: