PRODUCT IDENTIFICATION SYSTEM 

C

-Electrical Motor 

 

N

-Fail Safe Function (Non-Spring Return) 

 

 

61

-24V Floating C ON/OFF 

 

 

75

-24V Modulating C Fl ON/OFF 

 

 

46

-230V ON/OFF

 

 

 

05

-44 lb-in. (5 Nm) 

 

 

10

-88 lb-in. (10 Nm) 

 

 

A

-Standard Model 

 

 

 

1

-No Feedback 

 

 

 

2

-Voltage Feedback Signal 

 

 

 

0

-No Internal Auxiliary Switches 

 

 

 

2

-Two Internal Auxiliary Switches 

 

 

 

 

 

 

 

XX

-System Controlled Numbers

 

 

 

 

 

 

 

C

 

N

 

75

 

10

 

A

 

2

   

0 XX

 

 

 

 

BASIC FEATURES 

Fig. 1. Setting units and control elements 

 

 

Legend for Fig. 1: 

1) Universal shaft adapter 
2) Mechanical end limits (manually adjustable) 
3) Declutch button 
4) Function selection switch 
5) Removable access cover 
6) Anti-rotation bracket 

Contents of Package 

The delivery package includes the actuator, parts 1 through 6 
(see Fig. 1), plus two cable grommets and a spare cable 
grommet. 

RUN MODES 

The function selection switch (see Fig. 2) can be used to place 
the actuator into any one of two different modes: 

•  

Service/Off; or 

•  

the floating/2-position run mode (“Dir” for CCW-closing 

dampers or “Rev” for CW-closing dampers). 

 
 

 

Fig. 2.  Function selection switch 

Power-Off Behavior 

If power is removed, the shaft adapter remains in position. 

Service/Off 

If the function selection switch is set to the “Service/Off”  
position, then all rotary movement is cancelled, and all  
control signals are ignored, thus allowing the actuator to be 
manually operated safely. 

 

 

 
 
 
 
 
 
 
 
 

Model Description 

CN6105A1011 

5Nm, 24Vac/Vdc, floating control, non-spring 

return, no feedback and without aux. Switch

CN4605A1001 

5Nm, 230Vac, floating control, non-spring 

return, no feedback and without aux. Switch

CN6110A1003

 

10Nm, 24Vac/Vdc, floating control, non-spring 

return, no feedback and without aux. Switch

CN6110A1201

 

10Nm, 24Vac/Vdc, floating control, non-spring 

return, no feedback and with aux. Switch

 

CN4610A1001

 

10Nm, 230Vac, floating control, non-spring 

return, no feedback and without aux. Switch

 

CN05,CN10 SERIES DAMPER ACTUATORS FOR FLOATING/2-POSITON CONTROL 

CN0B-0544CH33 R0805B 

Summary of Contents for CN05 Series

Page 1: ... All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN6105 CN6110 5 VA 2 W CN4605 22 VA 2 W at 50 Hz CN4610 25 VA 2 W at 60 Hz Ambient limits Ambient operating limits 5 140 F 20 60 C Ambient storage limits 22 176 F 30 80 C Relative humidity 5 95 non condensing Safety Protection standard IP54 Protection class II as per EN 60730 1 Overvoltage category...

Page 2: ...ator into any one of two different modes Service Off or the floating 2 position run mode Dir for CCW closing dampers or Rev for CW closing dampers Fig 2 Function selection switch Power Off Behavior If power is removed the shaft adapter remains in position Service Off If the function selection switch is set to the Service Off position then all rotary movement is cancelled and all control signals ar...

Page 3: ...ection switch setting only one manner of wiring is permitted see Fig 9 Table 2 Behavior of CN4605 CN4610 control signal at switch setting term 1 term 3 Dir Service Off Rev open open stops stops stops open 230 Vac stops stops stops 230 Vac open CW stops CCW 230 Vac 230 Vac CCW stops CW MANUAL ADJUSTMENT IMPORTANT To prevent equipment damage before manual adjustment you must remove power or set the ...

Page 4: ...nti rotation bracket is 3 35 in a max of 4 25 in is allowed see also Fig 11 Depending upon the specifics of your mounting site the actuator may shift in position slightly while tightening the screws at the top of the shaft adapter The anti rotation bracket features a T piece with a 5 mm long shank to accommodate for this movement It is important to ensure that this play is not impeded Universal Sh...

Page 5: ... these terminals must be equipped with spark suppression Table 4 Signals at terminals for CN4605 CN4610 terminal signal 1 L 230 V 2 N 230 V 3 control signal NOTE All cables connected to these terminals must be equipped with spark suppression Table 5 Internal end switches SSW2 terminal type of switch S1 common lead for switches A and B S2 S3 change over switch A S1 S2 opens and S1 S3 closes when sh...

Page 6: ...nal Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C Printed in China on recycled paper containing at least 10 post consumer paper fibers CN05 CN10 SERIES DAMPER ACTUATORS FOR FLOATING 2 POSITON CONTROL CN0B 0544CH33 R0805B ...

Reviews: