See the following table for the pin assignments:
RJ 45 Pin Number
Ethernet Signal Name
1
TX+ (Transmitted Data+)
2
TX- (Transmitted Data-)
3
RX+ (Received Data+)
4
N/C
5
N/C
6
RX - ( Received Data-)
7
N/C
8
N/C
Table 4-6: Ethernet Ports
RS485 Ports
The CN100 controller has one RS485 port to some specific
equipment. Each port has five terminals: 485 A+, 485 B-, chassis
ground and termination. See the following picture for the RS485 pin
assignment.
Figure 4-7: Pin Assignment of RS485 Port
The regulations are recommended to follow:
n
All chassis ground terminals of RS485 must be connected to the
earth.
n
Use single shielded two wire twisted cable.
RS485 Terminals: A termination resistor (120-ohm) is used within
CN100 controller to match the characteristic impedance of the cable
32
Chapter 4 - CN100 Platform Installation