27
Power Cabling
A CN100 Controller installation requires a 24VDC to power the
controller and NAM. The CN100 controller is equipped with an on-
board protection system to protect against voltage fluctuations
beyond the rated range of 18 to 30 VDC.
Power supply for Redundant Controller
The CN100 IOTA supports redundant power supply.
For each power supply, connect positive and negative poles of the
24V power source to the power input terminals of the redundant
controller. This powers the controller and any I/O modules connected
in the same row as the controller. This does not provide the loop
power to the field instruments.