background image

 

® U.S. Registered Trademark 

 

EN0B-0341CH33 R0803A 

Copyright © 2008 Honeywell Inc. • All rights reserved 

CN20, CN34 SERIES 

NON-SPRING RETURN DIRECT-COUPLED DAMPER ACTUATORS 

FOR MODULATING AND FLOATING / 2-POSITION CONTROL 

 

PRODUCT DATA 

 

GENERAL 

These direct-coupled damper actuators provide modulating 
control for: 

 air 

dampers, 

 VAV 

units, 

 

air handling units, 

 ventilation 

flaps, 

 louvers, 

and 

 

reliable control for air damper applications with up to 

4.6 m

2

 / 50 sq.ft. (20 Nm / 177 lb-in) or 7.8 m

2

 / 85 sq. ft. 

(34 Nm / 300 lb-in) (seal-less dampers; air friction-

dependent). 

 

FEATURES 

 

Self-centering shaft adapter 

 

Access cover to facilitate connectivity 

 

Service/off for safe & easy servicing 

 

Rotation direction selectable by switch 

 

Declutch for manual adjustment 

 

Mechanical end limits 

 

Field-installable auxiliary switches 

 

Mountable in any orientation (no IP54 if upside down) 

 

Mechanical position indicator 

 

CE and UL certified 

SPECIFICATIONS 

Supply voltage

 

24 Vac/dc  

±

15%, 50/60 Hz; 

 

 

Nominal voltage

 

24 Vac/dc, 50/60 Hz;

 

All values stated hereinafter apply to operation under 
nominal voltage conditions. 
Power consumption 

CN7220A2007 

6 VA / 3 W 

CN7234A2008 

6 VA / 3 W 

Ambient limits 

Ambient operating limits 

-20...+60 

°

C (-5...+140 °F) 

Ambient storage limits 

-40...+80 

°

C (-40...+175 °F) 

Relative humidity 

5...95%, non-condensing 

Safety 

Protection standard 

IP54 as per EN 60529 

Protection class 

II as per EN 60730-1 

Overvoltage category 

II 

Lifetime 

Full strokes 

60000 

Repositions 1.5 

million 

Mounting 

Round damper shaft 

10...27 mm (3/8...1-1/16") 

Square damper shaft 

10...18 mm (3/8...11/16"); 

 45° 

steps 

Shaft length 

min. 22 mm (7/8") 

Control signal

 0(2)...10 

Vdc 

 0(4)...20 

mA 

Input impedance 

>100 k

Ω

 [0...10 V] 

 500 

Ω

 [0...20 mA] 

Feedback signal 

Limits 

±

 1 mA at 0...10 V 

End switches (when included) 

Rating 

5 A (resistive) / 3 A (inductive) 

Triggering points 

5

°

 / 85

°

 

Torque rating

 

CN7220A2007 

20 Nm (177 lb-in) 

CN7234A2008 

34 Nm (300 lb-in) 

Runtime 

 95 sec (60 Hz) / 110 sec (50 Hz 

or DC supply) 

Rotation stroke

 95

°

 

±

 3

°

 

Dimensions

 

see "Dimensions" on page 8 

Weight (without cables)

  1.35 kg (3 lbs.) 

Noise rating

 

40 dB(A) max. at 1 m 

Certification                         

CE & UL

 

     

 

 

 

Summary of Contents for CN34 Series

Page 1: ...Supply voltage 24 Vac dc 15 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220A2007 6 VA 3 W CN7234A2008 6 VA 3 W Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 40 80 C 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 Prot...

Page 2: ...liary Switches 2 Two Internal Auxiliary Switches XX System Controlled Numbers C N 72 20 A 2 0 XX Fig 1 Product Identification System OPERATION FUNCTIONS Legend for Fig 2 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 5 Declutch button 6 Anti rotation bracket 7 Function Selection Switch 8 Access cover Contents of Package The delivery packa...

Page 3: ... function selection switch setting Table 2 describes the actuator behavior stops rotates CCW or rotates CW for the 2 position mode in relation to the control signals applied to terminals 3 and 4 and to the function selection switch setting Table 3 describes the actuator behavior stops rotates CCW rotates CW runs in proportional position or runs to 0 of max stroke for the modulating mode in relatio...

Page 4: ... see Fig A1 the control signal s value rises up into the upper dead band i e to more than the max control signal minus 0 14V or drops down into the lower dead band i e to less than the min control signal plus 0 14V and if the shaft adapter can remain at the respective upper or lower mechanical end limit at least 3 seconds the actuator will recognize the new position automatically and auto adaption...

Page 5: ...d Internal End Switches NOTE Applicable to models with internal switches only The internal end switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position 5 10 15 92 5 0 90 2 5 85 80 75 85 80 75 2 5 90 0 92 5 5 10 15 5 10 15 0 90 85 80 75 CCW internal end switch CW internal end switch actuator scale clockwise end switch scal...

Page 6: ...le Fig 12 Access cover models with internal switches Depending upon the model the access cover may have one or two terminal strips including a layout with a description for each of the terminals Fig 13 Actuator with access cover removed models with internal switches OPTIONAL ACCESSORIES The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 S1 S2 S3 A B S4 S...

Page 7: ...d in the preceding wiring diagrams Function selection switch Terminal Modulating Floating 2 position 1 24 V power unused unused 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused unused NOTE All cables connected to these terminals must be equipped with spark suppression Connecting cabl...

Page 8: ...stion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C EN0B 0341CH33 R0803A DIMENSIONS ...

Reviews: