background image

CN20, CN34 SERIES DAMPER ACTUATOR FOR MODULATING AND FLOATING CONTROL 

EN0B-0341CH33 R0803A 

 

0 0.24

0

50

100

5.0

10.0

9.76

upper dead band (9.76 to 10.0 V)

control signal (V)

final position of sha

ft adapter 

(% of max. stroke)

range of proportional

actuator movement

(0.24 to 9.76 V)

lower dead band (0 to 0.24 V)

 

Fig.4. Final actuator position in dependence upon control 

signal (example selection setting of 0...10 V) 

0

0

50

100

5

10

feedback signal (V)

cur

rent position of 

sh

af

adapter (%

 o

f max. 

stroke)

 

Fig.5. Feedback signal in dependence upon current 

position of actuator (example selection switch setting of 

0...10 V) 

Adaption 

Adaption is a function in which the actuator re-maps its feed-

back signal and control signal in accordance with repositioned 

mechanical end limits (see Fig.6) and thus recognizes their 

new positions. 

fin

al po

si

tion o

f

act

uator (% of max

.)

final p

osi

tion

 of ac

tuator (degrees

)

0

95

0

10.0

control signal (volts)

new position of UPPER

mechanical end limit

new position of LOWER

mechanical end limit

bef

or

ad

ap

tio

n

afte

r a

dap

tion

0

(before)

100

(before)

0

(after)

100

(after)

 

Fig.6. Adaption (selection switch set to "0...10 V") 

Adaption will be carried out only

 

when: 

  Modulating models only, such as CN7220A2007, 

CN7234A2008, etc, 

  actuator is wired in modulating mode (see Fig. A1) 

  the control signal’s value rises up into the upper dead 

band (i.e to more than the max. control signal minus 
0.14V) or drops down into the lower dead band (i.e to less 
than the min. control signal plus 0.14V), and if the shaft 
adapter can remain at the respective (upper or lower) 
mechanical end limit at least 3 seconds, the actuator will 
recognize the new position automatically, and auto-
adaption is happened (see Fig. 4). 

 

Sleep Mode 

 

When actuator reaches end stop or any obstacles blocking its 
running, it will fall into sleep mode automatically. Actuator will 
periodically start up and try to resume running, which will save 
energy significantly through whole service life. 
 

Overriding 

An override is a condition in which a 24 V signal is applied to 

terminal 4 of an actuator in the modulating mode, thus 

causing the actuator to ignore the control signal at terminal 3, 

whereupon it will instead move to a position of 0% of its 

maximum stroke. It would be the most left side [0/2~10V 

mode] or most right side [10~0/2 V mode] (see Table 3). 

 

Feedback 

If correspondingly wired (see A1), the actuator provides, via 

terminal 5, a feedback signal(0/2~10V) proportional to the 

actual position of the actuator (see Fig. 5). 

 

Dip Switches 

The actuator is equipped with two dip switches (only switch 1 

selectable) accessible after removing the access cover (see 

Fig. 7). 

 

 

1: (U) VOLTAGE CONTROL

O

 

N

 

1

 

2

 

O

N

1

2

2: RESERVED

1: (mA) CURRENT 
2: RESERVED

O

N

1

2

 

Fig.7. Dip switches (view with PCB at bottom) 

Summary of Contents for CN34 Series

Page 1: ...Supply voltage 24 Vac dc 15 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220A2007 6 VA 3 W CN7234A2008 6 VA 3 W Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 40 80 C 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 Prot...

Page 2: ...liary Switches 2 Two Internal Auxiliary Switches XX System Controlled Numbers C N 72 20 A 2 0 XX Fig 1 Product Identification System OPERATION FUNCTIONS Legend for Fig 2 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 5 Declutch button 6 Anti rotation bracket 7 Function Selection Switch 8 Access cover Contents of Package The delivery packa...

Page 3: ... function selection switch setting Table 2 describes the actuator behavior stops rotates CCW or rotates CW for the 2 position mode in relation to the control signals applied to terminals 3 and 4 and to the function selection switch setting Table 3 describes the actuator behavior stops rotates CCW rotates CW runs in proportional position or runs to 0 of max stroke for the modulating mode in relatio...

Page 4: ... see Fig A1 the control signal s value rises up into the upper dead band i e to more than the max control signal minus 0 14V or drops down into the lower dead band i e to less than the min control signal plus 0 14V and if the shaft adapter can remain at the respective upper or lower mechanical end limit at least 3 seconds the actuator will recognize the new position automatically and auto adaption...

Page 5: ...d Internal End Switches NOTE Applicable to models with internal switches only The internal end switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position 5 10 15 92 5 0 90 2 5 85 80 75 85 80 75 2 5 90 0 92 5 5 10 15 5 10 15 0 90 85 80 75 CCW internal end switch CW internal end switch actuator scale clockwise end switch scal...

Page 6: ...le Fig 12 Access cover models with internal switches Depending upon the model the access cover may have one or two terminal strips including a layout with a description for each of the terminals Fig 13 Actuator with access cover removed models with internal switches OPTIONAL ACCESSORIES The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 S1 S2 S3 A B S4 S...

Page 7: ...d in the preceding wiring diagrams Function selection switch Terminal Modulating Floating 2 position 1 24 V power unused unused 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused unused NOTE All cables connected to these terminals must be equipped with spark suppression Connecting cabl...

Page 8: ...stion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C EN0B 0341CH33 R0803A DIMENSIONS ...

Reviews: