background image

CN20, CN34 SERIES DAMPER ACTUATOR FOR MODULATING AND FLOATING CONTROL 

 

 5 

EN0B-0341CH33 

R0803A 

Voltage/Current Control Signal Selection Dip Switch 

In its default shipping position, the voltage/current control 

signal dip switch (see Fig. 7) is set to 

OFF

 (= voltage control). 

as shown in Fig. 7. Setting it to ON results in current control 

4…20mA. 

 

Position Indication 

The hub adapter indicates the rotation angle position by 

means of the rotational angle scales (0...90° / 90...0°). 

 

 

Fig.8. Position indication 

Manual Adjustment 

 

IMPORTANT 

In order to prevent equipment damage, you must 

remove power set the rotation direction switch to the 

"Service/Off before manual adjustment. 

 

After removing power or setting the rotation direction switch to 

the "Service/Off" position, the gear train can be disengaged 

using the declutch button, permitting the actuator shaft to be 

manually rotated to any position. The feedback signal will 

then follow the new position. 

 

Limitation of Rotation Stroke 

Two mechanical end limits (adjustable in 5° increments) are 

provided to limit the angle of rotation as desired (see Fig.9). 

 

 

Fig.9. Mechanical end limits 

 

The mechanical end limits must be securely fastened in place. 

It is important that they properly mesh with the rotational 

angle scales when the screws are tightened. 

 

Internal End Switches 

NOTE:

 Applicable to models with internal switches only. 

 

The internal end switches are set to change from "common" 

to "normally open" at angles of 5° and 85°, respectively, from 

the totally counterclockwise position. 

 

5

10

15

92.5

0

90

-2.5

85

80

75

85

80

75

-2.5

90

0

92.5

5

10

15

5

10

15

0

90

85

80

75

CCW internal

end switch

CW internal

end switch

actuator scale: clockwise

end switch scale

actuator scale: counterclockwise

 

Fig. 10. Internal end switches 

 

 

INSTALLATION 

These actuators are designed for single-point mounting. 

 

IMPORTANT 

In order to prevent equipment damage, you must 

remove power or set the rotation direction switch to the 

"Service/Off" position before manual operation. 

 

Mounting Instructions 

All information and steps are included in the installation 

instructions supplied with the actuator. 

 

Mounting Position 

The actuators can be mounted in any desired orientation (no 

IP54 if mounted upside down; see Fig.11). Choose an 

orientation permitting easy access to the actuator's cables 

and controls. 

 

IP54

IP54

IP54

IP54

 

Fig. 11. Mounting for IP54 

 

Mounting Bracket and Screws 

If the actuator is to be mounted directly on a damper shaft, 

use the mounting bracket and screws included in the delivery 

package. 

 

Self-Centering Shaft Adapter 

The self-centering shaft adapter can be used for shafts 

having various diameters (10...27 mm [3/8...1-1/16"]) and 

shapes (square or round). 

 

In the case of short shafts, the shaft adapter may be reversed 

and mounted on the duct side. 

 

 

 

Summary of Contents for CN34 Series

Page 1: ...Supply voltage 24 Vac dc 15 50 60 Hz Nominal voltage 24 Vac dc 50 60 Hz All values stated hereinafter apply to operation under nominal voltage conditions Power consumption CN7220A2007 6 VA 3 W CN7234A2008 6 VA 3 W Ambient limits Ambient operating limits 20 60 C 5 140 F Ambient storage limits 40 80 C 40 175 F Relative humidity 5 95 non condensing Safety Protection standard IP54 as per EN 60529 Prot...

Page 2: ...liary Switches 2 Two Internal Auxiliary Switches XX System Controlled Numbers C N 72 20 A 2 0 XX Fig 1 Product Identification System OPERATION FUNCTIONS Legend for Fig 2 1 Self centering shaft adapter 2 Retainer clip 3 Rotational angle scales 0 90 90 0 4 Mechanical end limits 5 Declutch button 6 Anti rotation bracket 7 Function Selection Switch 8 Access cover Contents of Package The delivery packa...

Page 3: ... function selection switch setting Table 2 describes the actuator behavior stops rotates CCW or rotates CW for the 2 position mode in relation to the control signals applied to terminals 3 and 4 and to the function selection switch setting Table 3 describes the actuator behavior stops rotates CCW rotates CW runs in proportional position or runs to 0 of max stroke for the modulating mode in relatio...

Page 4: ... see Fig A1 the control signal s value rises up into the upper dead band i e to more than the max control signal minus 0 14V or drops down into the lower dead band i e to less than the min control signal plus 0 14V and if the shaft adapter can remain at the respective upper or lower mechanical end limit at least 3 seconds the actuator will recognize the new position automatically and auto adaption...

Page 5: ...d Internal End Switches NOTE Applicable to models with internal switches only The internal end switches are set to change from common to normally open at angles of 5 and 85 respectively from the totally counterclockwise position 5 10 15 92 5 0 90 2 5 85 80 75 85 80 75 2 5 90 0 92 5 5 10 15 5 10 15 0 90 85 80 75 CCW internal end switch CW internal end switch actuator scale clockwise end switch scal...

Page 6: ...le Fig 12 Access cover models with internal switches Depending upon the model the access cover may have one or two terminal strips including a layout with a description for each of the terminals Fig 13 Actuator with access cover removed models with internal switches OPTIONAL ACCESSORIES The following optional accessories can be ordered separately Auxiliary Switch Kit Order no SW2 S1 S2 S3 A B S4 S...

Page 7: ...d in the preceding wiring diagrams Function selection switch Terminal Modulating Floating 2 position 1 24 V power unused unused 2 common common common 3 0 2 10 V control 24 V control signal 24 V control signal 4 24 V override 24 V control signal 24 V control signal 5 0 2 10 V feedback unused unused NOTE All cables connected to these terminals must be equipped with spark suppression Connecting cabl...

Page 8: ...stion Controls Division of Honeywell Technologies Sàrl Ecublens Route du Bois 37 Switzerland by its Authorized Representative Automation and Control Solutions Honeywell International Inc Honeywell Tianjin Limited 1985 Douglas Drive North 66 BaiHe Road TEDA Golden Valley MN 55422 Tianjin 300457 P R C EN0B 0341CH33 R0803A DIMENSIONS ...

Reviews: