To set a controller as an OPC UA server
1.
From the Home Page, click
Configure Ethernet Ports
and select
ETH1
or
ETH2
.
2.
Under
Network Setting
, select
Use the following IP address
and enter
the details in the
IP Address
,
Subnet Mask
and
Gateway
fields.
3.
Under
Protocol Binding
, select
OPC UA Server
for the Ethernet port.
4.
Click
Save
to save the configuration, and click
Back
to return to the
Home Page.
5.
Click
Make
to compile the configuration to the controller.
Publishing to Experion
This function enables the user to publish the related configuration for
Experion to configure point and system status for ControlEdge 900
controller in Experion.
For how to publish the configuration to Experion, See "Publishing to
Experion" on page 110 for more information.
Configuring DNP3 Slave
DNP3 is used for communication between the controller and a DNP3
master such as a SCADA system like Experion. The controller acts as a
DNP3 slave.
Binding protocol to Ethernet ports
1.
From the Home Page of ControlEdge Builder, click the arrow
beside
Configure Ethernet Ports
, and select
ETH1
or
ETH2
.
2.
Under
Network Setting
, select
Use the following IP address
and enter
the IP address of the Ethernet port.
3.
Under
Protocol Binding
, select
DNP3
.
4.
Click
Save
to complete the configuration.
Configuring DNP3 slave protocol
This section only introduces simple procedures to configure DNP3
slave. For more information, see "Configuring DNP3 slave" in the
ControlEgde Builder User's Guide
.
100
Chapter 6 - Communication