105
For more information about the function block, right-click it and
select
Help on FB/FU
to display the embedded help.
5.
Double-click the pin-outs of the function block to assign variables.
The
Variable Properties
dialog appears.
6.
Select the
Name
,
Data Type
and
Usage
from the list.
l
For the parameter
GEN_DEV_STATUS
, you should select
HAR_
GEN_DEV_STATUS
from the
Data Type
list.
l
For the parameter
DEV_INFO
, you should select
HART_CMD48_
DEV_INFO
from the
Data Type
list.
7.
Assign Initial value and I/O address details.
l
For the parameter
IOM
, enter the target module number in the
Initial Value
field. For example, if the target module name is
"Expansion I/O 01", enter "01".
l
For the parameter
CHN
, enter the target channel number in the
Initial Value
field.
8.
Click
OK
. The workplace will appear as shown below.
9.
Click
Make
from the toolbar to compile the programs.
10.
Click
Download
from the toolbar to download the compiled
programs of HART to the controller.
Chapter 6 - Communication