o
Up to 80000 DNP3 events can be saved to Flash.
o
Up to 200000 DNP3 events can be saved to SD card.
8.
Click
Save
.
Communicating with Experion via DNP3
Experion server to ControlEdge 2020 Controller communication is
with the DNP3 protocol, so DNP3 must be enabled on the Ethernet
port(s) connected to the same network as the Experion Server.
For more details about the Experion integration with ControlEdge
2020 controller, see the
Experion PKS DNP3 Interface Reference
.
Configuring a DNP3 slave
A new project is created and a controller is added to the project in
ControlEdge Builder.
To set a controller as a DNP3 slave
1.
From the Home Page, click
Configure Ethernet Ports
and select
ETH1
or
ETH2
.
2.
Under
Network Setting
, select
Use the following IP address
and enter
the details in the
IP Address
,
Subnet Mask
and
Gateway
fields.
3.
Under
Protocol Binding
, select
DNP3
to for the Ethernet port.
4.
Click
Save
to save the configuration, and click
Back
to return to the
Home Page.
5.
Click
Make
to compile the configuration to the controller.
Publishing to Experion
This function enables the user to publish the related configuration for
Experion to configure point and system status for ControlEdge 2020
controller in Experion.
1.
From the Home Page of ControlEdge Builder, click
Publish to
Experion
under
I/O and Communications
. The project configuration
will be published to Experion directly.
2.
If the publish fails for ControlEdge 2020 controller, you can export
the configuration manually.
a.
A warning message appears that the publish has failed. Click
OK
.
102
Chapter 6 - Communication
Summary of Contents for ControlEdge 2020 SC-TEPL01
Page 28: ...Figure 3 8 Single star topology 28 Chapter 3 Hardware ...
Page 40: ...40 Chapter 3 Hardware ...
Page 66: ...66 Chapter 4 Software ...
Page 114: ...114 Chapter 6 Communication ...
Page 126: ...126 Notices ...