45
Port
Default setting
The secondary controller static IP address: 192.168.1.51
To configure IP address
1.
From the Home Page, click the arrow beside
Configure Ethernet
Ports
, and select
ETH1
or
ETH2
.
2.
Under
Network Setting
, configure the IP address of the Ethernet
port for the controller.
3.
Under the
Protocol Binding
, select the protocol which you want to
bind to the port.
4.
Click
Save
to complete the Ethernet port configuration.
5.
Click
Back
to return to the Home Page.
TIP: If new IP settings are compiled and downloaded, the
controller will be disconnected from the configuring device.
Configuring controller start up
This function enables you to configure the controller status after the
power cycle.
For ControlEdge 900 controller, this feature is only applicable when
the mode switch is in REMOTE position.
Under
Controller and Programming
, select
Configure Controller Start Up
,
the
Configure Controller Start Up
page appears. There are four options
for controller start up:
n
Last operating mode, or Running after an abnormal stop
This option is the default setting for ControlEdge 2020 controller.
The controller will start in the operating mode that it was last in
prior to a power off, unless there was an abnormal stop caused by
a system error such as a watchdog timeout issue. It will then start
in
Running
mode.
l
If the controller was in
Running
mode before power off, the
controller will warm start in
Running
. If the warm start fails, the
controller will go to
Stopped
mode.
l
If the controller was stopped manually before power off, the
controller will start in
Stopped
mode.
l
If the controller was stopped abnormally before power off, the
Chapter 4 - Software