background image

WEB-300E, WEB-600E/U, CP-300E, CP-600E/U SERIES CONTROLLERS

9

31-00010—01

Fig. 5. NPB-PWR-UN-H/U module wiring connections.

Wiring NPB-PWR-UN-H/U input 

power and earth ground.

1.

Remove power from the AC circuit being wired to 

the NPB-PWR-UN-H/U. See the previous Warning.

2.

Remove the NPB-PWR-UN-H/U cover. To do this, 

press in the four tabs on both ends of the unit, and 

lift the cover off. If the controller or a IO-16-H/U 

accessory module is plugged into the unit, you may 

need to slide it away to get to the cover tabs.

3.

Connect the supplied earth grounding wire to a 

nearby grounding point. See Fig. 5.

4.

Make AC circuit connections line (mains) and neu-

tral to the terminals labeled “INPUT PWR.”

5.

Replace the cover on the NPB-PWR-UN-H/U mod-

ule. Make sure all modules in the mounted assem-

bly are firmly connected together and secured.

CAUTION

Do not energize the AC circuit wired to the 

NPB-PWR-UN-H/U until all other controller 

mounting and wiring is completed. See “Power 

Up and Initial Checkout” on page 12.

NPB-WPM-US/U 

(Wall Mount AC Adapter)

The NPB-WPM-US/U is a self-contained, isolated, Class 

2, switching power supply designed to plug into a 

standard building power receptacle of appropriate voltage. 

To supply power to the controller, you simply plug the 

barrel connector plug from the NPB-WPM-US/U into the 

barrel power connector on the controller’s base board 

(see Fig. 3 on page 5).

NOTE: The adapter’s 15W output rating is derated 

50% at the 60°C (140°F) maximum ambient 

temperature (for a controller 

without

 a NiMH 

battery), such that 

no I/O modules are sup-

ported at 60°C

. See “Environmental Require-

ments” on page 3.

CAUTION

Do not plug the barrel connect plug from the 

NPB-WPM-US/U into the controller until all 

other mounting and wiring is completed.

See “Initial power up and checkout.” on page 12.

Communications Wiring

Communications ports are on the controller’s bottom side, 

which include:

• Ethernet

• Serial

NOTE: Prior to connecting cables, provide strain 

relief for them to prevent damage to the 

controller.

SUPPLIED EARTH

GROUNDING WIRE 

EARTH

GROUND 

NOTE:  THE 6-PIN CONNECTOR ON THE NPB-PWR-UN-H/U IS NOT USED WITH A 

                WEB-300E OR WEB-600E/U SERIES CONTROLLER.  THE 6-PIN CONNECTOR IS 

             DESIGNED FOR USE WITH OTHER CONTROLLERS OR MODULES, AND MUST 

             BE LEFT UNUSED.    

REMOVE COVER

6-PIN

CONNECTOR

NOT USED  

120 OR 240VAC

50–60 HZ

SINGLE PHASE  

LINE

NEUTRAL

L N

M34992

Summary of Contents for CP-300E Series

Page 1: ... system installation Instructions in this document apply to the products listed in Table 1 Not covered in this document is the WEBs AX software installation and configuration required for a fully functioning unit In addition the mounting and wiring of JACE expansion options are covered in separate documents See Related Documentation on this page and Expansion Options on page 5 Related Documentatio...

Page 2: ...des two Ethernet ports one RS 232 port and one RS 485 port Web User Interface and Niagara Connectivity included oBIX Client Server driver included CP 300E Comfort Point 300E includes two Ethernet ports one RS 232 port and one RS 485 port Web User Interface and Niagara Connectivity included oBIX Client Server driver included WEB 600E U The WEB 600E U is designed for Battery less operation and DIN r...

Page 3: ...any static electricity you may have accumulated Discharge static electricity by touching a known securely grounded object Do not handle printed circuit boards PCBs without proper protection against static discharge Use a wrist strap when handling PCBs The wrist strap clamp must be secured to earth ground Battery Precautions CAUTION The optional NiMH battery used in this device may present a risk o...

Page 4: ...er and accessory mounting details To mount on DIN rail 1 Securely install the DIN rail with at least two screws near the two rail ends 2 Position the controller on the rail tilting to hook DIN rail tabs over one edge of the DIN rail Fig 1 3 Use a screwdriver to pry down the plastic locking clip and push down and in on the unit forcing the locking clip to snap over the other DIN rail edge 4 Mount a...

Page 5: ...PTIONS The controller provides for field installable expansion using these types of options Option cards Install on connectors on the controller s base board See About Option Cards on page 5 Accessory modules To chain on the controller s 20 pin connector See About Accessory Modules on page 6 About Option Cards The controller has two 2 available option slots for option cards designed for use with c...

Page 6: ... aligned with the standoffs c Place the four screws through the bracket end plates and into the standoffs on the controller base board With a screwdriver hand tighten the screws For more details see NiMH Battery Installation and Maintenance on page 14 Otherwise place the two screws through the option card end plate and into the standoffs on the base board With a screwdriver hand tighten the screws...

Page 7: ...ller power NOTE See Environmental Requirements on page 3 for mains supply requirements The controller does not include an on off switch To apply power you either if NPB PWR H U plug in its 2 position power connector if NPB PWR UN H U energize the AC circuit 120 240 Vac wired to that module if NPB WPM US U plug in the power connector to the controller CAUTION Do not connect both the NPB WPM US U an...

Page 8: ...module is a 2 position power connector and an earth ground spade lug as shown in Fig 4 Connect the supplied earth ground wire to a nearby earth ground point Unplug the power connector plug from the module and make connections to it as shown CAUTION Do not plug 24V power into the NPB PWR H U reinsert connector plug until all other mounting and wiring is completed See Initial power up and checkout o...

Page 9: ... isolated Class 2 switching power supply designed to plug into a standard building power receptacle of appropriate voltage To supply power to the controller you simply plug the barrel connector plug from the NPB WPM US U into the barrel power connector on the controller s base board see Fig 3 on page 5 NOTE The adapter s 15W output rating is derated 50 at the 60 C 140 F maximum ambient temperature...

Page 10: ...he serial connectors see Fig 3 on page 5 These LEDs are labeled on the board COM1 COM2 and are not visible with the cover on RS 232 An RS 232 serial port using a male DB 9 connector always operates as COM1 You can use standard DB 9 serial cables with this port The controller is a serial DTE device such that another DTE device PC for example requires a null modem cable If connecting to a DCE device...

Page 11: ...ross the and terminals Termi nation resistors are typically 100 or 120 ohm value resistors Whenever termination resistors are used RS 485 biasing is typically required Adding RS 485 Bias To add biasing you must power off the controller and remove a few assemblies such as metal shield and NPM3E or NPM6E processor module to access the base board jumper pins located behind the RS 485 port Then you mu...

Page 12: ...own over the other side Make sure that its corner holes align with the metal standoffs below 4 Refasten the four Phillips head screws that secure the shield to the standoffs 5 Replace the plastic cover onto the unit POWER UP AND INITIAL CHECKOUT Ensure power wiring to the controller is ready see Power Wiring on page 7 See Fig 3 page 4 for the location of status LEDs and connectors See Fig 4 on pag...

Page 13: ...atform service An example is a station with many rapidly changing values all captured as histories on COV In this case you may wish to disable SRAM support and install and use only the optional NiMH battery pack For an overview see About Backup Configurations on page 13 Complete WEBs AX details on the operation of the controller s integral SRAM are in the JACE Data Recovery Service SRAM support En...

Page 14: ...s for the two serial ports are located on the controller s bottom board on the opposite side of the RS 232 and RS 485 ports Labels COM1 and COM2 correspond to the software configuration of the COM ports LEDs show the transmit and receive activity for the serial ports and optional modem NOTE You must remove the cover to see these LEDs See Removing and Replacing the Cover on page 4 The yellow transm...

Page 15: ...hand tighten these screws 10 Replace the cover 11 Restore power to the controller and verify normal operation Battery maintenance Battery life expectancy is a function of its discharge cycles the number of discharges and their depth and the ambient temperature of the battery during normal operation In most applications the NiMH battery should see relatively few discharges Therefore ambient tempera...

Page 16: ... section on page 6 To replace a controller with a new replacement unit proceed as follows REPLACING A WEB CP 300E OR WEB CP 600E U CONTROLLER 1 If possible use the appropriate WEBs AX software tool to back up the controller s configuration to your PC 2 Remove power to the controller The unit should power down automatically Wait for all LEDs to remain off NOTE If IO accessory modules are installed ...

Page 17: ...ning a Defective Unit For proper credit on an in warranty unit ship the defective unit per the vendor s return material procedures NOTE If the defective unit is under warranty please follow return instructions provided in this section If the unit is out of warranty please discard any replaced part Do not return an out of warranty controller Prior to returning the unit contact your vendor to obtain...

Page 18: ...MENDED OVER TAB MOUNTING SEE FIGURE 1 WEB 300E OR WEB 600E U NPB PWR H U NPB PWR UN H U OR IO 16 H U DISTANCE BETWEEN CENTER OF TABS FROM ONE UNIT TO ANOTHER UNIT NOTE IF MOUNTING ACCESSORY MODULES FUTURE REMOVAL REPLACEMENT OF THE CONTROLLER IS SIMPLIFIED IF YOU DO NOT INSTALL SCREWS IN THE ACCESSORY MODULE SIDE TABS OF THE CONTROLLER SEE ABOVE ACCESSORY MODULE SIDE TABS M35000 6 23 32 171 2 1 2 ...

Page 19: ...WEB 300E WEB 600E U CP 300E CP 600E U SERIES CONTROLLERS 19 31 00010 01 ...

Page 20: ...national Inc 31 00010 01 M S 09 13 Printed in United States By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from and against any liability cost or damages including attorneys fees arising out of or resulting from any mo...

Reviews: