WEB-300E, WEB-600E/U, CP-300E, CP-600E/U SERIES CONTROLLERS
9
31-00010—01
Fig. 5. NPB-PWR-UN-H/U module wiring connections.
Wiring NPB-PWR-UN-H/U input
power and earth ground.
1.
Remove power from the AC circuit being wired to
the NPB-PWR-UN-H/U. See the previous Warning.
2.
Remove the NPB-PWR-UN-H/U cover. To do this,
press in the four tabs on both ends of the unit, and
lift the cover off. If the controller or a IO-16-H/U
accessory module is plugged into the unit, you may
need to slide it away to get to the cover tabs.
3.
Connect the supplied earth grounding wire to a
nearby grounding point. See Fig. 5.
4.
Make AC circuit connections line (mains) and neu-
tral to the terminals labeled “INPUT PWR.”
5.
Replace the cover on the NPB-PWR-UN-H/U mod-
ule. Make sure all modules in the mounted assem-
bly are firmly connected together and secured.
CAUTION
Do not energize the AC circuit wired to the
NPB-PWR-UN-H/U until all other controller
mounting and wiring is completed. See “Power
Up and Initial Checkout” on page 12.
NPB-WPM-US/U
(Wall Mount AC Adapter)
The NPB-WPM-US/U is a self-contained, isolated, Class
2, switching power supply designed to plug into a
standard building power receptacle of appropriate voltage.
To supply power to the controller, you simply plug the
barrel connector plug from the NPB-WPM-US/U into the
barrel power connector on the controller’s base board
NOTE: The adapter’s 15W output rating is derated
50% at the 60°C (140°F) maximum ambient
temperature (for a controller
without
a NiMH
battery), such that
no I/O modules are sup-
ported at 60°C
. See “Environmental Require-
CAUTION
Do not plug the barrel connect plug from the
NPB-WPM-US/U into the controller until all
other mounting and wiring is completed.
See “Initial power up and checkout.” on page 12.
Communications Wiring
Communications ports are on the controller’s bottom side,
which include:
• Ethernet
• Serial
NOTE: Prior to connecting cables, provide strain
relief for them to prevent damage to the
controller.
SUPPLIED EARTH
GROUNDING WIRE
EARTH
GROUND
NOTE: THE 6-PIN CONNECTOR ON THE NPB-PWR-UN-H/U IS NOT USED WITH A
WEB-300E OR WEB-600E/U SERIES CONTROLLER. THE 6-PIN CONNECTOR IS
DESIGNED FOR USE WITH OTHER CONTROLLERS OR MODULES, AND MUST
BE LEFT UNUSED.
REMOVE COVER
6-PIN
CONNECTOR
NOT USED
120 OR 240VAC
50–60 HZ
SINGLE PHASE
LINE
NEUTRAL
L N
M34992