The light source of this luminaire is not replaceable when the light source reaches its end of
life the whole luminaire shall be replaced.
ATTENTION!!!
4
5
(*)
Maintained operation: The luminaire lights its illumination source, when it is powered by the
mains power supply or not
.
Non Maintained operation: The luminaire lights its illumination source,
only in mains power supply’s
failure.
Cube M ST LED
SELFTESTING MAINTAINED
EMERGENCY LUMINAIRE
Cube
Technical Characteristics
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-MH)
MINIMUM POWER FACTOR
WIRE CROSS SECTION
MAX OPEN CIRCUIT VOLTAGE
Irated
Prated
U-OUT
MAXIMUM SUPPLY CURRENT
INSULATION BETWEEN SUPPLY & CONTROL TERMINALS
INSULATION BETWEEN SUPPLY & BATTERY CIRCUIT
BATTERY PROTECTION
CHARGE TIME
MINIMUM DURATION
LIGHT SOURCE
DEGREES OF COVER PROTECTION
LIGHT SOURCE LUMINOUS FLUX (MAINS / EMERGENCY)
INDICATIONS/CONTROLS
MAX CHARGE VOLTAGE
TRICKLE CHARGE VOLTAGE/CURRENT
MIN MAX. CHARGE CURRENT
MIN MAX. DISCHARGE CURRENT
MIN MAX. DISCHARGE VOLTAGE
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
CONTROL GEAR MAX.TEMPERATURE: tc
RELATIVE HUMIDITY
CONSTRUCTION MATERIAL
EXTERNAL DIMENSION (L x W x H)
WEIGHT
GUARANTEE
4. Remove the old battery and place a new one of the same type and characteristics.
3. Replace the removed parts.
1. Remove the top cover (Step 1 of hanging or ceiling installation).
2. Unscrew the 2 screws that hold the battery to its base.
It can be done only by a competent person and after the mains interruption
.
Battery Replacement
Module Connection & Dip Switch
1:
Maintained operation
(*)
A:
Including test device
B:
Including remote test mode
NOTE:
LED= Light Emitting Diode
X:
Self contained
E:
With non-replacable lamp(s) and/or battery
LABELING EXPLANATION:
60:
1 hour duration
C:
Including inhibiting mode
480
: 8 hours duration
180:
3 hours duration
X 1
6 0
A E
IP40
Maintained
Μ
370/270/110lm
Light output
1h/
3
h/8h
Duration
50
m
NM
Non-Maintained
Controlgear classification in accordance with IEC 62034: with automatic test function.
220-240V AC
/ 50-60Hz
6.4W / 6.6VA
2
2
0.5mm - 2.5mm
33V
1h: 2.2W
1h: 200 mA
3h: 1.5W
3h: 141mA
8h: 57mA
8h: 0.6W
33V
29.2 mA
4.8V/2Ah
0.92
Basic insulation
Basic insulation
3 hours
370/270lm
310-490mA
190-210mA
5.8V/70mA
6V
16h
4-6V
8 hours
360/110lm
170-191mA
1
hour
370/370lm
438-700mA
16 power
LEDs
LED Charge, Lamp Fault LED, Battery Fault LED/Test BUTTON
IP40
Deep discharge and overcharge protection / the control gear will recharge the battery normally after the test of 22.3
o
5
to 40 C
o
53 C at PSU1
Aluminium, ABS/PC
,
PC, Acrylic Plate
2326gr.
310 x 310 x 330 mm
Up to 95%
4 years
EN 60598-1, EN 60598-2-22, EN 55015, EN 61547,
EN 61000-3-2, EN 61000-3-3
1
3
4
2
Module connection
ON
1 2 3 4
Maintained operation
(default position)
ON
1 2 3 4
Non-maintained operation
ON
1 2 3 4
ON
1 2 3 4
ON
1 2 3 4
1h
(default position)
3h
8h
Dip Switch (DS1) Settings
Autonomy duration selection
Technical label installation
Changing the operating mode
The user can select one of the 3 available minimum autonomy durations: 1 hour, 3 hours and 8 hours. The selection
must be done while the luminaire is disconnected from AC and battery supplies. The selection is achieved through
Switches 2 & 3 of DS1. Switch 1 is not used.
Two additional labels are included in the package, one for 3 hours duration (180) and one for 8 hour duration (480).
Depending on the selected duration, the installer must cover the default 1 hour (60) printing with one that has the
required duration. Please take notice of the orientation of the label.
The control of maintained or non maintained operation of the luminary is achieved through Switch 4 of DS1. For
maintained operation, switch number 4 must be in ON position. For non-maintained operation,switch number 4
must be in OFF position.
Honeywell Life Safety AS
http://www.hls-nordic.com
Po. Box 3514, N-3007 Drammen, Norway