STRYKER CVAHU ZIO CONFIGURATION GUIDE
43
Figure 77: Parameter Cnfg In Occ Snsr
OCC SNSP:
Displays and allows modification of
logical input configuration /terminal assignment for
occupancy sensor. This can be changed as UI 1, UI
2, UI 3, UI 4, UI 5, UI 6, DI 1, DI 2, DI 3, DI 4, and
UNDEFINED
Default Parameter setting:
UNDEFINED.
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
47 = DI 1
48 = DI 2
49 = DI 3
50 = DI 4
255 = UNDEFINED
Figure 78: Parameter Cnfg In Window
WINDOW:
Displays and allows modification of logical
input configuration /terminal assignment for window
contacts. This can be changed as UI 1, UI 2, UI 3, UI
4, UI 5, UI 6, DI 1, DI 2, DI 3, DI 4, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
47 = DI 1
48 = DI 2
49 = DI 3
50 = DI 4
255 = UNDEFINED