STRYKER CVAHU ZIO CONFIGURATION GUIDE
28
Override
(CVAHU override used for fan)
Figure 35: Parameter Override Fan Ovrd
FAN OVRD:
Displays and allows modification of
supply fan override command as ON, OFF or
UNDEFINED.
Default configuration:
UNDEFINED
Configuration settings in program are as follows:
0 = OFF, 1 = ON, 255 = UNDEFINED
Alarms
(CVAHU parameter alarms)
Figure 36: Parameter Alarms Emrg Ovrd
EMRG OVRD:
Displays smoke detector status as
TRUE, FALS or UNDEFINED.
Configuration settings in program are as follows:
0 = FALS, 1 = TRUE, 255 = UNDEFINED
Figure 37: Parameter Alarms Clg Ovrd
CLG OVRD:
Displays cooling override status as
TRUE, FALS or UNDEFINED.
Configuration settings in program are as follows:
0 = FALS, 1 = TRUE, 255 = UNDEFINED