STRYKER CVAHU ZIO CONFIGURATION GUIDE
40
Cnfg In
(Configuration of CVAHU inputs)
Figure 71: Parameter Cnfg In Spe Temp
SPC TEMP:
Displays and allows modification of
logical input configuration /terminal assignment for
space temperature. This can be changed as UI 1, UI
2, UI 3, UI 4, UI 5, UI 6, ZIO, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
7 = ZIO
255 = UNDEFINED
Figure 72: Parameter Cnfg In Spe Rh
SPC RH:
Displays and allows modification of logical
input configuration /terminal assignment for space
relative humidity. This can be changed as UI 1, UI 2,
UI 3, UI 4, UI 5, UI 6, ZIO, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
7 = ZIO
255 = UNDEFINED