STRYKER CVAHU ZIO CONFIGURATION GUIDE
41
Figure 73: Parameter Cnfg In Spe CO
2
SPC CO
2
:
Displays and allows modification of logical
input configuration /terminal assignment for space
CO
2
. This can be changed as: UI 1, UI 2, UI 3, UI 4,
UI 5, UI 6, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
255 = UNDEFINED
Figure 74: Parameter Cnfg In Dischair
DISCHAIR:
Displays and allows modification of
logical input configuration /terminal assignment for
discharge air temperature. This can be changed as:
UI 1, UI 2, UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10,
SB11, SB12, and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
21 = SB8 (C7400s temperature bus Address = 8)
22 = SB9 (C7400s temperature bus Address = 9)
23 = SB10 (C7400s temperature bus Address = 10)
24 = SB11 (C7400s temperature bus Address = 11)
25 = SB12 (C7400s temperature bus Address = 12)
255 = UNDEFINED
Note:
1. Up to 5 Sbus sensor are supported. The
Sbus address is fixed and the configuration
enables addresses 8 through 12.
2. Bus address = DIPswi 8
3. Sbus address is fixed
Sensor #
Bus Address
DIP SW 123
0
8
000
1
9
100
2
10
010
3
11
110
4
12
001