STRYKER CVAHU ZIO CONFIGURATION GUIDE
42
Figure 75: Parameter Cnfg In Mixedair
MIXEDAIR:
Displays and allows modification of
logical input configuration /terminal assignment for
mixed air temperature. This can be changed as UI 1,
UI 2, UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10, SB11,
SB12, and UNDEFINED
Default Parameter setting:
UNDEFINED.
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
21 = SB8 (C7400s temperature bus Address = 8)
22 = SB9 (C7400s temperature bus Address = 9)
23 = SB10 (C7400s temperature bus Address = 10)
24 = SB11 (C7400s temperature bus Address = 11)
25 = SB12 (C7400s temperature bus Address = 12)
255 = UNDEFINED
Figure 76: Parameter Cnfg In Od Temp
OD TEMP:
Displays and allows modification of logical
input configuration /terminal assignment for outside
air temperature. This can be changed as UI 1, UI 2,
UI 3, UI 4, UI 5, UI 6, SB8, SB9, SB10, SB11, SB12,
and UNDEFINED.
Default Parameter setting:
UNDEFINED
Configuration settings in program are as follows:
0 = UI 1
1 = UI 2
2 = UI 3
3 = UI 4
4 = UI 5
5 = UI 6
21 = SB8 (C7400s temperature bus Address = 8)
22 = SB9 (C7400s temperature bus Address = 9)
23 = SB10 (C7400s temperature bus Address = 10)
24 = SB11 (C7400s temperature bus Address = 11)
25 = SB12 (C7400s temperature bus Address = 12)
255 = UNDEFINED