31-00083—02
18
Wiring Method
NOTE:
When attaching two or more wires to the same
terminal, other than 14 AWG (2.0 sq mm), be sure to twist
them together. Deviation from this rule can result in improper
electrical contact (see Fig. 17). Each terminal can
accommodate the following gauges of wire:
• Single wire: from 22 AWG to 14 AWG solid or stranded
• Multiple wires: up to two 18 AWG stranded, with 1/4 watt
wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire in the
required terminal location and tighten the screw.
3. If two or more wires are being inserted into one terminal
location, twist the wires together a minimum of three turns
before inserting them (see Fig. 17).
4. Cut the twisted end of the wires to 3/16 in. (5 mm) before
inserting them into the terminal and tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection.
Fig. 17. Attaching two or more wires at terminal blocks.
Wiring Details
Each controller is shipped with the digital outputs, which
switch the 24 Vac to the load (High Side). The three analog
outputs (AO) are used to control modulating heating, cooling
and economizer equipment. Any AO may be used as a digital
output, as follows:
• False (0%) produces 0 Vdc, (0 mA)
• True (100%) produces the maximum 11 Vdc (22 mA)
The wiring connection terminals described in Table 10 are
shown in Fig. 19 and Fig. 20 on page 20 and 20.
Table 10. Description of wiring terminal connections.
1/2
(13)
STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
1.
2.
TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3.
CUT TWISTED END OF WIRES TO 3/16 IN. (5 MM)
BEFORE INSERTING INTO TERMINAL AND
TIGHTENING SCREW. THEN PULL ON EACH
WIRE IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M17207A
Terminal
Label
Connection
INPUT POWER & GROUND
1
24 Vac
24 Vac Power
2
24 Vac COM
24 Vac Power
3
EGND
Earth Ground
4
20Vdc
20 Vdc Power
5
SBUS 1
Sylk
6
SBUS 2
Sylk
NETWORK CONNECTIONS
7
NET-1
L
ON
W
ORKS
® communications
8
NET-2
L
ON
W
ORKS
® communications
DIGITAL OUTPUTS
a
9
DO-3
Digital Output
10
COM
Common
11
DO-4
Digital Output
12
COM
Common
13
DO-1
Digital Output
14
DO-2
Digital Output
15
COM
Common
ANALOG OUTPUTS
b
16
AO-1
Analog Output
17
COM
Common
18
AO-2
Analog Output
UNIVERSAL INPUTS
19
UI-1
Universal Input
20
COM
Common
21
UI-2
Universal Input
22
UI-3
Universal Input
23
COM
Common
24
UI-4
Universal Input
a
For the CVL4022AS controller ONLY, terminals 9-12 (DO3, DO4, &
COM) are not present. The actuator is internally hardwired to these ter-
minals.
b
Analog outputs may be configured as digital outputs and operate as
follows:
– False (0%) produces 0 Vdc, (0 mA)
– True (100%) produces the maximum 11 Vdc (22 mA)