85
31-00083—02
fan_output
If a fan is configured as one speed, This value is 100 percent, when the fan is
running and is zero when the fan is not running. If a modulating fan is configured,
reports the fan speed in percentage.
0 – 100%
in_alarm
0 - Means there is no application alarm.
Not 0 - Means there is an application alarm
nvoVelSenPress
SNVT
press_f
The calibrated value of the cooling airflow pressure sensor. The sensor value minus
the offset value.
-0.0494
≤
range
≤
1.5833 inWc
nvoWindow
aka
nvoEnergyHoldOff
SNVT
switch
This network output allows the
hard wired window sensor
to be used by other
nodes on the network.
The valid states are described below:
Table 22. Network Variable - Outputs (Continued)
Nv/field
Net Data Type
Description
State
Value
Meaning
SW_OFF
0
Window closed
SW_ON
100%
Window open
SW_NUL
0
Window sensor not configured