31-00083—02
90
DeadBand
Speed
fpm
20
fpm
The flow control deadband. This is configured based on the
damper motor speed. Since airflow control is implemented in face
velocity, the deadband is in feet per minute.
Floating Actuators
Proportional Actuators
Notes:
Proportional actuators not recommended for pressure
independent airflow control.
0
≤
range < TR
≤
5000 fpm
Precision: 0
MaxAoChg
SNVT
lev_percent
1.15
%
The flow control maximum analog output change per second. This
is configured based on the damper motor speed.
0.01
≤
range
≤
100%
Precision: 3
MinAoChg
SNVT
lev_percent
0.11
%
Minimum output change per second.
default value is 0.11 pct
0
≤
range
≤
100%
Precision: 3
EnableLowFlowAlm
ubyte
1
Enable low airflow alarm.
0: disable low aiiflow alarm
1: enable low airflow alarm
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description
Motor Speed
(sec)
Deadband (fpm)
15
125
30
65
60
30
90
20
180
20
420
20
Model Number Deadband (fpm)
ML7174
460
ML7284
260
ML7475
330
MN7505
45
MN7510
45
Motor Speed
(sec)
maxAOchg
per second
15
1.15
30
1.15
60
1.15
90
1.15
180
0.56
420
0.24