31-00083—02
92
TrackModeOffset
SNVT
flow_f
0
cfm Flow tracking offset. This value is used when the
FlowControlType = FlowTracking
The temperature control is turned off and the
airflowSP = FlowT TrackModeOffset
-138850
≤
range
≤
138850 cfm
Precision: 0
Notes:
The current version of Spyder Tool does not support negative
values for InternalDataType = cfm
HtgLockout
SNVT
flow
0
cfm
nciFreshAirRqd
SNVT
flow
0
cfm This is the amount of fresh air required for this zone during
scheduled occupancy.
0
≤
range
≤
138850 cfm
Precision: 0
nciHeat
Reheat
ubyte
0
Reheat output configuration.
Used to Tune the heating PID control loop and set the stages of
the Cycler.
0: cooling only
1: one stage reheat
2: two stage reheat
3: three stage reheat
10: modulating reheat output
range: 0, 1, 2, 3, 10
ReheatControl
ubyte
1
Reheat airflow control
0: The Reheat airflow or damper position is set to a fixed position
1: ReHeat airflow and damper Position varies (between minimum
position and fixed reheat) according to the temperature control
loop.
HeatSeq
ubyte
0
Heating sequence.
0: reheat only
1: peripheral then reheat.
2: reheat then peripheral
3: reheat & peripheral then reheat airflow. At the end of the
sequence, reheat airflow is modulated with heating demand or
constant based on the ReheatControl value.
0: fixed airflow at maxReheatFlow
1: modulated airflow up to maxReheatFlow
Note: Sequence #3 is not appropriate for electric reheat coils.
4: peripheral only.
PeriphMinPos
SNVT
lev_percent
0
% sets the minimum peripheral Heat modulating valve Position. This
feature allows the user to maintain flow in pipes that may
otherwise freeze. If the outdoor air temperature value is connected
to the zone terminal, the minimum position is active when the
outdoor air temperature is below 40F.
0
≤
range
≤
100%
Precision: 1
Table 23. Configuration Parameters (Continued)
NCI/Field
Net Data
Type
Default
Val
AP
Internal
Units
Description
Flow Control
Fixed Reheat Position
Pressure dependent
nciFlowSP.ReheatFlowPos
Pressure independent
nciMaxReheatFlow